 "manufacturer": "Shinko Technos",
 "manufacturer_slug": "shinko-technos",
 "model": "BCS2 / BCR2 / BCD2 digital indicating controller (C5, C5W options)",
 "model_slug": "bcx2",
 "short_model": "BCx2",
 "aliases": [
  "BCS2",
  "BCR2",
  "BCD2",
  "BCx2"
 ],
 "equipment_type": "Sensor (digital temperature controller)",
 "applies_to": "Shinko BCx2 series (BCS2, BCR2, BCD2) with the C5 or C5W communication option, standard (not JC-allocated) command set; manual No.BCx2CE6.",
 "summary": "The BCx2 series are PID temperature controllers sharing one command set. With the C5/C5W option they talk Shinko protocol, Modbus ASCII or Modbus RTU on RS485; every item is a 16-bit holding register. This map covers the setup and PID settings, SV memories, event outputs, heater burnout and loop break alarms, run modes, PV, MV, current SV, heater current and the status words.",
 "transport": [
  "RTU",
  "ASCII"
 ],
 "defaults": {
  "unit_id": 0,
  "baud": 9600,
  "parity": "Even",
  "data_bits": 7,
  "stop_bits": 1,
  "tcp_port": null
 },
 "addressing": {
  "convention": "hex 0-based",
  "note": "Registers are listed as hex data items (0001H) that go into the request unchanged. The manual adds that the matching Modicon holding-register number is the item in decimal plus 40001 (0001H = 40002)."
 },
 "default_word_order": null,
 "firmware": null,
 "source": {
  "title": "Communication Instruction Manual BCD2, BCR2, BCS2 (C5W, C5)",
  "doc_number": "No.BCx2CE6",
  "revision_date": "2019-12",
  "url": "https://shinko-technos.co.jp/e/manual/english/BCx2CE6.pdf",
  "pages": "Section 7.1, pp. 26-33; communication settings pp. 4-5"
 },
 "notes": [
  "This map is for the standard 'MODBUS RTU' / 'MODBUS ASCII' protocol settings. The 'JC command allocated' protocol settings switch the unit to the older JC-series layout (section 7.2) and are not covered.",
  "All data are 16-bit; negatives are two's complement. Items marked 'decimal point ignored' are sent as whole numbers; apply the decimal point place (0005H).",
  "Read-only items from 0100H can be read with function 03 or 04.",
  "00E2H means control output ON/OFF, auto/manual, or program STOP/RUN depending on the OUT/OFF key function in 00E0H; in each case 0 is the first state (output ON / automatic / STOP) and 1 the second (output OFF / manual / RUN).",
  "The table lists SV1 at both 0001H and 000EH (followed by SV2-SV4 at 000FH-0011H).",
  "Left out: program-pattern settings (005EH-0077H), unit model and error status words, and section 8 SV digital transmission.",
  "Units of PID times, cycles and MV are not printed in the command table."
 ],
 "integration": {
  "summary": "In Engineering mode 1 choose MODBUS RTU, an 8-bit data format and a non-zero instrument number. Then poll PV 0100H, OUT1 MV 0101H and status flags 010DH/010EH; write SV1 at 0001H.",
  "minimum_registers": [
   {
    "table": "holding_register",
    "address": 256,
    "why": "Process value"
   },
   {
    "table": "holding_register",
    "address": 1,
    "why": "Set value SV1"
   },
   {
    "table": "holding_register",
    "address": 257,
    "why": "OUT1 manipulated value"
   },
   {
    "table": "holding_register",
    "address": 269,
    "why": "Output and alarm status"
   },
   {
    "table": "holding_register",
    "address": 270,
    "why": "Run mode status"
   },
   {
    "table": "holding_register",
    "address": 5,
    "why": "Decimal point for scaling"
   }
  ],
  "enable": "Requires the C5 or C5W option. Hold the up and down keys for 3 s in RUN mode to enter Engineering mode 1, then set Communication protocol to MODBUS RTU (not the JC command allocated variant), instrument number, speed, data bit/parity and stop bit.",
  "watchdog": null,
  "quirks": [
   "Factory data format is 7 bits/Even; Modbus RTU needs one of the 8-bit choices.",
   "Instrument number defaults to 0, the Modbus broadcast address; set 1-95.",
   "Response delay time (default 10 ms) adds to every reply."
  ],
  "setup": [
   "Factory defaults: Shinko protocol, instrument 0, 9600 bps, 7 bits/Even, 1 stop bit, response delay 10 ms.",
   "Speeds 9600, 19200 or 38400 bps."
  ],
  "gotchas": [
   "Writing 1234H to 00FEH returns every setting to factory default.",
   "Settings are stored in non-volatile memory; avoid cyclic writes."
  ]
 },
 "registers": [
  {
   "table": "holding_register",
   "address": 1,
   "documented": "0001H",
   "name": "SV1",
   "description": "Set value. Decimal point ignored: Raw integer; apply the decimal point setting.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2,
   "documented": "0002H",
   "name": "Input type",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "K -200 to 1370",
    "1": "K -200.0 to 400.0",
    "2": "J -200 to 1000",
    "3": "R 0 to 1760",
    "4": "S 0 to 1760",
    "5": "B 0 to 1820",
    "6": "E -200 to 800",
    "7": "T -200.0 to 400.0",
    "8": "N -200 to 1300",
    "9": "PL-II 0 to 1390",
    "10": "C (W/Re5-26) 0 to 2315",
    "11": "Pt100 -200.0 to 850.0",
    "12": "JPt100 -200.0 to 500.0",
    "13": "Pt100 -200 to 850",
    "14": "JPt100 -200 to 500",
    "15": "K -328 to 2498",
    "16": "K -328.0 to 752.0",
    "17": "J -328 to 1832",
    "18": "R 32 to 3200",
    "19": "S 32 to 3200",
    "20": "B 32 to 3308",
    "21": "E -328 to 1472",
    "22": "T -328.0 to 752.0",
    "23": "N -328 to 2372",
    "24": "PL-II 32 to 2534",
    "25": "C (W/Re5-26) 32 to 4199",
    "26": "Pt100 -328.0 to 1562.0",
    "27": "JPt100 -328.0 to 932.0",
    "28": "Pt100 -328 to 1562",
    "29": "JPt100 -328 to 932",
    "30": "4-20 mA DC -2000 to 10000",
    "31": "0-20 mA DC -2000 to 10000",
    "32": "0-1 V DC -2000 to 10000",
    "33": "0-5 V DC -2000 to 10000",
    "34": "1-5 V DC -2000 to 10000",
    "35": "0-10 V DC -2000 to 10000"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 3,
   "documented": "0003H",
   "name": "Scaling high limit",
   "description": "Decimal point ignored: Raw integer; apply the decimal point setting.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 4,
   "documented": "0004H",
   "name": "Scaling low limit",
   "description": "Decimal point ignored: Raw integer; apply the decimal point setting.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 5,
   "documented": "0005H",
   "name": "Decimal point place",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "No decimal point",
    "1": "1 decimal place",
    "2": "2 decimal places",
    "3": "3 decimal places"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 6,
   "documented": "0006H",
   "name": "Event output EV1 allocation",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "No event",
    "1": "High limit alarm",
    "2": "Low limit alarm",
    "3": "High/Low limits alarm",
    "4": "High/Low limits independent alarm",
    "5": "High/Low limit range alarm",
    "6": "High/Low limit range independent alarm",
    "7": "Process high alarm",
    "8": "Process low alarm",
    "9": "High limit with standby",
    "10": "Low limit with standby",
    "11": "High/Low limits with standby",
    "12": "High/Low limits with standby independent",
    "13": "Heater burnout alarm output",
    "14": "Loop break alarm output",
    "15": "Time signal output",
    "16": "Output during AT",
    "17": "Pattern end output",
    "18": "Output by communication command"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 7,
   "documented": "0007H",
   "name": "Event output EV2 allocation",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "No event",
    "1": "High limit alarm",
    "2": "Low limit alarm",
    "3": "High/Low limits alarm",
    "4": "High/Low limits independent alarm",
    "5": "High/Low limit range alarm",
    "6": "High/Low limit range independent alarm",
    "7": "Process high alarm",
    "8": "Process low alarm",
    "9": "High limit with standby",
    "10": "Low limit with standby",
    "11": "High/Low limits with standby",
    "12": "High/Low limits with standby independent",
    "13": "Heater burnout alarm output",
    "14": "Loop break alarm output",
    "15": "Time signal output",
    "16": "Output during AT",
    "17": "Pattern end output",
    "18": "Output by communication command",
    "19": "Heating/cooling control relay contact output"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 11,
   "documented": "000BH",
   "name": "Transmission output type",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "PV",
    "1": "SV",
    "2": "MV",
    "3": "DV"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 12,
   "documented": "000CH",
   "name": "Transmission output high limit",
   "description": "Decimal point ignored: Raw integer; apply the decimal point setting.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 13,
   "documented": "000DH",
   "name": "Transmission output low limit",
   "description": "Decimal point ignored: Raw integer; apply the decimal point setting.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 14,
   "documented": "000EH",
   "name": "SV1 (memory)",
   "description": "Set value memory 1. Decimal point ignored: Raw integer; apply the decimal point setting.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 15,
   "documented": "000FH",
   "name": "SV2 (memory)",
   "description": "Set value memory 2. Decimal point ignored: Raw integer; apply the decimal point setting.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 16,
   "documented": "0010H",
   "name": "SV3 (memory)",
   "description": "Set value memory 3. Decimal point ignored: Raw integer; apply the decimal point setting.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 17,
   "documented": "0011H",
   "name": "SV4 (memory)",
   "description": "Set value memory 4. Decimal point ignored: Raw integer; apply the decimal point setting.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 18,
   "documented": "0012H",
   "name": "EV1 alarm value",
   "description": "Decimal point ignored: Raw integer; apply the decimal point setting.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 19,
   "documented": "0013H",
   "name": "EV1 high limit alarm value",
   "description": "Decimal point ignored: Raw integer; apply the decimal point setting.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 20,
   "documented": "0014H",
   "name": "EV2 alarm value",
   "description": "Decimal point ignored: Raw integer; apply the decimal point setting.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 21,
   "documented": "0015H",
   "name": "EV2 high limit alarm value",
   "description": "Decimal point ignored: Raw integer; apply the decimal point setting.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 28,
   "documented": "001CH",
   "name": "Heater burnout alarm 1 value",
   "description": "Decimal point ignored: Raw integer; apply the decimal point setting.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 29,
   "documented": "001DH",
   "name": "Heater burnout alarm 2 value",
   "description": "Decimal point ignored: Raw integer; apply the decimal point setting.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 30,
   "documented": "001EH",
   "name": "Loop break alarm time",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 31,
   "documented": "001FH",
   "name": "Loop break alarm band",
   "description": "Decimal point ignored: Raw integer; apply the decimal point setting.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 32,
   "documented": "0020H",
   "name": "Event input DI1 allocation",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "No event",
    "1": "Set value memory",
    "2": "Control ON/OFF",
    "3": "Direct/Reverse action",
    "4": "Preset output 1 ON/OFF",
    "5": "Preset output 2 ON/OFF",
    "6": "Auto/Manual control",
    "7": "Remote/Local",
    "8": "Program control RUN/STOP",
    "9": "Program control holding/not holding",
    "10": "Program control advance",
    "11": "Integral action holding"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 33,
   "documented": "0021H",
   "name": "Event input DI2 allocation",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "No event",
    "1": "Set value memory",
    "2": "Control ON/OFF",
    "3": "Direct/Reverse action",
    "4": "Preset output 1 ON/OFF",
    "5": "Preset output 2 ON/OFF",
    "6": "Auto/Manual control",
    "7": "Remote/Local",
    "8": "Program control RUN/STOP",
    "9": "Program control holding/not holding",
    "10": "Program control advance",
    "11": "Integral action holding"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 36,
   "documented": "0024H",
   "name": "EV1 alarm value 0 enabled/disabled",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Disabled",
    "1": "Enabled"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 37,
   "documented": "0025H",
   "name": "EV1 alarm hysteresis",
   "description": "Decimal point ignored: Raw integer; apply the decimal point setting.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 38,
   "documented": "0026H",
   "name": "EV1 alarm delay time",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 39,
   "documented": "0027H",
   "name": "EV1 alarm energized/de-energized",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Energized",
    "1": "De-energized"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 40,
   "documented": "0028H",
   "name": "EV2 alarm value 0 enabled/disabled",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Disabled",
    "1": "Enabled"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 41,
   "documented": "0029H",
   "name": "EV2 alarm hysteresis",
   "description": "Decimal point ignored: Raw integer; apply the decimal point setting.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 42,
   "documented": "002AH",
   "name": "EV2 alarm delay time",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 43,
   "documented": "002BH",
   "name": "EV2 alarm energized/de-energized",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Energized",
    "1": "De-energized"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 60,
   "documented": "003CH",
   "name": "OUT1 proportional band",
   "description": "Decimal point ignored: Raw integer; apply the decimal point setting.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 61,
   "documented": "003DH",
   "name": "Integral time",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 62,
   "documented": "003EH",
   "name": "Derivative time",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 63,
   "documented": "003FH",
   "name": "ARW",
   "description": "Anti-reset windup.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 64,
   "documented": "0040H",
   "name": "Manual reset",
   "description": "Decimal point ignored: Raw integer; apply the decimal point setting.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 65,
   "documented": "0041H",
   "name": "OUT1 proportional cycle",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 66,
   "documented": "0042H",
   "name": "OUT1 ON/OFF hysteresis",
   "description": "Decimal point ignored: Raw integer; apply the decimal point setting.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 67,
   "documented": "0043H",
   "name": "OUT1 high limit",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 68,
   "documented": "0044H",
   "name": "OUT1 low limit",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 69,
   "documented": "0045H",
   "name": "OUT1 rate-of-change",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 70,
   "documented": "0046H",
   "name": "OUT2 cooling method",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Air cooling",
    "1": "Oil cooling",
    "2": "Water cooling"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 71,
   "documented": "0047H",
   "name": "OUT2 proportional band",
   "description": "Decimal point ignored: Raw integer; apply the decimal point setting.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 72,
   "documented": "0048H",
   "name": "OUT2 proportional cycle",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 73,
   "documented": "0049H",
   "name": "OUT2 ON/OFF hysteresis",
   "description": "Decimal point ignored: Raw integer; apply the decimal point setting.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 74,
   "documented": "004AH",
   "name": "OUT2 high limit",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 75,
   "documented": "004BH",
   "name": "OUT2 low limit",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 76,
   "documented": "004CH",
   "name": "Overlap band/dead band",
   "description": "Decimal point ignored: Raw integer; apply the decimal point setting.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 77,
   "documented": "004DH",
   "name": "Direct/reverse action",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Reverse (heating)",
    "1": "Direct (cooling)"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 78,
   "documented": "004EH",
   "name": "Set value lock",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Unlock",
    "1": "Lock 1",
    "2": "Lock 2",
    "3": "Lock 3",
    "4": "Lock 4",
    "5": "Lock 5"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 79,
   "documented": "004FH",
   "name": "Sensor correction coefficient",
   "description": "Decimal point ignored: Raw integer; apply the decimal point setting.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 80,
   "documented": "0050H",
   "name": "Sensor correction",
   "description": "Decimal point ignored: Raw integer; apply the decimal point setting.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 81,
   "documented": "0051H",
   "name": "PV filter time constant",
   "description": "Decimal point ignored: Raw integer; apply the decimal point setting.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 82,
   "documented": "0052H",
   "name": "Response delay time",
   "description": "Comm response delay.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 83,
   "documented": "0053H",
   "name": "SVTC bias",
   "description": "Decimal point ignored: Raw integer; apply the decimal point setting.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 84,
   "documented": "0054H",
   "name": "External setting input high limit",
   "description": "Decimal point ignored: Raw integer; apply the decimal point setting.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 85,
   "documented": "0055H",
   "name": "External setting input low limit",
   "description": "Decimal point ignored: Raw integer; apply the decimal point setting.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 86,
   "documented": "0056H",
   "name": "Remote bias",
   "description": "Decimal point ignored: Raw integer; apply the decimal point setting.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 87,
   "documented": "0057H",
   "name": "SV rise/fall rate start type",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "SV start",
    "1": "PV start"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 88,
   "documented": "0058H",
   "name": "SV rise rate",
   "description": "Decimal point ignored: Raw integer; apply the decimal point setting.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 89,
   "documented": "0059H",
   "name": "SV fall rate",
   "description": "Decimal point ignored: Raw integer; apply the decimal point setting.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 90,
   "documented": "005AH",
   "name": "Indication when control output OFF",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "OFF indication",
    "1": "No indication",
    "2": "PV indication",
    "3": "PV indication + any alarm active"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 91,
   "documented": "005BH",
   "name": "AT bias",
   "description": "Decimal point ignored: Raw integer; apply the decimal point setting.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 92,
   "documented": "005CH",
   "name": "Output status when input errors occur",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Output OFF",
    "1": "Output ON"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 93,
   "documented": "005DH",
   "name": "Auto/manual after power ON",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Automatic control",
    "1": "Manual control"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 224,
   "documented": "00E0H",
   "name": "OUT/OFF key function",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Control output OFF function",
    "1": "Auto/Manual control",
    "2": "Program control"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 225,
   "documented": "00E1H",
   "name": "Remote/local",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Local",
    "1": "Remote"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 226,
   "documented": "00E2H",
   "name": "Output OFF / Auto-Manual / Program RUN",
   "description": "Meaning follows the OUT/OFF key function (00E0H); see notes.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 227,
   "documented": "00E3H",
   "name": "Program control holding",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Not holding",
    "1": "Holding"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 228,
   "documented": "00E4H",
   "name": "Output by communication command",
   "description": "",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": {
    "0": "EV1 output on",
    "1": "EV2 output on"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 229,
   "documented": "00E5H",
   "name": "Manual control MV",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 230,
   "documented": "00E6H",
   "name": "AT/Auto-reset perform/cancel",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Cancel AT / AT on startup / auto-reset",
    "1": "AT/Auto-reset perform",
    "2": "AT on startup perform"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 231,
   "documented": "00E7H",
   "name": "Controller/converter",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Controller",
    "1": "Converter"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 232,
   "documented": "00E8H",
   "name": "AT gain",
   "description": "Decimal point ignored: Raw integer; apply the decimal point setting.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 233,
   "documented": "00E9H",
   "name": "Program control advance",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "W",
   "values": {
    "1": "Advance perform"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 254,
   "documented": "00FEH",
   "name": "Data clear",
   "description": "Resets all settings to factory defaults.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "W",
   "values": {
    "4660": "Clear data (1234H)"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 255,
   "documented": "00FFH",
   "name": "Key operation change flag clearing",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "W",
   "values": {
    "1": "Clear the flag"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 256,
   "documented": "0100H",
   "name": "PV",
   "description": "Process value. Decimal point ignored: Raw integer; apply the decimal point setting.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 257,
   "documented": "0101H",
   "name": "OUT1 MV",
   "description": "Decimal point ignored: Raw integer; apply the decimal point setting.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 258,
   "documented": "0102H",
   "name": "OUT2 MV",
   "description": "Decimal point ignored: Raw integer; apply the decimal point setting.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 259,
   "documented": "0103H",
   "name": "Current SV",
   "description": "Decimal point ignored: Raw integer; apply the decimal point setting.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 260,
   "documented": "0104H",
   "name": "Set value memory number",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 261,
   "documented": "0105H",
   "name": "Remaining time (program)",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 263,
   "documented": "0107H",
   "name": "Step number (program)",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 264,
   "documented": "0108H",
   "name": "Number of repetitions (program)",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 265,
   "documented": "0109H",
   "name": "CT1 current value",
   "description": "Decimal point ignored: Raw integer; apply the decimal point setting.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 266,
   "documented": "010AH",
   "name": "CT2 current value",
   "description": "Decimal point ignored: Raw integer; apply the decimal point setting.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 268,
   "documented": "010CH",
   "name": "Key operation changed item",
   "description": "Data item last changed from the keypad.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 269,
   "documented": "010DH",
   "name": "Status flag 1",
   "description": "",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "0": "OUT1 output on",
    "1": "OUT2 output on",
    "2": "EV1 output on",
    "3": "EV2 output on",
    "9": "AT/auto-reset/AT on startup performing",
    "10": "1 = AT on startup, 0 = AT/auto-reset",
    "11": "Heater burnout alarm",
    "12": "Loop break alarm",
    "13": "Overscale",
    "14": "Underscale",
    "15": "Settings changed by keypad"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 270,
   "documented": "010EH",
   "name": "Status flag 2",
   "description": "",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "0": "DI1 input on",
    "1": "DI2 input on",
    "5": "Program control RUN (unit status 1)",
    "6": "Setting mode (unit status 2)",
    "7": "Warm-up",
    "8": "USB connection",
    "9": "Control output OFF",
    "10": "Manual control",
    "11": "Program control mode",
    "12": "Program control RUN",
    "13": "Wait function on",
    "14": "Hold function on",
    "15": "Pattern end function on"
   },
   "offset": 0
  }
 ],
 "page": "https://easymodbus.com/modbus-register-maps/shinko-technos/bcx2",
 "address_note": "address = 0-based Modbus wire (PDU) address; documented = as printed in the source.",
 "note": "Re-typed from the manufacturer's public documentation (see source) and verified against it. Registers vary by firmware and options; verify against the live device before writing."
}