{
 "manufacturer": "Shinko Technos",
 "manufacturer_slug": "shinko-technos",
 "model": "DCL-33A DC digital indicating controller (C5 option)",
 "model_slug": "dcl-33a-dc",
 "short_model": "DCL-33A DC",
 "aliases": [
  "DCL-33A DC",
  "DCL-33A-DC-C5"
 ],
 "equipment_type": "Sensor (digital temperature controller)",
 "applies_to": "Shinko DCL-33A DC with the C5 option; communication manual No.DCL3CDCE2.",
 "summary": "The DCL-33A DC is a Shinko PID temperature controller variant with its own communication manual and command table. With the C5 option it speaks Shinko protocol, Modbus ASCII or Modbus RTU on RS485; all items are signed 16-bit holding registers. The map covers SV, PID, alarm, heater burnout and loop break settings, input type, PV, MV, status and heater current.",
 "transport": [
  "RTU",
  "ASCII"
 ],
 "defaults": {
  "unit_id": 0,
  "baud": 9600,
  "parity": "Even",
  "data_bits": 8,
  "stop_bits": 1,
  "tcp_port": null
 },
 "addressing": {
  "convention": "hex 0-based",
  "note": "Registers are listed as hex data items (0001H) that go into the request unchanged. The manual adds that the matching Modicon holding-register number is the item in decimal plus 40001 (0001H = 40002)."
 },
 "default_word_order": null,
 "firmware": null,
 "source": {
  "title": "Communication Instruction Manual DCL-33A DC (C5)",
  "doc_number": "No.DCL3CDCE2",
  "revision_date": "2014-03",
  "url": "https://shinko-technos.co.jp/e/manual/english/DCL3CDCE2.pdf",
  "pages": "Section 7 command table, pp. 11-13; communication settings p. 2"
 },
 "notes": [
  "All data are 16-bit two's complement. Values with a decimal point are sent as whole numbers; apply the decimal point place (001AH).",
  "Units of PID times, cycles and MV are not printed in the command table.",
  "Protocol, instrument number, speed, parity and stop bit are keypad-only settings."
 ],
 "integration": {
  "summary": "Choose Modbus RTU in Auxiliary function setting mode 1 and set a non-zero instrument number, then poll PV 0080H, MV 0081H/0082H and status 0085H; write SV at 0001H.",
  "minimum_registers": [
   {
    "table": "holding_register",
    "address": 128,
    "why": "Process value"
   },
   {
    "table": "holding_register",
    "address": 1,
    "why": "Set value"
   },
   {
    "table": "holding_register",
    "address": 129,
    "why": "OUT1 manipulated value"
   },
   {
    "table": "holding_register",
    "address": 133,
    "why": "Status bits"
   },
   {
    "table": "holding_register",
    "address": 26,
    "why": "Decimal point for scaling"
   }
  ],
  "enable": "Requires the C5 option. Hold the key pair shown on p. 2 for 3 s to enter Auxiliary function setting mode 1, press the advance key twice to reach Communication protocol, choose Modbus RTU, then set instrument number, speed, parity and stop bit.",
  "watchdog": null,
  "quirks": [
   "Instrument number defaults to 0, the Modbus broadcast address; set 1-95."
  ],
  "setup": [
   "Factory defaults: Shinko protocol, instrument 0, 9600 bps, even parity, 1 stop bit.",
   "Speeds 2400, 4800, 9600, 19200 bps."
  ],
  "gotchas": [
   "This map differs from the DCL-33A manual DCL32CE3; check which manual matches the unit."
  ]
 },
 "registers": [
  {
   "table": "holding_register",
   "address": 1,
   "documented": "0001H",
   "name": "SV",
   "description": "Set value. Raw integer; apply the decimal point setting.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 3,
   "documented": "0003H",
   "name": "AT perform/cancel",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Cancel",
    "1": "Perform"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 4,
   "documented": "0004H",
   "name": "OUT1 proportional band",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 5,
   "documented": "0005H",
   "name": "OUT2 proportional band",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 6,
   "documented": "0006H",
   "name": "Integral time",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 7,
   "documented": "0007H",
   "name": "Derivative time",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8,
   "documented": "0008H",
   "name": "OUT1 proportional cycle",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 9,
   "documented": "0009H",
   "name": "OUT2 proportional cycle",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 10,
   "documented": "000AH",
   "name": "Manual reset",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 11,
   "documented": "000BH",
   "name": "Alarm value",
   "description": "Raw integer; apply the decimal point setting.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 15,
   "documented": "000FH",
   "name": "Heater burnout alarm value",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 16,
   "documented": "0010H",
   "name": "Loop break alarm time",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 17,
   "documented": "0011H",
   "name": "Loop break alarm span",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 18,
   "documented": "0012H",
   "name": "Set value lock",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Unlock",
    "1": "Lock 1",
    "2": "Lock 2",
    "3": "Lock 3"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 21,
   "documented": "0015H",
   "name": "Sensor correction value",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 22,
   "documented": "0016H",
   "name": "Overlap/dead band",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 24,
   "documented": "0018H",
   "name": "Scaling high limit",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 25,
   "documented": "0019H",
   "name": "Scaling low limit",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 26,
   "documented": "001AH",
   "name": "Decimal point place",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "XXXX",
    "1": "XXX.X",
    "2": "XX.XX",
    "3": "X.XXX"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 27,
   "documented": "001BH",
   "name": "PV filter time constant",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 28,
   "documented": "001CH",
   "name": "OUT1 high limit",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 29,
   "documented": "001DH",
   "name": "OUT1 low limit",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 30,
   "documented": "001EH",
   "name": "OUT1 ON/OFF hysteresis",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 31,
   "documented": "001FH",
   "name": "OUT2 action mode",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Air cooling (linear)",
    "1": "Oil cooling (1.5th power)",
    "2": "Water cooling (2nd power)"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 32,
   "documented": "0020H",
   "name": "OUT2 high limit",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 33,
   "documented": "0021H",
   "name": "OUT2 low limit",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 34,
   "documented": "0022H",
   "name": "OUT2 ON/OFF hysteresis",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 35,
   "documented": "0023H",
   "name": "Alarm type",
   "description": "Changing it resets the alarm value to 0.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "No alarm action",
    "1": "High limit alarm",
    "2": "Low limit alarm",
    "3": "High/Low limits alarm",
    "4": "High/Low limit range alarm",
    "5": "Process high alarm",
    "6": "Process low alarm",
    "7": "High limit with standby",
    "8": "Low limit with standby",
    "9": "High/Low limits with standby"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 37,
   "documented": "0025H",
   "name": "Alarm hysteresis",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 41,
   "documented": "0029H",
   "name": "Alarm action delay time",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 64,
   "documented": "0040H",
   "name": "Alarm energized/de-energized",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Energized",
    "1": "De-energized"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 66,
   "documented": "0042H",
   "name": "Alarm HOLD function",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Alarm not holding",
    "1": "Alarm holding"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 68,
   "documented": "0044H",
   "name": "Input type",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "K -200 to 1370 C",
    "1": "K -199.9 to 400.0 C",
    "2": "J -200 to 1000 C",
    "3": "R 0 to 1760 C",
    "4": "S 0 to 1760 C",
    "5": "B 0 to 1820 C",
    "6": "E -200 to 800 C",
    "7": "T -199.9 to 400.0 C",
    "8": "N -200 to 1300 C",
    "9": "PL-II 0 to 1390 C",
    "10": "C (W/Re5-26) 0 to 2315 C",
    "11": "Pt100 -199.9 to 850.0 C",
    "12": "JPt100 -199.9 to 500.0 C",
    "13": "Pt100 -200 to 850 C",
    "14": "JPt100 -200 to 500 C",
    "15": "K -320 to 2500 F",
    "16": "K -199.9 to 750.0 F",
    "17": "J -320 to 1800 F",
    "18": "R 0 to 3200 F",
    "19": "S 0 to 3200 F",
    "20": "B 0 to 3300 F",
    "21": "E -320 to 1500 F",
    "22": "T -199.9 to 750.0 F",
    "23": "N -320 to 2300 F",
    "24": "PL-II 0 to 2500 F",
    "25": "C (W/Re5-26) 0 to 4200 F",
    "26": "Pt100 -199.9 to 999.9 F",
    "27": "JPt100 -199.9 to 900.0 F",
    "28": "Pt100 -300 to 1500 F",
    "29": "JPt100 -300 to 900 F",
    "30": "4-20 mA DC",
    "31": "0-20 mA DC",
    "32": "0-1 V DC",
    "33": "0-5 V DC",
    "34": "1-5 V DC",
    "35": "0-10 V DC"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 69,
   "documented": "0045H",
   "name": "Direct/reverse control action",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Heating (reverse)",
    "1": "Cooling (direct)"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 71,
   "documented": "0047H",
   "name": "AT bias",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 72,
   "documented": "0048H",
   "name": "ARW",
   "description": "Anti-reset windup.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 111,
   "documented": "006FH",
   "name": "Key lock",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Key enabled",
    "1": "Key locked"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 112,
   "documented": "0070H",
   "name": "Key operation change flag clearing",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "W",
   "values": {
    "0": "No action",
    "1": "Clear all"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 128,
   "documented": "0080H",
   "name": "PV",
   "description": "Process value. Raw integer; apply the decimal point setting.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 129,
   "documented": "0081H",
   "name": "OUT1 MV",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 130,
   "documented": "0082H",
   "name": "OUT2 MV",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 133,
   "documented": "0085H",
   "name": "Status flag",
   "description": "",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "0": "OUT1 on",
    "1": "OUT2 on",
    "2": "Alarm output on",
    "6": "Heater burnout alarm output",
    "7": "Loop break alarm output",
    "8": "Overscale",
    "9": "Underscale",
    "11": "AT running",
    "13": "1 = converter, 0 = controller",
    "15": "Settings changed by keypad"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 134,
   "documented": "0086H",
   "name": "Heater current value",
   "description": "Held value while OUT1 is on.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  }
 ],
 "page": "https://easymodbus.com/modbus-register-maps/shinko-technos/dcl-33a-dc",
 "address_note": "address = 0-based Modbus wire (PDU) address; documented = as printed in the source.",
 "note": "Re-typed from the manufacturer's public documentation (see source) and verified against it. Registers vary by firmware and options; verify against the live device before writing."
}
