 "manufacturer": "Senva",
 "manufacturer_slug": "senva",
 "model": "TG series toxic/combustible gas monitor (RS-485 Modbus)",
 "model_slug": "tg-gas-monitor",
 "short_model": "TG",
 "aliases": [
  "Senva TG",
  "TG series"
 ],
 "equipment_type": "Sensor (gas detector)",
 "applies_to": "Senva TG series RS-485 gas monitors (one or two gas sensors, optional temperature), Modbus Protocol Guide 154-0036-0A (2020-02-07).",
 "summary": "The Senva TG is a wall-mount gas monitor with one or two gas sensors, a fan relay, an alarm relay and a buzzer, plus an RS-485 port that auto-detects BACnet MS/TP, Modbus RTU or Modbus ASCII. All data is in holding registers. This map covers communication setup, units, setpoints and hysteresis, sensor life and status, system state, relay and buzzer control, and the gas, temperature and supply-voltage readings with their statistics.",
 "transport": [
  "RTU",
  "ASCII"
 ],
 "defaults": {
  "unit_id": null,
  "baud": null,
  "parity": null,
  "data_bits": null,
  "stop_bits": null,
  "tcp_port": null
 },
 "addressing": {
  "convention": "0-based",
  "note": "The guide prints raw protocol addresses prefixed with R (R320 = address 320); in Modicon notation that is 40321. 'R320/21' is a 2-register value starting at 320."
 },
 "default_word_order": "ABCD",
 "firmware": null,
 "source": {
  "title": "TG Modbus Protocol Guide",
  "doc_number": "154-0036-0A",
  "revision_date": "2020-02-07",
  "url": "https://www.zotsupply.com/content/PDFs/Senva/Gas%20Monitoring/154-0036-0A.pdf",
  "unofficial": true,
  "pages": "register index pp. 2-3; configuration p. 5; register details pp. 7-19; data types p. 20"
 },
 "notes": [
  "Source host: the unaltered Senva guide hosted by a distributor; we did not find it on Senva's own site.",
  "Word order: the guide says UINT32 and FLOAT use two registers in full network byte order, MSB first, and gives UINT32 byte examples, so high word first (ABCD).",
  "BOOL registers are listed as UINT16 with 0/1 values. The default slave address is 100 plus the last two digits of the serial number; baud, parity and data bits are auto-detected by default.",
  "Gas concentrations are FLOAT values; the guide gives setpoint defaults in ppm but does not print a unit on the concentration registers.",
  "The source prints inconsistent value codes for R201 (4-8 for sensor 2 status) and R230 (4/5 for the alarm relay), so no value table is given for them.",
  "Left out: User Data R294-301 (free storage) and Sensor calibration registers mentioned but not listed (R156, R166)."
 ],
 "registers": [
  {
   "table": "holding_register",
   "address": 102,
   "documented": "R102",
   "name": "Reset status",
   "description": "Reason for the last reset.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "1": "Configuration reset",
    "3": "Power loss",
    "5": "Hardware watchdog"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 103,
   "documented": "R103",
   "name": "Reset count",
   "description": "Lifetime count of firmware resets.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 104,
   "documented": "R104",
   "name": "Up time",
   "description": "Time since last reset.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "s",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 111,
   "documented": "R111",
   "name": "Identify device",
   "description": "LEDs light and LCD blinks the address while active.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Inactive",
    "1": "Active"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 112,
   "documented": "R112",
   "name": "Auto protocol",
   "description": "Default active.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Inactive",
    "1": "Active"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 113,
   "documented": "R113",
   "name": "Auto MAC (slave) address",
   "description": "Default active.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Inactive",
    "1": "Active"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 114,
   "documented": "R114",
   "name": "Auto baud rate",
   "description": "Default active.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Inactive",
    "1": "Active"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 115,
   "documented": "R115",
   "name": "Auto parity",
   "description": "Default active.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Inactive",
    "1": "Active"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 116,
   "documented": "R116",
   "name": "Auto data bits",
   "description": "Default active.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Inactive",
    "1": "Active"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 117,
   "documented": "R117",
   "name": "Auto stop bits",
   "description": "Default active.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Inactive",
    "1": "Active"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 118,
   "documented": "R118",
   "name": "Buzzer override",
   "description": "Forces the buzzer regardless of state.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Inactive",
    "1": "Active"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 122,
   "documented": "R122",
   "name": "RS485 protocol",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "1": "Auto",
    "2": "BACnet",
    "3": "Modbus RTU",
    "4": "Modbus ASCII",
    "5": "BACnet and Modbus RTU",
    "6": "BACnet and Modbus ASCII",
    "7": "Modbus RTU and ASCII",
    "8": "Any protocol"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 123,
   "documented": "R123",
   "name": "Slave address",
   "description": "1-254 (use 1-247); also answers to 255.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 124,
   "documented": "R124",
   "name": "RS485 baud rate",
   "description": "1200-460800. Writing turns auto baud off; no remote way back.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 126,
   "documented": "R126",
   "name": "RS485 parity",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "1": "Auto",
    "2": "No parity",
    "3": "Odd parity",
    "4": "Even parity"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 127,
   "documented": "R127",
   "name": "RS485 data bits",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "1": "Auto",
    "2": "7 bits",
    "3": "8 bits"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 128,
   "documented": "R128",
   "name": "RS485 stop bits",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "1": "Auto",
    "2": "1 bit",
    "3": "1.5 bits",
    "4": "2 bits"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 133,
   "documented": "R133",
   "name": "Temperature units",
   "description": "Default °F.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "1": "Degrees Fahrenheit",
    "2": "Degrees Celsius"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 134,
   "documented": "R134",
   "name": "Smoothed temperature response time",
   "description": "Default 30 s.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "s",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 135,
   "documented": "R135",
   "name": "Gas 1 response time",
   "description": "Default 10 s.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "s",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 136,
   "documented": "R136",
   "name": "Gas 2 response time",
   "description": "Default 10 s.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "s",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 150,
   "documented": "R150",
   "name": "Sensor 1 warning setpoint",
   "description": "Gas level for the Warning state.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 152,
   "documented": "R152",
   "name": "Sensor 1 alarm setpoint",
   "description": "Gas level for the Alarm state.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 154,
   "documented": "R154",
   "name": "Sensor 1 hysteresis",
   "description": "Default 0.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 158,
   "documented": "R158",
   "name": "Sensor 1 life",
   "description": "Remaining sensor life; starts at 1825.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "days",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 160,
   "documented": "R160",
   "name": "Sensor 2 warning setpoint",
   "description": "Default 1.0 ppm.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 162,
   "documented": "R162",
   "name": "Sensor 2 alarm setpoint",
   "description": "Default 3.0 ppm.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 164,
   "documented": "R164",
   "name": "Sensor 2 hysteresis",
   "description": "Default 0.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 168,
   "documented": "R168",
   "name": "Sensor 2 life",
   "description": "Remaining sensor life; starts at 1825.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "days",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 170,
   "documented": "R170",
   "name": "Current system state",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "1": "Normal",
    "2": "Warning",
    "3": "Alarm",
    "4": "Extended alarm"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 190,
   "documented": "R190",
   "name": "System configuration reset",
   "description": "Write 9699690 to restore factory defaults (address and serial settings too).",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "",
   "access": "W",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 192,
   "documented": "R192",
   "name": "System statistics reset",
   "description": "Write 4765089 to reset min/max/average statistics.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "",
   "access": "W",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 195,
   "documented": "R195",
   "name": "Auto reset statistics",
   "description": "When active, reading a statistic also resets it.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Inactive",
    "1": "Active"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 196,
   "documented": "R196",
   "name": "Sensor 1 pulse status",
   "description": "Pulse health check for electrochemical sensors.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Inactive",
    "1": "Active"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 197,
   "documented": "R197",
   "name": "Sensor 2 pulse status",
   "description": "Pulse health check for electrochemical sensors.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Inactive",
    "1": "Active"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 200,
   "documented": "R200",
   "name": "Sensor 1 sensor status",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "No fault detected",
    "1": "No sensor",
    "2": "Over range",
    "3": "Under range",
    "7": "Unreliable other"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 201,
   "documented": "R201",
   "name": "Sensor 2 sensor status",
   "description": "Value coding printed inconsistently in the source (see notes).",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 210,
   "documented": "R210",
   "name": "Fan relay",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "1": "Inactive",
    "2": "Active"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 211,
   "documented": "R211",
   "name": "Fan relay override",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "1": "System",
    "2": "Inactive",
    "3": "Active"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 212,
   "documented": "R212",
   "name": "Fan maximum off time",
   "description": "0 = ignored.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "s",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 214,
   "documented": "R214",
   "name": "Fan minimum on time",
   "description": "Default 60 s.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "s",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 216,
   "documented": "R216",
   "name": "Fan minimum off time",
   "description": "Default 60 s.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "s",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 218,
   "documented": "R218",
   "name": "Fan state count",
   "description": "Transitions since restart; write 0 to reset.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 220,
   "documented": "R220",
   "name": "Fan total active time",
   "description": "Since restart; write 0 to reset.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "s",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 230,
   "documented": "R230",
   "name": "Alarm relay",
   "description": "Value coding printed inconsistently in the source (see notes).",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 231,
   "documented": "R231",
   "name": "Alarm relay override",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "1": "System",
    "2": "Inactive",
    "3": "Active"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 232,
   "documented": "R232",
   "name": "Alarm maximum off time",
   "description": "0 = ignored.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "s",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 234,
   "documented": "R234",
   "name": "Alarm minimum on time",
   "description": "Default 60 s.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "s",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 236,
   "documented": "R236",
   "name": "Alarm minimum off time",
   "description": "Default 60 s.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "s",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 238,
   "documented": "R238",
   "name": "Alarm state count",
   "description": "Transitions since restart; write 0 to reset.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 240,
   "documented": "R240",
   "name": "Alarm total active time",
   "description": "Since restart; write 0 to reset.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "s",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 250,
   "documented": "R250",
   "name": "Alarm buzzer",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "1": "Inactive",
    "2": "Active"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 251,
   "documented": "R251",
   "name": "Alarm buzzer override",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "1": "System",
    "2": "Inactive",
    "3": "Active"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 252,
   "documented": "R252",
   "name": "Buzzer delay",
   "description": "Delay after entering Alarm; default 1800 s.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "s",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 254,
   "documented": "R254",
   "name": "Buzzer minimum on time",
   "description": "Default 0 s.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "s",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 256,
   "documented": "R256",
   "name": "Buzzer minimum off time",
   "description": "Default 0 s.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "s",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 258,
   "documented": "R258",
   "name": "Buzzer state count",
   "description": "Transitions since restart; write 0 to reset.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 260,
   "documented": "R260",
   "name": "Buzzer total active time",
   "description": "Since restart; write 0 to reset.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "s",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 278,
   "documented": "R278",
   "name": "Location string",
   "description": "Up to 31 characters, null terminated; appended to Server ID.",
   "data_type": "STRING",
   "length": 16,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 310,
   "documented": "R310",
   "name": "Temperature",
   "description": "Primary reading. Units per R133 (default °F); thermistor models only.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 312,
   "documented": "R312",
   "name": "Temperature - instantaneous",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 314,
   "documented": "R314",
   "name": "Temperature - minimum",
   "description": "Write 0 to reset.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 316,
   "documented": "R316",
   "name": "Temperature - maximum",
   "description": "Write 0 to reset.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 318,
   "documented": "R318",
   "name": "Temperature - average",
   "description": "Write 0 to reset.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 320,
   "documented": "R320",
   "name": "Sensor 1 gas concentration",
   "description": "Primary reading.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 322,
   "documented": "R322",
   "name": "Sensor 1 gas concentration - smoothed",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 324,
   "documented": "R324",
   "name": "Sensor 1 gas concentration - minimum",
   "description": "Write 0 to reset.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 326,
   "documented": "R326",
   "name": "Sensor 1 gas concentration - maximum",
   "description": "Write 0 to reset.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 328,
   "documented": "R328",
   "name": "Sensor 1 gas concentration - average",
   "description": "Write 0 to reset.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 330,
   "documented": "R330",
   "name": "Sensor 2 gas concentration",
   "description": "Primary reading.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 332,
   "documented": "R332",
   "name": "Sensor 2 gas concentration - smoothed",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 334,
   "documented": "R334",
   "name": "Sensor 2 gas concentration - minimum",
   "description": "Write 0 to reset.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 336,
   "documented": "R336",
   "name": "Sensor 2 gas concentration - maximum",
   "description": "Write 0 to reset.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 338,
   "documented": "R338",
   "name": "Sensor 2 gas concentration - average",
   "description": "Write 0 to reset.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 380,
   "documented": "R380",
   "name": "Power supply voltage",
   "description": "Primary reading.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "V",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 382,
   "documented": "R382",
   "name": "Power supply voltage - instantaneous",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "V",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 384,
   "documented": "R384",
   "name": "Power supply voltage - minimum",
   "description": "Write 0 to reset.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "V",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 386,
   "documented": "R386",
   "name": "Power supply voltage - maximum",
   "description": "Write 0 to reset.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "V",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 388,
   "documented": "R388",
   "name": "Power supply voltage - average",
   "description": "Write 0 to reset.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "V",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  }
 ],
 "integration": {
  "summary": "Connect the TG to the RS-485 bus and poll; it learns the protocol, baud and parity from traffic. Its address is 100 + the last two serial digits. Read R320 (gas 1), R170 (state) and R210/R230 (relays) with FC 03; floats are high word first.",
  "minimum_registers": [
   {
    "table": "holding_register",
    "address": 320,
    "why": "Sensor 1 gas concentration"
   },
   {
    "table": "holding_register",
    "address": 330,
    "why": "Sensor 2 gas concentration"
   },
   {
    "table": "holding_register",
    "address": 170,
    "why": "System state"
   },
   {
    "table": "holding_register",
    "address": 210,
    "why": "Fan relay"
   },
   {
    "table": "holding_register",
    "address": 230,
    "why": "Alarm relay"
   },
   {
    "table": "holding_register",
    "address": 158,
    "why": "Sensor 1 remaining life"
   }
  ],
  "enable": "No setup needed: with Auto Protocol, Auto Baud and Auto Parity active (factory default) the TG adapts to the bus. Fix the settings via R122-R128 once the network is stable.",
  "watchdog": null,
  "quirks": [
   "Addresses are raw (R320 = address 320).",
   "Floats and UINT32 are big-endian, high word first.",
   "Writing R124 turns auto-baud off and cannot be undone remotely if the new rate is wrong."
  ],
  "setup": [
   "Default slave address = 100 + last two digits of the serial number.",
   "Auto baud 9600-115200; parity even/odd/none detected automatically."
  ],
  "gotchas": [
   "Writing 9699690 to R190 erases all configuration including the address.",
   "With Auto Reset Statistics on, every read of a min/max/average resets it."
  ]
 },
 "page": "https://easymodbus.com/modbus-register-maps/senva/tg-gas-monitor",
 "address_note": "address = 0-based Modbus wire (PDU) address; documented = as printed in the source.",
 "note": "Re-typed from the manufacturer's public documentation (see source) and verified against it. Registers vary by firmware and options; verify against the live device before writing."
}