 "manufacturer": "Senva",
 "manufacturer_slug": "senva",
 "model": "EM-RS485 networked energy meter (Modbus RTU/ASCII)",
 "model_slug": "em-rs485",
 "short_model": "EM-RS485",
 "aliases": [
  "EM-RS485",
  "Senva EM-RS485",
  "Senva protocol energy meter"
 ],
 "equipment_type": "Energy meter",
 "applies_to": "Senva EM-RS485 three-phase energy meters with Senva CVT sensors, firmware v1.1.2, Modbus Protocol Guide 154-0023-0B (2017-04-10).",
 "summary": "The Senva EM-RS485 is a compact three-phase energy meter that reads Senva current/voltage transducers (CVTs) and talks Modbus RTU, Modbus ASCII or BACnet MS/TP on RS-485 with auto-detected line settings. Measurements are IEEE floats in holding registers: system and per-phase voltage, current, power factor, real/reactive/apparent power, energy, demand, plus condition flags. This map covers the main reading and setup registers.",
 "transport": [
  "RTU",
  "ASCII"
 ],
 "defaults": {
  "unit_id": null,
  "baud": null,
  "parity": null,
  "data_bits": null,
  "stop_bits": null,
  "tcp_port": null
 },
 "addressing": {
  "convention": "0-based",
  "note": "The guide prints raw protocol addresses with an R prefix (R420 = wire address 420; Modicon 40421). R420/21 marks a two-register value starting at 420. S phase registers are R phase + 1000, T phase + 2000."
 },
 "default_word_order": "ABCD",
 "firmware": "v1.1.2",
 "source": {
  "title": "EM-RS485 Modbus Protocol Guide",
  "doc_number": "154-0023-0B",
  "revision_date": "2017-04-10",
  "url": "https://senvainc.com/catalog/documents/downloadcenter/EM-RS485%20Modbus%20Protocol%20Guide.pdf",
  "pages": "pp. 6-8 (configuration), 8-38 (registers), 39 (data types and UINT32 byte example)"
 },
 "notes": [
  "Word order: the data-types section says UINT32 and FLOAT use two registers in network byte order and gives byte examples (0xAABBCCDD sent as AA BB CC DD across registers r and r+1), so the high word comes first (ABCD).",
  "Units are settable: power follows R163 (default kW), energy R173 (default kWh), temperature R133 (default °F), angles R153 (default degrees). The units listed here are the defaults.",
  "Energy registers (R700-R765, R1700-R1765) read as floats by default; with R170 = 1 they read as unsigned integers 0-999999 that wrap. They are listed as FLOAT32 here (the default).",
  "Most analog measurements also have Instantaneous, Minimum, Maximum and Average copies in the next registers (for example R422 instantaneous, R424 min, R426 max, R428 average for R420); those copies are not listed. Writing 0 resets a statistic.",
  "Default slave address is 100 plus the last two digits of the serial number. Baud (9600-115200), parity, data bits and protocol are auto-detected out of the box.",
  "Strings (CVT serial/model, location) and the remaining PowerPrint, pulse-input and multiplier settings are left out for length."
 ],
 "registers": [
  {
   "table": "holding_register",
   "address": 102,
   "documented": "R102",
   "name": "Reset reason",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 103,
   "documented": "R103",
   "name": "Reset count",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 104,
   "documented": "R104/05",
   "name": "Up time",
   "description": "Time since last reset.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "s",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 111,
   "documented": "R111",
   "name": "Identify meter",
   "description": "Flash LEDs to find the meter (BOOL).",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Inactive",
    "1": "Active (all LEDs blink green)"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 122,
   "documented": "R122",
   "name": "RS485 protocol",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "1": "Auto",
    "2": "BACnet",
    "3": "Modbus RTU",
    "4": "Modbus ASCII",
    "5": "BACnet + Modbus RTU",
    "6": "BACnet + Modbus ASCII",
    "7": "Modbus RTU + ASCII",
    "8": "Any protocol"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 123,
   "documented": "R123",
   "name": "Slave address",
   "description": "1-254; also answers global address 255.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 124,
   "documented": "R124/25",
   "name": "RS485 baud rate",
   "description": "1200-460800; writing it turns auto-baud off.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "baud",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 126,
   "documented": "R126",
   "name": "RS485 parity",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "1": "Auto",
    "2": "None",
    "3": "Odd",
    "4": "Even"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 127,
   "documented": "R127",
   "name": "RS485 data bits",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "1": "Auto",
    "2": "7 bits",
    "3": "8 bits"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 128,
   "documented": "R128",
   "name": "RS485 stop bits",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "1": "Auto",
    "2": "1 bit",
    "3": "1.5 bits",
    "4": "2 bits"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 133,
   "documented": "R133",
   "name": "Temperature units",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "1": "°F",
    "2": "°C"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 153,
   "documented": "R153",
   "name": "Angle units",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "1": "Degrees",
    "2": "Radians"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 161,
   "documented": "R161",
   "name": "System phase selection",
   "description": "Which phases make up system totals.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "1": "3 phase",
    "2": "R and S",
    "3": "S and T",
    "4": "R and T"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 163,
   "documented": "R163",
   "name": "Power units",
   "description": "Reactive and apparent power follow the same scale.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "1": "kW",
    "2": "W",
    "3": "MW"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 170,
   "documented": "R170",
   "name": "Energy data type",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Floating point",
    "1": "Unsigned integer 0-999999 (wraps)"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 173,
   "documented": "R173",
   "name": "Energy units",
   "description": "Reactive and apparent energy follow the same scale.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "1": "kWh",
    "2": "Wh",
    "3": "MWh"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 194,
   "documented": "R194",
   "name": "Energy reset count",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 200,
   "documented": "R200",
   "name": "Setup button",
   "description": "Reads 1 while the button is pressed.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 201,
   "documented": "R201",
   "name": "Binary input 1",
   "description": "Stable state of pulse input 1 (input is active low).",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 202,
   "documented": "R202",
   "name": "Binary input 2",
   "description": "Stable state of pulse input 2 (input is active low).",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 210,
   "documented": "R210/11",
   "name": "Pulse input 1 count",
   "description": "",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 220,
   "documented": "R220/21",
   "name": "Pulse input 2 count",
   "description": "",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 310,
   "documented": "R310/11",
   "name": "Temperature",
   "description": "Meter ambient temperature; unit set by R133 (default °F).",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "°F / °C",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 380,
   "documented": "R380/81",
   "name": "Power supply voltage",
   "description": "Internal supply voltage after rectification.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "V",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 400,
   "documented": "R400",
   "name": "Active system conditions",
   "description": "",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "5": "Mismatched voltage",
    "6": "Reverse RST order",
    "7": "Not 3-phase",
    "12": "Frequency drift",
    "15": "Phase drift"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 401,
   "documented": "R401",
   "name": "Previous system conditions",
   "description": "Latched copy of R400; write 0 to clear.",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": {
    "5": "Mismatched voltage",
    "6": "Reverse RST order",
    "7": "Not 3-phase",
    "12": "Frequency drift",
    "15": "Phase drift"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 410,
   "documented": "R410/11",
   "name": "Line frequency",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "Hz",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 420,
   "documented": "R420/21",
   "name": "Phase average RMS voltage",
   "description": "Average of valid phases.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "V",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 450,
   "documented": "R450/51",
   "name": "Phase-to-phase average RMS voltage",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "V",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 520,
   "documented": "R520/21",
   "name": "Phase average RMS current",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "A",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 540,
   "documented": "R540/41",
   "name": "Phase average current angle",
   "description": "Unit set by R153.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "deg / rad",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 550,
   "documented": "R550/51",
   "name": "System power factor",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 600,
   "documented": "R600/01",
   "name": "Total real power",
   "description": "Unit set by R163 (default kW).",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "kW",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 610,
   "documented": "R610/11",
   "name": "Phase average real power",
   "description": "Unit set by R163.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "kW",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 620,
   "documented": "R620/21",
   "name": "Net real power",
   "description": "Negative = net export. Unit set by R163.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "kW",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 640,
   "documented": "R640/41",
   "name": "Total reactive power",
   "description": "Unit follows R163 (default kVAR).",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "kVAR",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 660,
   "documented": "R660/61",
   "name": "Total apparent power",
   "description": "Unit follows R163 (default kVA).",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "kVA",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 700,
   "documented": "R700/01",
   "name": "Total real energy",
   "description": "Unit set by R173 (default kWh); type per R170.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "kWh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 702,
   "documented": "R702/03",
   "name": "Total real energy import",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "kWh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 704,
   "documented": "R704/05",
   "name": "Total real energy export",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "kWh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 706,
   "documented": "R706/07",
   "name": "Total real energy net",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "kWh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 720,
   "documented": "R720/21",
   "name": "System real energy",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "kWh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 722,
   "documented": "R722/23",
   "name": "System real energy import",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "kWh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 724,
   "documented": "R724/25",
   "name": "System real energy export",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "kWh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 740,
   "documented": "R740/41",
   "name": "Total reactive energy",
   "description": "Unit follows R173 (default kVARh).",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "kVARh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 760,
   "documented": "R760/61",
   "name": "Total apparent energy",
   "description": "Unit follows R173 (default kVAh).",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "kVAh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 800,
   "documented": "R800/01",
   "name": "Demand real power",
   "description": "Current demand window. Unit per R163.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "kW",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 806,
   "documented": "R806/07",
   "name": "Maximum demand real power",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "kW",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 840,
   "documented": "R840/41",
   "name": "Demand reactive power",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "kVAR",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 860,
   "documented": "R860/61",
   "name": "Demand apparent power",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "kVA",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1102,
   "documented": "R1102",
   "name": "R phase CVT present",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "No",
    "1": "Yes"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1103,
   "documented": "R1103",
   "name": "R phase CVT status",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "1": "No CVT",
    "2": "No error",
    "3": "Detection error",
    "4": "Communication error",
    "5": "Configuration error",
    "6": "Version error",
    "7": "Technology error"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1140,
   "documented": "R1140/41",
   "name": "R phase CVT voltage rating",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "V",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1150,
   "documented": "R1150/51",
   "name": "R phase CVT current rating",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "A",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1152,
   "documented": "R1152/53",
   "name": "R phase current multiplier",
   "description": "Default 1.0.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1400,
   "documented": "R1400",
   "name": "R phase active conditions",
   "description": "",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "0": "Sensor fault",
    "1": "No load",
    "2": "Negative power",
    "3": "Phase loss",
    "4": "Bad frequency",
    "5": "Low power factor",
    "6": "Over current",
    "7": "Over voltage",
    "8": "High harmonics",
    "9": "Unexpected sensor",
    "10": "Missing sensor",
    "11": "Surge voltage",
    "13": "Brown-out voltage"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1401,
   "documented": "R1401",
   "name": "R phase previous conditions",
   "description": "Write 0 to clear.",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": {
    "0": "Sensor fault",
    "1": "No load",
    "2": "Negative power",
    "3": "Phase loss",
    "4": "Bad frequency",
    "5": "Low power factor",
    "6": "Over current",
    "7": "Over voltage",
    "8": "High harmonics",
    "9": "Unexpected sensor",
    "10": "Missing sensor",
    "11": "Surge voltage",
    "13": "Brown-out voltage"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1420,
   "documented": "R1420/21",
   "name": "R phase RMS voltage",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "V",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1450,
   "documented": "R1450/51",
   "name": "R phase-to-phase RMS voltage",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "V",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1520,
   "documented": "R1520/21",
   "name": "R phase RMS current",
   "description": "Includes current multiplier; always positive.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "A",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1540,
   "documented": "R1540/41",
   "name": "R phase current angle",
   "description": "Unit set by R153.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "deg / rad",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1550,
   "documented": "R1550/51",
   "name": "R phase power factor",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1600,
   "documented": "R1600/01",
   "name": "R phase real power",
   "description": "Unit per R163.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "kW",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1640,
   "documented": "R1640/41",
   "name": "R phase reactive power",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "kVAR",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1660,
   "documented": "R1660/61",
   "name": "R phase apparent power",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "kVA",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1700,
   "documented": "R1700/01",
   "name": "R phase total real energy",
   "description": "Unit per R173; type per R170.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "kWh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1740,
   "documented": "R1740/41",
   "name": "R phase total reactive energy",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "kVARh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1760,
   "documented": "R1760/61",
   "name": "R phase total apparent energy",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "kVAh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1800,
   "documented": "R1800/01",
   "name": "R phase demand real power",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "kW",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2103,
   "documented": "R2103",
   "name": "S phase CVT status",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "1": "No CVT",
    "2": "No error",
    "3": "Detection error",
    "4": "Communication error",
    "5": "Configuration error",
    "6": "Version error",
    "7": "Technology error"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2400,
   "documented": "R2400",
   "name": "S phase active conditions",
   "description": "",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "0": "Sensor fault",
    "1": "No load",
    "2": "Negative power",
    "3": "Phase loss",
    "4": "Bad frequency",
    "5": "Low power factor",
    "6": "Over current",
    "7": "Over voltage",
    "8": "High harmonics",
    "9": "Unexpected sensor",
    "10": "Missing sensor",
    "11": "Surge voltage",
    "13": "Brown-out voltage"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2420,
   "documented": "R2420/21",
   "name": "S phase RMS voltage",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "V",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2520,
   "documented": "R2520/21",
   "name": "S phase RMS current",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "A",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2550,
   "documented": "R2550/51",
   "name": "S phase power factor",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2600,
   "documented": "R2600/01",
   "name": "S phase real power",
   "description": "Unit per R163.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "kW",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2700,
   "documented": "R2700/01",
   "name": "S phase total real energy",
   "description": "Unit per R173.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "kWh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 3103,
   "documented": "R3103",
   "name": "T phase CVT status",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "1": "No CVT",
    "2": "No error",
    "3": "Detection error",
    "4": "Communication error",
    "5": "Configuration error",
    "6": "Version error",
    "7": "Technology error"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 3400,
   "documented": "R3400",
   "name": "T phase active conditions",
   "description": "",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "0": "Sensor fault",
    "1": "No load",
    "2": "Negative power",
    "3": "Phase loss",
    "4": "Bad frequency",
    "5": "Low power factor",
    "6": "Over current",
    "7": "Over voltage",
    "8": "High harmonics",
    "9": "Unexpected sensor",
    "10": "Missing sensor",
    "11": "Surge voltage",
    "13": "Brown-out voltage"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 3420,
   "documented": "R3420/21",
   "name": "T phase RMS voltage",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "V",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 3520,
   "documented": "R3520/21",
   "name": "T phase RMS current",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "A",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 3550,
   "documented": "R3550/51",
   "name": "T phase power factor",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 3600,
   "documented": "R3600/01",
   "name": "T phase real power",
   "description": "Unit per R163.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "kW",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 3700,
   "documented": "R3700/01",
   "name": "T phase total real energy",
   "description": "Unit per R173.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "kWh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  }
 ],
 "integration": {
  "summary": "Connect RS-485 to an active Modbus master and let the meter auto-detect the line, then read the float pairs at R600 (total kW), R700 (kWh), R420 (V) and R520 (A) with function 03.",
  "minimum_registers": [
   {
    "table": "holding_register",
    "address": 600,
    "why": "Total real power"
   },
   {
    "table": "holding_register",
    "address": 700,
    "why": "Total real energy"
   },
   {
    "table": "holding_register",
    "address": 420,
    "why": "Average voltage"
   },
   {
    "table": "holding_register",
    "address": 520,
    "why": "Average current"
   },
   {
    "table": "holding_register",
    "address": 550,
    "why": "Power factor"
   },
   {
    "table": "holding_register",
    "address": 410,
    "why": "Frequency"
   },
   {
    "table": "holding_register",
    "address": 400,
    "why": "System condition flags"
   }
  ],
  "enable": "Modbus is on by default (protocol Auto). Lock baud/parity/protocol with R122-R128 for permanent installations.",
  "watchdog": null,
  "quirks": [
   "Read and write both registers of a 32-bit value together.",
   "Units change with R163/R173/R133/R153; check them before scaling.",
   "The meter answers the global address 255 as well as its own address."
  ],
  "setup": [
   "Default address = 100 + last two digits of the serial number.",
   "Hold the Setup button while powering up to clear learned line settings."
  ],
  "gotchas": [
   "Writing a new baud rate cuts communication until the master matches it.",
   "On a mixed-baud network auto-detection is unpredictable; set the line settings manually."
  ]
 },
 "page": "https://easymodbus.com/modbus-register-maps/senva/em-rs485",
 "address_note": "address = 0-based Modbus wire (PDU) address; documented = as printed in the source.",
 "note": "Re-typed from the manufacturer's public documentation (see source) and verified against it. Registers vary by firmware and options; verify against the live device before writing."
}