 "manufacturer": "Shinko Technos",
 "manufacturer_slug": "shinko-technos",
 "model": "GR200 paperless recorder (Modbus RTU / Modbus TCP)",
 "model_slug": "gr200",
 "short_model": "GR200",
 "aliases": [
  "GR200"
 ],
 "equipment_type": "Sensor (paperless recorder)",
 "applies_to": "Shinko GR200 paperless recorder with RS-485 Modbus RTU or Ethernet Modbus TCP; manual GR2CE1.",
 "summary": "The GR200 is an up-to-18-channel paperless recorder. It is a Modbus RTU slave on RS-485 and also answers Modbus TCP on port 502 over Ethernet. This map covers the read-only measured values and channel status for all 18 channels plus the per-channel range, scaling and decimal point settings needed to interpret them.",
 "transport": [
  "RTU",
  "TCP"
 ],
 "defaults": {
  "unit_id": 1,
  "baud": 19200,
  "parity": "Odd",
  "data_bits": 8,
  "stop_bits": 1,
  "tcp_port": 502
 },
 "addressing": {
  "convention": "Modicon",
  "note": "Registers are printed as 30xxx/40xxx numbers; the manual says the address in the message is the lower four digits minus 1 (40003 is sent as 0002). The manual's example reads CH2 measured value (30102) at relative address 0065H."
 },
 "default_word_order": null,
 "firmware": null,
 "source": {
  "title": "Instruction Manual Paperless Recorder Communication Functions (RS-485 MODBUS/Ethernet) Type GR200",
  "doc_number": "GR2CE1",
  "revision_date": "2008-07",
  "url": "https://shinko-technos.co.jp/e/manual/english/GR2CE1.pdf",
  "pages": "Settings p. 6; addressing p. 13; data format p. 23; maps pp. 24-36"
 },
 "notes": [
  "Long (2-register) values such as totalizer counts and totalizing times are left out: the manual says one value spans two registers but never states which word comes first.",
  "Channel setting blocks are 64 registers apart: CH1 starts at 40001, CH2 at 40065 ... CH18 at 41089.",
  "Holding registers are read with function 03 and written with 10H; the map lists no single-register write (06).",
  "Tags, colours, totalizer, alarm, display and network settings are omitted; the manual's Table 2 and Table 5 code lists are not reproduced.",
  "Measured values carry no decimal point; place it from the channel's decimal point setting."
 ],
 "integration": {
  "summary": "Read input registers 30101-30118 for the measured values and 30131-30148 for channel status in one block each with function 04, and read each channel's decimal point setting once with function 03.",
  "minimum_registers": [
   {
    "table": "input_register",
    "address": 100,
    "why": "CH1 measured value"
   },
   {
    "table": "input_register",
    "address": 130,
    "why": "CH1 status"
   },
   {
    "table": "holding_register",
    "address": 17,
    "why": "CH1 decimal point"
   },
   {
    "table": "holding_register",
    "address": 15,
    "why": "CH1 engineering start"
   },
   {
    "table": "holding_register",
    "address": 16,
    "why": "CH1 engineering end"
   },
   {
    "table": "input_register",
    "address": 85,
    "why": "Memory card utilization"
   }
  ],
  "enable": "Set MODBUS Station No. (0-255; 0 stops communication), speed and parity on the front panel. For Modbus TCP (port 502) also turn the MODBUS TCP/IP function ON (factory OFF) and cycle power.",
  "watchdog": null,
  "quirks": [
   "Out-of-range readings come back as 32767 (over), -32767 (under) or -32768 (burnout/error); check the status registers.",
   "The recorder accepts written values outside the setting range without complaint."
  ],
  "setup": [
   "Factory defaults: station 1, 19200 bps, odd parity, 8 data bits, 1 stop bit (8 bits and 1 stop bit are fixed). Up to 31 units per RS-485 line."
  ],
  "gotchas": [
   "A read is limited to 64 registers per message."
  ]
 },
 "registers": [
  {
   "table": "input_register",
   "address": 85,
   "documented": "30086",
   "name": "Memory card utilization",
   "description": "0-1000 = 0.0-100.0 %; 1000 means full.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 100,
   "documented": "30101",
   "name": "CH1 measured value",
   "description": "No decimal point sent; 32767 over, -32767 under, -32768 burnout/error.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 101,
   "documented": "30102",
   "name": "CH2 measured value",
   "description": "No decimal point sent; 32767 over, -32767 under, -32768 burnout/error.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 102,
   "documented": "30103",
   "name": "CH3 measured value",
   "description": "No decimal point sent; 32767 over, -32767 under, -32768 burnout/error.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 103,
   "documented": "30104",
   "name": "CH4 measured value",
   "description": "No decimal point sent; 32767 over, -32767 under, -32768 burnout/error.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 104,
   "documented": "30105",
   "name": "CH5 measured value",
   "description": "No decimal point sent; 32767 over, -32767 under, -32768 burnout/error.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 105,
   "documented": "30106",
   "name": "CH6 measured value",
   "description": "No decimal point sent; 32767 over, -32767 under, -32768 burnout/error.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 106,
   "documented": "30107",
   "name": "CH7 measured value",
   "description": "No decimal point sent; 32767 over, -32767 under, -32768 burnout/error.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 107,
   "documented": "30108",
   "name": "CH8 measured value",
   "description": "No decimal point sent; 32767 over, -32767 under, -32768 burnout/error.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 108,
   "documented": "30109",
   "name": "CH9 measured value",
   "description": "No decimal point sent; 32767 over, -32767 under, -32768 burnout/error.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 109,
   "documented": "30110",
   "name": "CH10 measured value",
   "description": "No decimal point sent; 32767 over, -32767 under, -32768 burnout/error.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 110,
   "documented": "30111",
   "name": "CH11 measured value",
   "description": "No decimal point sent; 32767 over, -32767 under, -32768 burnout/error.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 111,
   "documented": "30112",
   "name": "CH12 measured value",
   "description": "No decimal point sent; 32767 over, -32767 under, -32768 burnout/error.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 112,
   "documented": "30113",
   "name": "CH13 measured value",
   "description": "No decimal point sent; 32767 over, -32767 under, -32768 burnout/error.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 113,
   "documented": "30114",
   "name": "CH14 measured value",
   "description": "No decimal point sent; 32767 over, -32767 under, -32768 burnout/error.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 114,
   "documented": "30115",
   "name": "CH15 measured value",
   "description": "No decimal point sent; 32767 over, -32767 under, -32768 burnout/error.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 115,
   "documented": "30116",
   "name": "CH16 measured value",
   "description": "No decimal point sent; 32767 over, -32767 under, -32768 burnout/error.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 116,
   "documented": "30117",
   "name": "CH17 measured value",
   "description": "No decimal point sent; 32767 over, -32767 under, -32768 burnout/error.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 117,
   "documented": "30118",
   "name": "CH18 measured value",
   "description": "No decimal point sent; 32767 over, -32767 under, -32768 burnout/error.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 130,
   "documented": "30131",
   "name": "CH1 status",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Normal",
    "1": "Burnout",
    "2": "Over",
    "3": "Under",
    "4": "Error"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 131,
   "documented": "30132",
   "name": "CH2 status",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Normal",
    "1": "Burnout",
    "2": "Over",
    "3": "Under",
    "4": "Error"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 132,
   "documented": "30133",
   "name": "CH3 status",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Normal",
    "1": "Burnout",
    "2": "Over",
    "3": "Under",
    "4": "Error"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 133,
   "documented": "30134",
   "name": "CH4 status",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Normal",
    "1": "Burnout",
    "2": "Over",
    "3": "Under",
    "4": "Error"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 134,
   "documented": "30135",
   "name": "CH5 status",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Normal",
    "1": "Burnout",
    "2": "Over",
    "3": "Under",
    "4": "Error"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 135,
   "documented": "30136",
   "name": "CH6 status",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Normal",
    "1": "Burnout",
    "2": "Over",
    "3": "Under",
    "4": "Error"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 136,
   "documented": "30137",
   "name": "CH7 status",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Normal",
    "1": "Burnout",
    "2": "Over",
    "3": "Under",
    "4": "Error"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 137,
   "documented": "30138",
   "name": "CH8 status",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Normal",
    "1": "Burnout",
    "2": "Over",
    "3": "Under",
    "4": "Error"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 138,
   "documented": "30139",
   "name": "CH9 status",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Normal",
    "1": "Burnout",
    "2": "Over",
    "3": "Under",
    "4": "Error"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 139,
   "documented": "30140",
   "name": "CH10 status",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Normal",
    "1": "Burnout",
    "2": "Over",
    "3": "Under",
    "4": "Error"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 140,
   "documented": "30141",
   "name": "CH11 status",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Normal",
    "1": "Burnout",
    "2": "Over",
    "3": "Under",
    "4": "Error"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 141,
   "documented": "30142",
   "name": "CH12 status",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Normal",
    "1": "Burnout",
    "2": "Over",
    "3": "Under",
    "4": "Error"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 142,
   "documented": "30143",
   "name": "CH13 status",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Normal",
    "1": "Burnout",
    "2": "Over",
    "3": "Under",
    "4": "Error"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 143,
   "documented": "30144",
   "name": "CH14 status",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Normal",
    "1": "Burnout",
    "2": "Over",
    "3": "Under",
    "4": "Error"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 144,
   "documented": "30145",
   "name": "CH15 status",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Normal",
    "1": "Burnout",
    "2": "Over",
    "3": "Under",
    "4": "Error"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 145,
   "documented": "30146",
   "name": "CH16 status",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Normal",
    "1": "Burnout",
    "2": "Over",
    "3": "Under",
    "4": "Error"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 146,
   "documented": "30147",
   "name": "CH17 status",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Normal",
    "1": "Burnout",
    "2": "Over",
    "3": "Under",
    "4": "Error"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 147,
   "documented": "30148",
   "name": "CH18 status",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Normal",
    "1": "Burnout",
    "2": "Over",
    "3": "Under",
    "4": "Error"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 9,
   "documented": "40010",
   "name": "CH1 input type",
   "description": "Code 0-40, see manual Table 2.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 12,
   "documented": "40013",
   "name": "CH1 scaling",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "OFF",
    "1": "ON"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 15,
   "documented": "40016",
   "name": "CH1 engineering start",
   "description": "Scaled low end; decimal point per 'decimal point' item.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 16,
   "documented": "40017",
   "name": "CH1 engineering end",
   "description": "Scaled high end; decimal point per 'decimal point' item.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 17,
   "documented": "40018",
   "name": "CH1 decimal point",
   "description": "Code 0-4 (manual Table 5); places the measured value decimal point.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 25,
   "documented": "40026",
   "name": "CH1 recording mode",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "With record",
    "1": "Display only"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 73,
   "documented": "40074",
   "name": "CH2 input type",
   "description": "Code 0-40, see manual Table 2.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 76,
   "documented": "40077",
   "name": "CH2 scaling",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "OFF",
    "1": "ON"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 79,
   "documented": "40080",
   "name": "CH2 engineering start",
   "description": "Scaled low end; decimal point per 'decimal point' item.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 80,
   "documented": "40081",
   "name": "CH2 engineering end",
   "description": "Scaled high end; decimal point per 'decimal point' item.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 81,
   "documented": "40082",
   "name": "CH2 decimal point",
   "description": "Code 0-4 (manual Table 5); places the measured value decimal point.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 89,
   "documented": "40090",
   "name": "CH2 recording mode",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "With record",
    "1": "Display only"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 137,
   "documented": "40138",
   "name": "CH3 input type",
   "description": "Code 0-40, see manual Table 2.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 140,
   "documented": "40141",
   "name": "CH3 scaling",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "OFF",
    "1": "ON"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 143,
   "documented": "40144",
   "name": "CH3 engineering start",
   "description": "Scaled low end; decimal point per 'decimal point' item.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 144,
   "documented": "40145",
   "name": "CH3 engineering end",
   "description": "Scaled high end; decimal point per 'decimal point' item.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 145,
   "documented": "40146",
   "name": "CH3 decimal point",
   "description": "Code 0-4 (manual Table 5); places the measured value decimal point.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 153,
   "documented": "40154",
   "name": "CH3 recording mode",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "With record",
    "1": "Display only"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 201,
   "documented": "40202",
   "name": "CH4 input type",
   "description": "Code 0-40, see manual Table 2.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 204,
   "documented": "40205",
   "name": "CH4 scaling",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "OFF",
    "1": "ON"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 207,
   "documented": "40208",
   "name": "CH4 engineering start",
   "description": "Scaled low end; decimal point per 'decimal point' item.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 208,
   "documented": "40209",
   "name": "CH4 engineering end",
   "description": "Scaled high end; decimal point per 'decimal point' item.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 209,
   "documented": "40210",
   "name": "CH4 decimal point",
   "description": "Code 0-4 (manual Table 5); places the measured value decimal point.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 217,
   "documented": "40218",
   "name": "CH4 recording mode",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "With record",
    "1": "Display only"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 265,
   "documented": "40266",
   "name": "CH5 input type",
   "description": "Code 0-40, see manual Table 2.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 268,
   "documented": "40269",
   "name": "CH5 scaling",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "OFF",
    "1": "ON"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 271,
   "documented": "40272",
   "name": "CH5 engineering start",
   "description": "Scaled low end; decimal point per 'decimal point' item.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 272,
   "documented": "40273",
   "name": "CH5 engineering end",
   "description": "Scaled high end; decimal point per 'decimal point' item.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 273,
   "documented": "40274",
   "name": "CH5 decimal point",
   "description": "Code 0-4 (manual Table 5); places the measured value decimal point.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 281,
   "documented": "40282",
   "name": "CH5 recording mode",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "With record",
    "1": "Display only"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 329,
   "documented": "40330",
   "name": "CH6 input type",
   "description": "Code 0-40, see manual Table 2.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 332,
   "documented": "40333",
   "name": "CH6 scaling",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "OFF",
    "1": "ON"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 335,
   "documented": "40336",
   "name": "CH6 engineering start",
   "description": "Scaled low end; decimal point per 'decimal point' item.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 336,
   "documented": "40337",
   "name": "CH6 engineering end",
   "description": "Scaled high end; decimal point per 'decimal point' item.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 337,
   "documented": "40338",
   "name": "CH6 decimal point",
   "description": "Code 0-4 (manual Table 5); places the measured value decimal point.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 345,
   "documented": "40346",
   "name": "CH6 recording mode",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "With record",
    "1": "Display only"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 393,
   "documented": "40394",
   "name": "CH7 input type",
   "description": "Code 0-40, see manual Table 2.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 396,
   "documented": "40397",
   "name": "CH7 scaling",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "OFF",
    "1": "ON"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 399,
   "documented": "40400",
   "name": "CH7 engineering start",
   "description": "Scaled low end; decimal point per 'decimal point' item.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 400,
   "documented": "40401",
   "name": "CH7 engineering end",
   "description": "Scaled high end; decimal point per 'decimal point' item.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 401,
   "documented": "40402",
   "name": "CH7 decimal point",
   "description": "Code 0-4 (manual Table 5); places the measured value decimal point.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 409,
   "documented": "40410",
   "name": "CH7 recording mode",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "With record",
    "1": "Display only"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 457,
   "documented": "40458",
   "name": "CH8 input type",
   "description": "Code 0-40, see manual Table 2.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 460,
   "documented": "40461",
   "name": "CH8 scaling",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "OFF",
    "1": "ON"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 463,
   "documented": "40464",
   "name": "CH8 engineering start",
   "description": "Scaled low end; decimal point per 'decimal point' item.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 464,
   "documented": "40465",
   "name": "CH8 engineering end",
   "description": "Scaled high end; decimal point per 'decimal point' item.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 465,
   "documented": "40466",
   "name": "CH8 decimal point",
   "description": "Code 0-4 (manual Table 5); places the measured value decimal point.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 473,
   "documented": "40474",
   "name": "CH8 recording mode",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "With record",
    "1": "Display only"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 521,
   "documented": "40522",
   "name": "CH9 input type",
   "description": "Code 0-40, see manual Table 2.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 524,
   "documented": "40525",
   "name": "CH9 scaling",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "OFF",
    "1": "ON"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 527,
   "documented": "40528",
   "name": "CH9 engineering start",
   "description": "Scaled low end; decimal point per 'decimal point' item.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 528,
   "documented": "40529",
   "name": "CH9 engineering end",
   "description": "Scaled high end; decimal point per 'decimal point' item.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 529,
   "documented": "40530",
   "name": "CH9 decimal point",
   "description": "Code 0-4 (manual Table 5); places the measured value decimal point.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 537,
   "documented": "40538",
   "name": "CH9 recording mode",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "With record",
    "1": "Display only"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 585,
   "documented": "40586",
   "name": "CH10 input type",
   "description": "Code 0-40, see manual Table 2.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 588,
   "documented": "40589",
   "name": "CH10 scaling",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "OFF",
    "1": "ON"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 591,
   "documented": "40592",
   "name": "CH10 engineering start",
   "description": "Scaled low end; decimal point per 'decimal point' item.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 592,
   "documented": "40593",
   "name": "CH10 engineering end",
   "description": "Scaled high end; decimal point per 'decimal point' item.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 593,
   "documented": "40594",
   "name": "CH10 decimal point",
   "description": "Code 0-4 (manual Table 5); places the measured value decimal point.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 601,
   "documented": "40602",
   "name": "CH10 recording mode",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "With record",
    "1": "Display only"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 649,
   "documented": "40650",
   "name": "CH11 input type",
   "description": "Code 0-40, see manual Table 2.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 652,
   "documented": "40653",
   "name": "CH11 scaling",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "OFF",
    "1": "ON"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 655,
   "documented": "40656",
   "name": "CH11 engineering start",
   "description": "Scaled low end; decimal point per 'decimal point' item.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 656,
   "documented": "40657",
   "name": "CH11 engineering end",
   "description": "Scaled high end; decimal point per 'decimal point' item.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 657,
   "documented": "40658",
   "name": "CH11 decimal point",
   "description": "Code 0-4 (manual Table 5); places the measured value decimal point.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 665,
   "documented": "40666",
   "name": "CH11 recording mode",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "With record",
    "1": "Display only"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 713,
   "documented": "40714",
   "name": "CH12 input type",
   "description": "Code 0-40, see manual Table 2.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 716,
   "documented": "40717",
   "name": "CH12 scaling",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "OFF",
    "1": "ON"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 719,
   "documented": "40720",
   "name": "CH12 engineering start",
   "description": "Scaled low end; decimal point per 'decimal point' item.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 720,
   "documented": "40721",
   "name": "CH12 engineering end",
   "description": "Scaled high end; decimal point per 'decimal point' item.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 721,
   "documented": "40722",
   "name": "CH12 decimal point",
   "description": "Code 0-4 (manual Table 5); places the measured value decimal point.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 729,
   "documented": "40730",
   "name": "CH12 recording mode",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "With record",
    "1": "Display only"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 777,
   "documented": "40778",
   "name": "CH13 input type",
   "description": "Code 0-40, see manual Table 2.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 780,
   "documented": "40781",
   "name": "CH13 scaling",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "OFF",
    "1": "ON"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 783,
   "documented": "40784",
   "name": "CH13 engineering start",
   "description": "Scaled low end; decimal point per 'decimal point' item.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 784,
   "documented": "40785",
   "name": "CH13 engineering end",
   "description": "Scaled high end; decimal point per 'decimal point' item.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 785,
   "documented": "40786",
   "name": "CH13 decimal point",
   "description": "Code 0-4 (manual Table 5); places the measured value decimal point.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 793,
   "documented": "40794",
   "name": "CH13 recording mode",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "With record",
    "1": "Display only"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 841,
   "documented": "40842",
   "name": "CH14 input type",
   "description": "Code 0-40, see manual Table 2.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 844,
   "documented": "40845",
   "name": "CH14 scaling",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "OFF",
    "1": "ON"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 847,
   "documented": "40848",
   "name": "CH14 engineering start",
   "description": "Scaled low end; decimal point per 'decimal point' item.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 848,
   "documented": "40849",
   "name": "CH14 engineering end",
   "description": "Scaled high end; decimal point per 'decimal point' item.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 849,
   "documented": "40850",
   "name": "CH14 decimal point",
   "description": "Code 0-4 (manual Table 5); places the measured value decimal point.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 857,
   "documented": "40858",
   "name": "CH14 recording mode",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "With record",
    "1": "Display only"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 905,
   "documented": "40906",
   "name": "CH15 input type",
   "description": "Code 0-40, see manual Table 2.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 908,
   "documented": "40909",
   "name": "CH15 scaling",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "OFF",
    "1": "ON"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 911,
   "documented": "40912",
   "name": "CH15 engineering start",
   "description": "Scaled low end; decimal point per 'decimal point' item.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 912,
   "documented": "40913",
   "name": "CH15 engineering end",
   "description": "Scaled high end; decimal point per 'decimal point' item.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 913,
   "documented": "40914",
   "name": "CH15 decimal point",
   "description": "Code 0-4 (manual Table 5); places the measured value decimal point.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 921,
   "documented": "40922",
   "name": "CH15 recording mode",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "With record",
    "1": "Display only"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 969,
   "documented": "40970",
   "name": "CH16 input type",
   "description": "Code 0-40, see manual Table 2.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 972,
   "documented": "40973",
   "name": "CH16 scaling",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "OFF",
    "1": "ON"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 975,
   "documented": "40976",
   "name": "CH16 engineering start",
   "description": "Scaled low end; decimal point per 'decimal point' item.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 976,
   "documented": "40977",
   "name": "CH16 engineering end",
   "description": "Scaled high end; decimal point per 'decimal point' item.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 977,
   "documented": "40978",
   "name": "CH16 decimal point",
   "description": "Code 0-4 (manual Table 5); places the measured value decimal point.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 985,
   "documented": "40986",
   "name": "CH16 recording mode",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "With record",
    "1": "Display only"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1033,
   "documented": "41034",
   "name": "CH17 input type",
   "description": "Code 0-40, see manual Table 2.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1036,
   "documented": "41037",
   "name": "CH17 scaling",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "OFF",
    "1": "ON"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1039,
   "documented": "41040",
   "name": "CH17 engineering start",
   "description": "Scaled low end; decimal point per 'decimal point' item.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1040,
   "documented": "41041",
   "name": "CH17 engineering end",
   "description": "Scaled high end; decimal point per 'decimal point' item.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1041,
   "documented": "41042",
   "name": "CH17 decimal point",
   "description": "Code 0-4 (manual Table 5); places the measured value decimal point.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1049,
   "documented": "41050",
   "name": "CH17 recording mode",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "With record",
    "1": "Display only"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1097,
   "documented": "41098",
   "name": "CH18 input type",
   "description": "Code 0-40, see manual Table 2.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1100,
   "documented": "41101",
   "name": "CH18 scaling",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "OFF",
    "1": "ON"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1103,
   "documented": "41104",
   "name": "CH18 engineering start",
   "description": "Scaled low end; decimal point per 'decimal point' item.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1104,
   "documented": "41105",
   "name": "CH18 engineering end",
   "description": "Scaled high end; decimal point per 'decimal point' item.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1105,
   "documented": "41106",
   "name": "CH18 decimal point",
   "description": "Code 0-4 (manual Table 5); places the measured value decimal point.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1113,
   "documented": "41114",
   "name": "CH18 recording mode",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "With record",
    "1": "Display only"
   },
   "bits": null,
   "offset": 0
  }
 ],
 "page": "https://easymodbus.com/modbus-register-maps/shinko-technos/gr200",
 "address_note": "address = 0-based Modbus wire (PDU) address; documented = as printed in the source.",
 "note": "Re-typed from the manufacturer's public documentation (see source) and verified against it. Registers vary by firmware and options; verify against the live device before writing."
}