 "manufacturer": "Shinko Technos",
 "manufacturer_slug": "shinko-technos",
 "model": "JCL-33A digital indicating controller (C5 option)",
 "model_slug": "jcl-33a",
 "short_model": "JCL-33A",
 "aliases": [
  "JCL-33A-C5",
  "JCL-33A C5"
 ],
 "equipment_type": "Sensor (digital temperature controller)",
 "applies_to": "Shinko JCL-33A with the C5 option, protocol set to plain 'Modbus RTU mode' or 'Modbus ASCII mode' (not the Block Read/Write modes, which use another layout); manual No.JCL3CE3.",
 "summary": "The JCL-33A is a digital indicating temperature controller; with the C5 option it talks Shinko protocol, Modbus ASCII or Modbus RTU over RS485. Every value is a signed 16-bit holding register. This map covers the set value, PID and alarm settings, input type, run/stop, program steps, PV, MV and the status flags.",
 "transport": [
  "RTU",
  "ASCII"
 ],
 "defaults": {
  "unit_id": 0,
  "baud": 9600,
  "parity": "Even",
  "data_bits": 8,
  "stop_bits": 1,
  "tcp_port": null
 },
 "addressing": {
  "convention": "hex 0-based",
  "note": "Registers are listed as hex data items (0001H) that go into the request unchanged. The manual adds that the matching Modicon holding-register number is the item in decimal plus 40001 (0001H = 40002)."
 },
 "default_word_order": null,
 "firmware": null,
 "source": {
  "title": "Communication Instruction Manual JCL-33A (C5)",
  "doc_number": "No.JCL3CE3",
  "revision_date": "2018-11",
  "url": "https://shinko-technos.co.jp/e/manual/english/JCL3CE3.pdf",
  "pages": "Section 7.1 command table, manual pp. 21-23 (PDF pp. 21-23); data notes p. 29"
 },
 "notes": [
  "This map is for the plain 'Modbus RTU mode' / 'Modbus ASCII mode' protocol setting. The 'Block Read/Write available' protocol settings use a different register layout (section 7.2 of the manual) and are not covered here.",
  "All data are 16-bit; negatives are two's complement. Values with a decimal point are sent as whole numbers, so apply the decimal point place (001AH) or the input type range.",
  "Units of PID times, cycles and MV are not printed in the command table; they match the keypad settings described in the main instruction manual.",
  "Protocol, instrument number, speed, parity and stop bit can only be set from the keypad, not over Modbus.",
  "Writes during keypad setting mode return exception 18 (12H); writes the unit cannot accept now (e.g. during AT) return exception 17 (11H)."
 ],
 "integration": {
  "summary": "Pick Modbus RTU in Auxiliary function setting mode 1, give each unit a non-zero instrument number, then read PV at 0080H and status at 0085H with function 03; write SV1 at 0001H with function 06.",
  "minimum_registers": [
   {
    "table": "holding_register",
    "address": 128,
    "why": "Process value"
   },
   {
    "table": "holding_register",
    "address": 1,
    "why": "Set value SV1"
   },
   {
    "table": "holding_register",
    "address": 129,
    "why": "OUT1 manipulated value"
   },
   {
    "table": "holding_register",
    "address": 133,
    "why": "Output/alarm/error status bits"
   },
   {
    "table": "holding_register",
    "address": 55,
    "why": "Control on/off (run/stop)"
   },
   {
    "table": "holding_register",
    "address": 26,
    "why": "Decimal point for scaling"
   }
  ],
  "enable": "Requires the C5 communication option. Set Communication protocol to Modbus RTU (not the Block Read/Write variant) in Auxiliary function setting mode 1, then instrument number, speed, parity and stop bit.",
  "watchdog": null,
  "quirks": [
   "Instrument number 0 is the factory default but is the Modbus broadcast address, so set 1-95 before polling.",
   "Writable registers accept writes even when the keypad set value lock is on.",
   "ON/OFF register 0037H: 0 = ON (STOP), 1 = OFF (RUN)."
  ],
  "setup": [
   "Factory defaults: Shinko protocol, instrument 0, 9600 bps, even parity, 1 stop bit.",
   "Modbus RTU uses 8 data bits; parity and stop bit are selectable.",
   "Up to 31 units per RS485 line, 1.2 km maximum."
  ],
  "gotchas": [
   "Settings are stored in non-volatile memory rated for about 1,000,000 writes; don't write SV cyclically.",
   "Undefined data items may return random data or errors; use only listed items."
  ]
 },
 "registers": [
  {
   "table": "holding_register",
   "address": 1,
   "documented": "0001H",
   "name": "SV1",
   "description": "Main set value. Raw integer; apply the decimal point setting.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 3,
   "documented": "0003H",
   "name": "AT perform/cancel",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "AT cancel",
    "1": "AT perform"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 4,
   "documented": "0004H",
   "name": "OUT1 proportional band",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 5,
   "documented": "0005H",
   "name": "OUT2 proportional band",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 6,
   "documented": "0006H",
   "name": "Integral time",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 7,
   "documented": "0007H",
   "name": "Derivative time",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8,
   "documented": "0008H",
   "name": "OUT1 proportional cycle",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 9,
   "documented": "0009H",
   "name": "OUT2 proportional cycle",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 10,
   "documented": "000AH",
   "name": "Manual reset",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 11,
   "documented": "000BH",
   "name": "A1 value",
   "description": "Alarm 1 setting. Raw integer; apply the decimal point setting.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 12,
   "documented": "000CH",
   "name": "A2 value",
   "description": "Alarm 2 setting. Raw integer; apply the decimal point setting.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 18,
   "documented": "0012H",
   "name": "Set value lock",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Unlock",
    "1": "Lock 1",
    "2": "Lock 2",
    "3": "Lock 3"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 21,
   "documented": "0015H",
   "name": "Sensor correction",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 22,
   "documented": "0016H",
   "name": "Overlap/dead band",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 24,
   "documented": "0018H",
   "name": "Scaling high limit",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 25,
   "documented": "0019H",
   "name": "Scaling low limit",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 26,
   "documented": "001AH",
   "name": "Decimal point place",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "No decimal point",
    "1": "1 decimal place",
    "2": "2 decimal places",
    "3": "3 decimal places"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 27,
   "documented": "001BH",
   "name": "PV filter time constant",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 28,
   "documented": "001CH",
   "name": "OUT1 high limit",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 29,
   "documented": "001DH",
   "name": "OUT1 low limit",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 30,
   "documented": "001EH",
   "name": "OUT1 ON/OFF hysteresis",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 34,
   "documented": "0022H",
   "name": "OUT2 ON/OFF hysteresis",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 35,
   "documented": "0023H",
   "name": "A1 type",
   "description": "Changing the type resets the A1 value to 0.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "No alarm action",
    "1": "High limit alarm",
    "2": "Low limit alarm",
    "3": "High/Low limits alarm",
    "4": "High/Low limit range alarm",
    "5": "Process high alarm",
    "6": "Process low alarm",
    "7": "High limit with standby",
    "8": "Low limit with standby",
    "9": "High/Low limits with standby",
    "10": "Timer function",
    "11": "Pattern end output"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 36,
   "documented": "0024H",
   "name": "A2 type",
   "description": "Changing the type resets the A2 value to 0.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "No alarm action",
    "1": "High limit alarm",
    "2": "Low limit alarm",
    "3": "High/Low limits alarm",
    "4": "High/Low limit range alarm",
    "5": "Process high alarm",
    "6": "Process low alarm",
    "7": "High limit with standby",
    "8": "Low limit with standby",
    "9": "High/Low limits with standby",
    "10": "Timer function",
    "11": "Pattern end output"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 37,
   "documented": "0025H",
   "name": "A1 hysteresis",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 38,
   "documented": "0026H",
   "name": "A2 hysteresis",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 41,
   "documented": "0029H",
   "name": "A1 delay time",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 42,
   "documented": "002AH",
   "name": "A2 delay time",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 55,
   "documented": "0037H",
   "name": "ON/OFF (RUN/STOP)",
   "description": "Control output on/off; the manual pairs ON with STOP and OFF with RUN.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "ON (STOP)",
    "1": "OFF (RUN)"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 66,
   "documented": "0042H",
   "name": "Alarm HOLD function",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Alarm not holding",
    "1": "Alarm holding"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 68,
   "documented": "0044H",
   "name": "Input type",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "K -200 to 1370 C",
    "1": "K -199.9 to 400.0 C",
    "2": "J -200 to 1000 C",
    "3": "R 0 to 1760 C",
    "4": "S 0 to 1760 C",
    "5": "B 0 to 1820 C",
    "6": "E -200 to 800 C",
    "7": "T -199.9 to 400.0 C",
    "8": "N -200 to 1300 C",
    "9": "PL-II 0 to 1390 C",
    "10": "C (W/Re5-26) 0 to 2315 C",
    "11": "Pt100 -199.9 to 850.0 C",
    "12": "JPt100 -199.9 to 500.0 C",
    "13": "Pt100 -200 to 850 C",
    "14": "JPt100 -200 to 500 C",
    "15": "K -320 to 2500 F",
    "16": "K -199.9 to 750.0 F",
    "17": "J -320 to 1800 F",
    "18": "R 0 to 3200 F",
    "19": "S 0 to 3200 F",
    "20": "B 0 to 3300 F",
    "21": "E -320 to 1500 F",
    "22": "T -199.9 to 750.0 F",
    "23": "N -320 to 2300 F",
    "24": "PL-II 0 to 2500 F",
    "25": "C (W/Re5-26) 0 to 4200 F",
    "26": "Pt100 -199.9 to 999.9 F",
    "27": "JPt100 -199.9 to 900.0 F",
    "28": "Pt100 -300 to 1500 F",
    "29": "JPt100 -300 to 900 F",
    "30": "4-20 mA DC",
    "31": "0-20 mA DC",
    "32": "0-1 V DC",
    "33": "0-5 V DC",
    "34": "1-5 V DC",
    "35": "0-10 V DC"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 69,
   "documented": "0045H",
   "name": "Direct/reverse action",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Reverse (heating)",
    "1": "Direct (cooling)"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 71,
   "documented": "0047H",
   "name": "AT bias",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 72,
   "documented": "0048H",
   "name": "ARW",
   "description": "Anti-reset windup.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 111,
   "documented": "006FH",
   "name": "Key lock",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Key enabled",
    "1": "Key locked"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 112,
   "documented": "0070H",
   "name": "Key operation change flag clearing",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "W",
   "values": {
    "0": "No action",
    "1": "Clear the flag"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 128,
   "documented": "0080H",
   "name": "PV",
   "description": "Process value. Raw integer; apply the decimal point setting.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 129,
   "documented": "0081H",
   "name": "OUT1 MV",
   "description": "Current OUT1 manipulated value; resolution not stated.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 130,
   "documented": "0082H",
   "name": "OUT2 MV",
   "description": "Current OUT2 manipulated value; resolution not stated.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 131,
   "documented": "0083H",
   "name": "Current SV",
   "description": "SV in use now. Raw integer; apply the decimal point setting.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 132,
   "documented": "0084H",
   "name": "Running step remaining time",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 133,
   "documented": "0085H",
   "name": "Status flag",
   "description": "",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "0": "OUT1 on",
    "1": "OUT2 on",
    "2": "A1 output on",
    "3": "A2 output on",
    "8": "Overscale",
    "9": "Underscale",
    "10": "1 = OFF (RUN), 0 = ON (STOP)",
    "11": "AT running",
    "12": "OUT/OFF key: 1 = program control, 0 = output on/off",
    "13": "1 = converter, 0 = controller",
    "15": "Settings changed by keypad"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 134,
   "documented": "0086H",
   "name": "Running step",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 4368,
   "documented": "1110H",
   "name": "Step 1 SV",
   "description": "Same as SV1. Program step set value.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 4369,
   "documented": "1111H",
   "name": "Step 1 time",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 4384,
   "documented": "1120H",
   "name": "Step 2 SV",
   "description": "Program step set value.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 4385,
   "documented": "1121H",
   "name": "Step 2 time",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 4400,
   "documented": "1130H",
   "name": "Step 3 SV",
   "description": "Program step set value.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 4401,
   "documented": "1131H",
   "name": "Step 3 time",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 4416,
   "documented": "1140H",
   "name": "Step 4 SV",
   "description": "Program step set value.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 4417,
   "documented": "1141H",
   "name": "Step 4 time",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 4432,
   "documented": "1150H",
   "name": "Step 5 SV",
   "description": "Program step set value.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 4433,
   "documented": "1151H",
   "name": "Step 5 time",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 4448,
   "documented": "1160H",
   "name": "Step 6 SV",
   "description": "Program step set value.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 4449,
   "documented": "1161H",
   "name": "Step 6 time",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 4464,
   "documented": "1170H",
   "name": "Step 7 SV",
   "description": "Program step set value.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 4465,
   "documented": "1171H",
   "name": "Step 7 time",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 4480,
   "documented": "1180H",
   "name": "Step 8 SV",
   "description": "Program step set value.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 4481,
   "documented": "1181H",
   "name": "Step 8 time",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 4496,
   "documented": "1190H",
   "name": "Step 9 SV",
   "description": "Program step set value.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 4497,
   "documented": "1191H",
   "name": "Step 9 time",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  }
 ],
 "page": "https://easymodbus.com/modbus-register-maps/shinko-technos/jcl-33a",
 "address_note": "address = 0-based Modbus wire (PDU) address; documented = as printed in the source.",
 "note": "Re-typed from the manufacturer's public documentation (see source) and verified against it. Registers vary by firmware and options; verify against the live device before writing."
}