 "manufacturer": "Shinko Technos",
 "manufacturer_slug": "shinko-technos",
 "model": "ACD-13A / ACR-13A / ACD-15A / ACR-15A digital indicating controller (C, C5 options)",
 "model_slug": "acd-acr-13a-15a",
 "short_model": "ACD/ACR-13A",
 "aliases": [
  "ACD-13A",
  "ACR-13A",
  "ACD-15A",
  "ACR-15A"
 ],
 "equipment_type": "Sensor (digital temperature controller)",
 "applies_to": "Shinko ACD/ACR-13A (PID) and ACD/ACR-15A (valve positioning) with the C or C5 communication option; manual No.ACDR1CE8.",
 "summary": "The ACD/ACR-13A are PID temperature controllers and the ACD/ACR-15A are valve-positioning versions with open/close outputs and a feedback potentiometer input. With the serial option they speak Shinko protocol, Modbus ASCII or Modbus RTU. The map covers SV and alarm values for memory 1, PID zone 1, input, output and event settings, run/manual control, PV, MV, current SV and status flags.",
 "transport": [
  "RTU",
  "ASCII"
 ],
 "defaults": {
  "unit_id": 0,
  "baud": 9600,
  "parity": "Even",
  "data_bits": 7,
  "stop_bits": 1,
  "tcp_port": null
 },
 "addressing": {
  "convention": "hex 0-based",
  "note": "Registers are listed as hex data items (0001H) that go into the request unchanged. The manual adds that the matching Modicon holding-register number is the item in decimal plus 40001 (0001H = 40002)."
 },
 "default_word_order": null,
 "firmware": null,
 "source": {
  "title": "Communication Instruction Manual ACD/R-13A, ACD/R-15A (C, C5)",
  "doc_number": "No. ACDR1CE8",
  "revision_date": "2020-03",
  "url": "https://shinko-technos.co.jp/e/manual/english/ACDR1CE8.pdf",
  "pages": "Section 7, pp. 12-14 and 17-18; communication settings p. 3"
 },
 "notes": [
  "All data are 16-bit two's complement; items marked 'decimal point ignored' are whole numbers, so apply the decimal point place (0033H).",
  "Items marked 13A or 15A apply only to that model type, per the manual's tags.",
  "Left out: event output allocations and later settings on pp. 14-16, CT current and remaining read items on p. 19, program steps and PID zones 2-5 (separate command tables on pp. 19-21).",
  "SV memory 1 values at 0001H-000BH are shared with program step 1.",
  "Input type changes take about 2 s to answer; set the master timeout to 2 s or more."
 ],
 "integration": {
  "summary": "Select MODBUS RTU in the Communication group, use an 8-bit data format and a non-zero instrument number, then read PV 0A00H, MV 0A01H and status 0A06H/0A07H; write SV at 0001H.",
  "minimum_registers": [
   {
    "table": "holding_register",
    "address": 2560,
    "why": "Process value"
   },
   {
    "table": "holding_register",
    "address": 1,
    "why": "Set value (memory 1)"
   },
   {
    "table": "holding_register",
    "address": 2561,
    "why": "Output MV"
   },
   {
    "table": "holding_register",
    "address": 2566,
    "why": "Output and alarm status"
   },
   {
    "table": "holding_register",
    "address": 209,
    "why": "Control output OFF or program RUN/STOP"
   },
   {
    "table": "holding_register",
    "address": 51,
    "why": "Decimal point for scaling"
   }
  ],
  "enable": "Requires the C or C5 option. From the PV/SV display step through the Engineering and Input groups to the Communication group (key sequence on p. 3), then set Communication protocol to MODBUS RTU, instrument number, speed, data bit/parity and stop bit.",
  "watchdog": null,
  "quirks": [
   "Factory format is 7 bits/Even, suited to Shinko protocol; Modbus RTU needs an 8-bit choice.",
   "Instrument number defaults to 0, the Modbus broadcast address; set 1-95."
  ],
  "setup": [
   "Factory defaults: Shinko protocol, instrument 0, 9600 bps, 7 bits/Even, 1 stop bit.",
   "Speeds 9600, 19200, 38400 bps."
  ],
  "gotchas": [
   "Key lock set to Prohibited (00D4H) reverts to Allowed after a power cycle."
  ]
 },
 "registers": [
  {
   "table": "holding_register",
   "address": 1,
   "documented": "0001H",
   "name": "SV (memory 1)",
   "description": "Set value, memory number SM1. Decimal point ignored: Raw integer; apply the decimal point setting.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2,
   "documented": "0002H",
   "name": "EVT1 alarm value (SM1)",
   "description": "Low side for independent alarms.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 3,
   "documented": "0003H",
   "name": "EVT1 high limit alarm value (SM1)",
   "description": "High side for independent alarms.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 4,
   "documented": "0004H",
   "name": "EVT2 alarm value (SM1)",
   "description": "Low side for independent alarms. (ACD/ACR-13A only)",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 5,
   "documented": "0005H",
   "name": "EVT2 high limit alarm value (SM1)",
   "description": "High side for independent alarms. (ACD/ACR-13A only)",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 6,
   "documented": "0006H",
   "name": "EVT3 alarm value (SM1)",
   "description": "Low side for independent alarms. (ACD/ACR-13A only)",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 7,
   "documented": "0007H",
   "name": "EVT3 high limit alarm value (SM1)",
   "description": "High side for independent alarms. (ACD/ACR-13A only)",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8,
   "documented": "0008H",
   "name": "EVT4 alarm value (SM1)",
   "description": "Low side for independent alarms.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 9,
   "documented": "0009H",
   "name": "EVT4 high limit alarm value (SM1)",
   "description": "High side for independent alarms.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 10,
   "documented": "000AH",
   "name": "EVT5 alarm value (SM1)",
   "description": "Low side for independent alarms.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 11,
   "documented": "000BH",
   "name": "EVT5 high limit alarm value (SM1)",
   "description": "High side for independent alarms.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 16,
   "documented": "0010H",
   "name": "AT/Auto-reset",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Cancel",
    "1": "Perform"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 17,
   "documented": "0011H",
   "name": "AT bias",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 32,
   "documented": "0020H",
   "name": "OUT1 proportional band (zone 1)",
   "description": "Decimal point ignored: Raw integer; apply the decimal point setting.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 33,
   "documented": "0021H",
   "name": "OUT2 proportional band (zone 1)",
   "description": "Decimal point ignored: Raw integer; apply the decimal point setting. (ACD/ACR-13A only)",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 34,
   "documented": "0022H",
   "name": "Integral time (zone 1)",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 35,
   "documented": "0023H",
   "name": "Derivative time (zone 1)",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 36,
   "documented": "0024H",
   "name": "ARW (zone 1)",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 37,
   "documented": "0025H",
   "name": "Manual reset (zone 1)",
   "description": "Decimal point ignored: Raw integer; apply the decimal point setting.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 38,
   "documented": "0026H",
   "name": "OUT1 / MV rate-of-change (zone 1)",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 48,
   "documented": "0030H",
   "name": "Input type",
   "description": "The reply to this item takes about 2 s.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "K -200 to 1370 C",
    "1": "K -200.0 to 400.0 C",
    "2": "J -200 to 1000 C",
    "3": "R 0 to 1760 C",
    "4": "S 0 to 1760 C",
    "5": "B 0 to 1820 C",
    "6": "E -200 to 800 C",
    "7": "T -200.0 to 400.0 C",
    "8": "N -200 to 1300 C",
    "9": "PL-II 0 to 1390 C",
    "10": "C (W/Re5-26) 0 to 2315 C",
    "11": "Pt100 -200.0 to 850.0 C",
    "12": "JPt100 -200.0 to 500.0 C",
    "13": "Pt100 -200 to 850 C",
    "14": "JPt100 -200 to 500 C",
    "15": "Pt100 -100.0 to 100.0 C",
    "16": "JPt100 -100.0 to 500.0 C",
    "17": "K -328 to 2498 F",
    "18": "K -328.0 to 752.0 F",
    "19": "J -328 to 1832 F",
    "20": "R 32 to 3200 F",
    "21": "S 32 to 3200 F",
    "22": "B 32 to 3308 F",
    "23": "E -328 to 1472 F",
    "24": "T -328.0 to 752.0 F",
    "25": "N -328 to 2372 F",
    "26": "PL-II 32 to 2534 F",
    "27": "C (W/Re5-26) 32 to 4199 F",
    "28": "Pt100 -328.0 to 1562.0 F",
    "29": "JPt100 -328.0 to 932.0 F",
    "30": "Pt100 -328 to 1562 F",
    "31": "JPt100 -328 to 932 F",
    "32": "Pt100 -148.0 to 212.0 F",
    "33": "JPt100 -148.0 to 932.0 F",
    "34": "4-20 mA DC",
    "35": "0-20 mA DC",
    "36": "0-10 mV DC",
    "37": "-10 to 10 mV DC",
    "38": "0-50 mV DC",
    "39": "0-100 mV DC",
    "40": "0-1 V DC",
    "41": "0-5 V DC",
    "42": "1-5 V DC",
    "43": "0-10 V DC"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 49,
   "documented": "0031H",
   "name": "Scaling high limit",
   "description": "Decimal point ignored: Raw integer; apply the decimal point setting.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 50,
   "documented": "0032H",
   "name": "Scaling low limit",
   "description": "Decimal point ignored: Raw integer; apply the decimal point setting.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 51,
   "documented": "0033H",
   "name": "Decimal point place",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "xxxxx",
    "1": "xxxx.x",
    "2": "xxx.xx",
    "3": "xx.xxx",
    "4": "x.xxxx"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 52,
   "documented": "0034H",
   "name": "PV filter time constant",
   "description": "Decimal point ignored: Raw integer; apply the decimal point setting.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 53,
   "documented": "0035H",
   "name": "Sensor correction",
   "description": "Decimal point ignored: Raw integer; apply the decimal point setting.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 64,
   "documented": "0040H",
   "name": "OUT1 proportional cycle",
   "description": "(ACD/ACR-13A only)",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 65,
   "documented": "0041H",
   "name": "OUT2 proportional cycle",
   "description": "(ACD/ACR-13A only)",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 66,
   "documented": "0042H",
   "name": "OUT1 / MV high limit",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 67,
   "documented": "0043H",
   "name": "OUT1 / MV low limit",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 68,
   "documented": "0044H",
   "name": "OUT1 ON/OFF hysteresis",
   "description": "Decimal point ignored: Raw integer; apply the decimal point setting.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 69,
   "documented": "0045H",
   "name": "OUT2 cooling method",
   "description": "(ACD/ACR-13A only)",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Air cooling",
    "1": "Oil cooling",
    "2": "Water cooling"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 70,
   "documented": "0046H",
   "name": "OUT2 high limit",
   "description": "(ACD/ACR-13A only)",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 71,
   "documented": "0047H",
   "name": "OUT2 low limit",
   "description": "(ACD/ACR-13A only)",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 72,
   "documented": "0048H",
   "name": "Overlap/dead band",
   "description": "Decimal point ignored: Raw integer; apply the decimal point setting. (ACD/ACR-13A only)",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 73,
   "documented": "0049H",
   "name": "OUT2 ON/OFF hysteresis",
   "description": "Decimal point ignored: Raw integer; apply the decimal point setting. (ACD/ACR-13A only)",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 74,
   "documented": "004AH",
   "name": "Direct/reverse action",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Reverse action",
    "1": "Direct action"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 75,
   "documented": "004BH",
   "name": "OUT1 MV preset output",
   "description": "Decimal point ignored: Raw integer; apply the decimal point setting. (ACD/ACR-13A only)",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 76,
   "documented": "004CH",
   "name": "OUT2 MV preset output",
   "description": "Decimal point ignored: Raw integer; apply the decimal point setting. (ACD/ACR-13A only)",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 80,
   "documented": "0050H",
   "name": "Event input EVI1 allocation",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "No event",
    "1": "Set value memory",
    "2": "Control ON/OFF",
    "3": "Direct/Reverse action",
    "4": "Timer start/stop",
    "5": "PV holding",
    "6": "PV peak value holding",
    "7": "Preset output 1",
    "8": "Auto/Manual control",
    "9": "Remote/Local",
    "10": "Program RUN/STOP",
    "11": "Program holding",
    "12": "Program advance",
    "13": "Integral action holding",
    "14": "Preset output 2"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 81,
   "documented": "0051H",
   "name": "Event input EVI2 allocation",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "No event",
    "1": "Set value memory",
    "2": "Control ON/OFF",
    "3": "Direct/Reverse action",
    "4": "Timer start/stop",
    "5": "PV holding",
    "6": "PV peak value holding",
    "7": "Preset output 1",
    "8": "Auto/Manual control",
    "9": "Remote/Local",
    "10": "Program RUN/STOP",
    "11": "Program holding",
    "12": "Program advance",
    "13": "Integral action holding",
    "14": "Preset output 2"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 82,
   "documented": "0052H",
   "name": "Event input EVI3 allocation",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "No event",
    "1": "Set value memory",
    "2": "Control ON/OFF",
    "3": "Direct/Reverse action",
    "4": "Timer start/stop",
    "5": "PV holding",
    "6": "PV peak value holding",
    "7": "Preset output 1",
    "8": "Auto/Manual control",
    "9": "Remote/Local",
    "10": "Program RUN/STOP",
    "11": "Program holding",
    "12": "Program advance",
    "13": "Integral action holding",
    "14": "Preset output 2"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 83,
   "documented": "0053H",
   "name": "Event input EVI4 allocation",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "No event",
    "1": "Set value memory",
    "2": "Control ON/OFF",
    "3": "Direct/Reverse action",
    "4": "Timer start/stop",
    "5": "PV holding",
    "6": "PV peak value holding",
    "7": "Preset output 1",
    "8": "Auto/Manual control",
    "9": "Remote/Local",
    "10": "Program RUN/STOP",
    "11": "Program holding",
    "12": "Program advance",
    "13": "Integral action holding",
    "14": "Preset output 2"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 198,
   "documented": "00C6H",
   "name": "PV color",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Green",
    "1": "Red",
    "2": "Orange",
    "3": "EVT1-5 ON: green to red",
    "4": "EVT1-5 ON: orange to red",
    "5": "PV continuous change",
    "6": "PV continuous change + EVT1-5 ON red"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 199,
   "documented": "00C7H",
   "name": "PV color range",
   "description": "Decimal point ignored: Raw integer; apply the decimal point setting.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 200,
   "documented": "00C8H",
   "name": "Backlight time",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 201,
   "documented": "00C9H",
   "name": "Bar graph",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "MV indication",
    "1": "DV indication",
    "2": "No indication",
    "3": "Valve opening (15A)"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 202,
   "documented": "00CAH",
   "name": "Deviation unit",
   "description": "Decimal point ignored: Raw integer; apply the decimal point setting.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 208,
   "documented": "00D0H",
   "name": "SV of current set value memory",
   "description": "Decimal point ignored: Raw integer; apply the decimal point setting.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 209,
   "documented": "00D1H",
   "name": "Control output OFF or RUN/STOP",
   "description": "Fixed value control: 0 ON, 1 OFF. Program control: 0 STOP, 1 RUN.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 210,
   "documented": "00D2H",
   "name": "Auto/manual control",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Automatic control",
    "1": "Manual control"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 211,
   "documented": "00D3H",
   "name": "Manual MV",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 212,
   "documented": "00D4H",
   "name": "Key operation allowed/prohibited",
   "description": "Returns to Allowed after a power cycle.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Allowed",
    "1": "Prohibited"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 224,
   "documented": "00E0H",
   "name": "FBP yes/no (15A)",
   "description": "Feedback potentiometer, ACD/ACR-15A valve control.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "FBP yes",
    "1": "FBP no"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 225,
   "documented": "00E1H",
   "name": "Open/closed output dead band (15A)",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 226,
   "documented": "00E2H",
   "name": "Open/closed output hysteresis (15A)",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 227,
   "documented": "00E3H",
   "name": "Open output time (15A)",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 228,
   "documented": "00E4H",
   "name": "Closed output time (15A)",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 229,
   "documented": "00E5H",
   "name": "Error detection during FBP adjustment (15A)",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Yes",
    "1": "No"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 240,
   "documented": "00F0H",
   "name": "Key operation change flag clearing",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "W",
   "values": {
    "0": "No action",
    "1": "Clear all"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2560,
   "documented": "0A00H",
   "name": "PV",
   "description": "Process value. Decimal point ignored: Raw integer; apply the decimal point setting.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2561,
   "documented": "0A01H",
   "name": "OUT1 MV / output MV",
   "description": "Decimal point ignored.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2562,
   "documented": "0A02H",
   "name": "OUT2 MV",
   "description": "Decimal point ignored. (ACD/ACR-13A only)",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2563,
   "documented": "0A03H",
   "name": "Current SV",
   "description": "Decimal point ignored: Raw integer; apply the decimal point setting.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2564,
   "documented": "0A04H",
   "name": "Remaining time (program)",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2565,
   "documented": "0A05H",
   "name": "Program running step",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2566,
   "documented": "0A06H",
   "name": "Status flag 1",
   "description": "",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "0": "OUT1 (13A) / open output (15A) on",
    "1": "OUT2 (13A) / closed output (15A) on",
    "2": "EVT1 output on",
    "3": "EVT2 output on (13A)",
    "4": "EVT3 output on (13A)",
    "5": "EVT4 output on",
    "6": "EVT5 output on",
    "7": "Heater burnout alarm (13A)",
    "8": "Loop break alarm",
    "9": "Overscale",
    "10": "Underscale",
    "11": "Standby mode",
    "12": "Setting mode",
    "13": "AT/Auto-reset running",
    "14": "Warm-up",
    "15": "Settings changed by keypad"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2567,
   "documented": "0A07H",
   "name": "Status flag 2",
   "description": "",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "0": "EVT1 input on",
    "1": "EVT2 input on",
    "2": "EVT3 input on",
    "3": "EVT4 input on",
    "11": "Manual control",
    "12": "Program control mode",
    "13": "Program control running",
    "14": "Wait active"
   },
   "offset": 0
  }
 ],
 "page": "https://easymodbus.com/modbus-register-maps/shinko-technos/acd-acr-13a-15a",
 "address_note": "address = 0-based Modbus wire (PDU) address; documented = as printed in the source.",
 "note": "Re-typed from the manufacturer's public documentation (see source) and verified against it. Registers vary by firmware and options; verify against the live device before writing."
}