 "manufacturer": "Shinko Technos",
 "manufacturer_slug": "shinko-technos",
 "model": "ACS2 digital indicating controller (C5, C5W options)",
 "model_slug": "acs2",
 "short_model": "ACS2",
 "aliases": [
  "ACS2-C5",
  "ACS2-C5W"
 ],
 "equipment_type": "Sensor (digital temperature controller)",
 "applies_to": "Shinko ACS2 with the C5 or C5W serial option, Shinko protocol / MODBUS RTU command set; manual No.ACS2CE3.",
 "summary": "The ACS2 is a Shinko PID temperature controller with SV memories, program control and several PID modes. With the C5/C5W option it speaks Shinko protocol, Modbus RTU or MC protocol on RS485; all items are 16-bit holding registers. This map covers SV memories, input setup, EV1 alarm handling, control mode and key function settings, and the full read block from 03E8H (PV, MV, SV, status, error and heater current).",
 "transport": [
  "RTU"
 ],
 "defaults": {
  "unit_id": 0,
  "baud": 9600,
  "parity": "Even",
  "data_bits": 7,
  "stop_bits": null,
  "tcp_port": null
 },
 "addressing": {
  "convention": "hex 0-based",
  "note": "Registers are listed as hex data items (0001H) that go into the request unchanged. The manual adds that the matching Modicon holding-register number is the item in decimal plus 40001 (0001H = 40002)."
 },
 "default_word_order": null,
 "firmware": null,
 "source": {
  "title": "Communication Instruction Manual ACS2 (C5W, C5)",
  "doc_number": "No. ACS2CE3",
  "revision_date": "2026-08",
  "url": "https://shinko-technos.co.jp/e/manual/english/ACS2CE3.pdf",
  "pages": "Section 7.1, pp. 21-29 (only pp. 21, 23, 26, 28-29 used); communication settings p. 4"
 },
 "notes": [
  "Only a subset of the setting table is mapped: PID terms, EV2/EV3, output and many other setting items on pp. 22-27 are left out, as are program pattern commands (section 7.1.3 onward).",
  "All data are 16-bit two's complement. Items marked 'decimal point ignored' are whole numbers; apply the decimal point of the input range.",
  "Error status flag (03F5H): the manual states 0 = normal, 1 = error only for bit 11; the other bits are listed without a polarity legend.",
  "Writing data clear (00D8H) restores factory settings including communication settings; not mapped here."
 ],
 "integration": {
  "summary": "In the Communication setting group choose MODBUS RTU, an 8-bit data format and a non-zero instrument number. Poll PV 03E8H, OUT1 MV 03E9H, status 03ECH/03EDH and errors 03F5H; write SV1 at 0001H.",
  "minimum_registers": [
   {
    "table": "holding_register",
    "address": 1000,
    "why": "Process value"
   },
   {
    "table": "holding_register",
    "address": 1,
    "why": "Set value SV1"
   },
   {
    "table": "holding_register",
    "address": 1001,
    "why": "OUT1 manipulated value"
   },
   {
    "table": "holding_register",
    "address": 1004,
    "why": "Output and alarm status"
   },
   {
    "table": "holding_register",
    "address": 1013,
    "why": "Error status"
   },
   {
    "table": "holding_register",
    "address": 1005,
    "why": "Run mode status"
   }
  ],
  "enable": "Requires the C5 or C5W option. In RUN mode step through the setting groups to the Communication setting group and enter it (keys shown on p. 4), set Communication protocol to MODBUS RTU mode, then instrument number, speed, data bit/parity and stop bit.",
  "watchdog": null,
  "quirks": [
   "Factory data format is 7 bits/Even; Modbus RTU needs an 8-bit choice.",
   "Instrument number defaults to 0, the Modbus broadcast address; set 1-95.",
   "Modbus ASCII is not offered on this model; protocols are Shinko, MODBUS RTU, MC protocol and SVTC."
  ],
  "setup": [
   "Factory defaults: Shinko protocol, instrument 0, 9600 bps, 7 bits/Even.",
   "Speeds 9600 to 115200 bps."
  ],
  "gotchas": [
   "Data clear (00D8H) also resets communication settings, so the unit may stop answering with the current master settings."
  ]
 },
 "registers": [
  {
   "table": "holding_register",
   "address": 1,
   "documented": "0001H",
   "name": "SV1 setting",
   "description": "Set value memory 1. Decimal point ignored: Raw integer; apply the decimal point setting.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2,
   "documented": "0002H",
   "name": "SV2 setting",
   "description": "Set value memory 2. Decimal point ignored: Raw integer; apply the decimal point setting.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 3,
   "documented": "0003H",
   "name": "SV3 setting",
   "description": "Set value memory 3. Decimal point ignored: Raw integer; apply the decimal point setting.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 4,
   "documented": "0004H",
   "name": "SV4 setting",
   "description": "Set value memory 4. Decimal point ignored: Raw integer; apply the decimal point setting.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 5,
   "documented": "0005H",
   "name": "SV5 setting",
   "description": "Set value memory 5. Decimal point ignored: Raw integer; apply the decimal point setting.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 6,
   "documented": "0006H",
   "name": "SV6 setting",
   "description": "Set value memory 6. Decimal point ignored: Raw integer; apply the decimal point setting.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 7,
   "documented": "0007H",
   "name": "SV7 setting",
   "description": "Set value memory 7. Decimal point ignored: Raw integer; apply the decimal point setting.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8,
   "documented": "0008H",
   "name": "SV8 setting",
   "description": "Set value memory 8. Decimal point ignored: Raw integer; apply the decimal point setting.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 32,
   "documented": "0020H",
   "name": "Input type selection",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "K -200 to 1370 C",
    "1": "K -200.0 to 800.0 C",
    "2": "K -200.0 to 400.0 C",
    "3": "J -200 to 1000 C",
    "4": "J -200.0 to 400.0 C",
    "5": "R 0 to 1760 C",
    "6": "S 0 to 1760 C",
    "7": "B 0 to 1820 C",
    "8": "E -200 to 800 C",
    "9": "T -200.0 to 400.0 C",
    "10": "N -200 to 1300 C",
    "11": "PL-II 0 to 1390 C",
    "12": "C (W/Re5-26) 0 to 2315 C",
    "13": "Pt100 -200.0 to 850.0 C",
    "14": "Pt100 -200 to 850 C",
    "15": "Pt100 -100.0 to 100.0 C",
    "16": "4-20 mA DC (built-in shunt)",
    "17": "0-20 mA DC (built-in shunt)",
    "18": "4-20 mA DC (external shunt)",
    "19": "0-20 mA DC (external shunt)",
    "20": "0-1 V DC",
    "21": "0-5 V DC",
    "22": "1-5 V DC",
    "23": "0-10 V DC"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 33,
   "documented": "0021H",
   "name": "Temperature unit selection",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Celsius",
    "1": "Fahrenheit"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 34,
   "documented": "0022H",
   "name": "Scaling high limit setting",
   "description": "Decimal point ignored: Raw integer; apply the decimal point setting.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 35,
   "documented": "0023H",
   "name": "Scaling low limit setting",
   "description": "Decimal point ignored: Raw integer; apply the decimal point setting.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 81,
   "documented": "0051H",
   "name": "EV1 enabled/disabled when alarm set to 0",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Disabled",
    "1": "Enabled"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 82,
   "documented": "0052H",
   "name": "EV1 hysteresis setting",
   "description": "Decimal point ignored: Raw integer; apply the decimal point setting.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 83,
   "documented": "0053H",
   "name": "EV1 action delay timer setting",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 84,
   "documented": "0054H",
   "name": "EV1 action energized/de-energized",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Energized",
    "1": "De-energized"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 85,
   "documented": "0055H",
   "name": "EV1 output latch selection",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Disabled",
    "1": "Enabled"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 86,
   "documented": "0056H",
   "name": "TS1 output step number",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 87,
   "documented": "0057H",
   "name": "TS1 OFF time setting",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 88,
   "documented": "0058H",
   "name": "TS1 ON time setting",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 176,
   "documented": "00B0H",
   "name": "Control action selection",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "2DOF PID",
    "1": "Fast-PID",
    "2": "Slow-PID",
    "3": "Gap-PID"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 184,
   "documented": "00B8H",
   "name": "Integral/derivative decimal point",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "No decimal point",
    "1": "With decimal point"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 192,
   "documented": "00C0H",
   "name": "Set value lock selection",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Unlock",
    "1": "Lock 1",
    "2": "Lock 2"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 193,
   "documented": "00C1H",
   "name": "SV rise/fall rate action selection",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "SV start",
    "1": "PV start"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 194,
   "documented": "00C2H",
   "name": "SV rise/fall rate time unit",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Minutes",
    "1": "Seconds"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 195,
   "documented": "00C3H",
   "name": "SV rise rate setting",
   "description": "Decimal point ignored: Raw integer; apply the decimal point setting.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 196,
   "documented": "00C4H",
   "name": "SV fall rate setting",
   "description": "Decimal point ignored: Raw integer; apply the decimal point setting.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 198,
   "documented": "00C6H",
   "name": "SV display method selection",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Set target value",
    "1": "Target value during ramp/program"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 199,
   "documented": "00C7H",
   "name": "Indication when control output OFF",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "OFF indication",
    "1": "No indication",
    "2": "PV indication",
    "3": "PV indication + any alarm active"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 200,
   "documented": "00C8H",
   "name": "OUT/OFF key function selection",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "No function",
    "1": "Auto/Manual control",
    "2": "Control output OFF function",
    "3": "Remote/Local selection",
    "4": "RUN/STOP (program control)"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 201,
   "documented": "00C9H",
   "name": "PF key function selection",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "No function",
    "1": "Auto/Manual control",
    "2": "Control output OFF function",
    "3": "Remote/Local selection",
    "4": "RUN/STOP (program control)"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1000,
   "documented": "03E8H",
   "name": "PV",
   "description": "Process value. Decimal point ignored: Raw integer; apply the decimal point setting.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1001,
   "documented": "03E9H",
   "name": "OUT1 MV",
   "description": "Decimal point ignored: Raw integer; apply the decimal point setting.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1002,
   "documented": "03EAH",
   "name": "OUT2 MV",
   "description": "Decimal point ignored: Raw integer; apply the decimal point setting.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1003,
   "documented": "03EBH",
   "name": "Current SV",
   "description": "Decimal point ignored: Raw integer; apply the decimal point setting.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1004,
   "documented": "03ECH",
   "name": "Status flag 1",
   "description": "",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "0": "OUT1 output on",
    "1": "OUT2 output on",
    "2": "EV1 output on",
    "3": "EV2 output on",
    "4": "EV3 output on",
    "10": "Operating terminal short-circuit alarm",
    "11": "Heater burnout alarm",
    "12": "Loop break alarm",
    "13": "Input high limit alarm",
    "14": "Input low limit alarm",
    "15": "Settings changed by keypad"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1005,
   "documented": "03EDH",
   "name": "Status flag 2",
   "description": "",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "0": "Warm-up",
    "1": "E1 input on",
    "2": "E2 input on",
    "3": "E3 input on",
    "4": "E4 input on",
    "5": "USB power (0 = instrument power)",
    "7": "Control permitted",
    "8": "AT running",
    "9": "Manual control",
    "10": "Remote",
    "11": "Program control mode",
    "12": "Program running",
    "13": "Wait function on",
    "14": "Hold function on",
    "15": "Pattern end function on"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1006,
   "documented": "03EEH",
   "name": "CT1 current value",
   "description": "Decimal point ignored: Raw integer; apply the decimal point setting.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1007,
   "documented": "03EFH",
   "name": "CT2 current value",
   "description": "Decimal point ignored: Raw integer; apply the decimal point setting.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1008,
   "documented": "03F0H",
   "name": "Ambient temperature",
   "description": "Decimal point ignored: Raw integer; apply the decimal point setting.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1009,
   "documented": "03F1H",
   "name": "Setting value memory number",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1010,
   "documented": "03F2H",
   "name": "Program operation step number",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1011,
   "documented": "03F3H",
   "name": "Program operation remaining time",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1012,
   "documented": "03F4H",
   "name": "Program operation number of repetitions",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1013,
   "documented": "03F5H",
   "name": "Error status flag",
   "description": "",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "0": "Alarm 1",
    "1": "Alarm 2",
    "2": "Alarm 3",
    "4": "Heater burnout alarm",
    "5": "Operation terminal short-circuit alarm",
    "6": "Loop break alarm",
    "7": "Sensor error",
    "8": "Overscale",
    "9": "Underscale",
    "10": "Cold junction error",
    "11": "Non-volatile IC memory error",
    "12": "Hardware error"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1020,
   "documented": "03FCH",
   "name": "EVT input display",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1021,
   "documented": "03FDH",
   "name": "Key operation change item reading",
   "description": "Data item last changed from the keypad.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  }
 ],
 "page": "https://easymodbus.com/modbus-register-maps/shinko-technos/acs2",
 "address_note": "address = 0-based Modbus wire (PDU) address; documented = as printed in the source.",
 "note": "Re-typed from the manufacturer's public documentation (see source) and verified against it. Registers vary by firmware and options; verify against the live device before writing."
}