 "manufacturer": "Shinko Technos",
 "manufacturer_slug": "shinko-technos",
 "model": "JIR-301-M digital indicator (C5 option)",
 "model_slug": "jir-301-m",
 "short_model": "JIR-301-M",
 "aliases": [
  "JIR-301-M-C5",
  "JIR-301-M C5"
 ],
 "equipment_type": "Sensor (digital temperature controller)",
 "applies_to": "Shinko JIR-301-M with the C5 option, plain (non-block) Modbus protocol setting; manual No.JIR32CE4.",
 "summary": "The JIR-301-M is a digital indicator with up to three alarm outputs and an optional retransmission output; it measures thermocouple, RTD, current or voltage inputs. With the C5 option it speaks Shinko protocol, Modbus ASCII or Modbus RTU on RS485. The map covers PV, alarm settings and states, input and scaling settings.",
 "transport": [
  "RTU",
  "ASCII"
 ],
 "defaults": {
  "unit_id": 0,
  "baud": 9600,
  "parity": "Even",
  "data_bits": 8,
  "stop_bits": 1,
  "tcp_port": null
 },
 "addressing": {
  "convention": "hex 0-based",
  "note": "Registers are listed as hex data items (0001H) that go into the request unchanged. The manual adds that the matching Modicon holding-register number is the item in decimal plus 40001 (0001H = 40002)."
 },
 "default_word_order": null,
 "firmware": null,
 "source": {
  "title": "Communication Instruction Manual JIR-301-M (C5)",
  "doc_number": "No.JIR32CE4",
  "revision_date": "2023-11",
  "url": "https://shinko-technos.co.jp/e/manual/english/JIR32CE4.pdf",
  "pages": "Section 7.1, pp. 24-26; communication settings p. 3"
 },
 "notes": [
  "This map is for the plain 'MODBUS RTU mode' / 'MODBUS ASCII mode' settings. The 'Block Read/Write available' settings use the different layout of section 7.2 and are not covered.",
  "All data are 16-bit two's complement. Items marked 'decimal point ignored' are whole numbers; apply the decimal point place (0008H).",
  "Item 0018H is not listed in the single-item table and is left out.",
  "Protocol, instrument number, speed, parity and stop bit are keypad-only settings."
 ],
 "integration": {
  "summary": "Choose MODBUS RTU and a non-zero instrument number on the keypad, then read PV at 0080H and status at 0081H with function 03.",
  "minimum_registers": [
   {
    "table": "holding_register",
    "address": 128,
    "why": "Process value"
   },
   {
    "table": "holding_register",
    "address": 129,
    "why": "Alarm and over/underscale status"
   },
   {
    "table": "holding_register",
    "address": 8,
    "why": "Decimal point for scaling"
   },
   {
    "table": "holding_register",
    "address": 1,
    "why": "Alarm 1 value"
   }
  ],
  "enable": "Requires the C5 option. In the keypad setup, step with the MODE key to Communication protocol and pick MODBUS RTU mode, then set instrument number, speed, parity and stop bit.",
  "watchdog": null,
  "quirks": [
   "Instrument number defaults to 0, the Modbus broadcast address; set 1-95.",
   "Parity and stop bit only apply to the Modbus settings."
  ],
  "setup": [
   "Factory defaults: Shinko protocol, instrument 0, 9600 bps, even parity, 1 stop bit.",
   "Speeds 2400-38400 bps."
  ],
  "gotchas": [
   "Settings are stored in non-volatile memory; avoid cyclic writes."
  ]
 },
 "registers": [
  {
   "table": "holding_register",
   "address": 1,
   "documented": "0001H",
   "name": "A1 value",
   "description": "Decimal point ignored: Raw integer; apply the decimal point setting.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2,
   "documented": "0002H",
   "name": "A2 value",
   "description": "Decimal point ignored: Raw integer; apply the decimal point setting.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 3,
   "documented": "0003H",
   "name": "A3 value",
   "description": "Decimal point ignored: Raw integer; apply the decimal point setting.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 4,
   "documented": "0004H",
   "name": "Set value lock",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Unlock",
    "1": "Lock 1",
    "2": "Lock 2",
    "3": "Lock 3"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 5,
   "documented": "0005H",
   "name": "Sensor correction",
   "description": "Decimal point ignored: Raw integer; apply the decimal point setting.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 6,
   "documented": "0006H",
   "name": "Scaling high limit",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 7,
   "documented": "0007H",
   "name": "Scaling low limit",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8,
   "documented": "0008H",
   "name": "Decimal point place",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "XXXX",
    "1": "XXX.X",
    "2": "XX.XX",
    "3": "X.XXX"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 9,
   "documented": "0009H",
   "name": "PV filter time constant",
   "description": "Decimal point ignored: Raw integer; apply the decimal point setting.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 10,
   "documented": "000AH",
   "name": "A1 hysteresis",
   "description": "Decimal point ignored: Raw integer; apply the decimal point setting.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 11,
   "documented": "000BH",
   "name": "A2 hysteresis",
   "description": "Decimal point ignored: Raw integer; apply the decimal point setting.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 12,
   "documented": "000CH",
   "name": "A3 hysteresis",
   "description": "Decimal point ignored: Raw integer; apply the decimal point setting.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 13,
   "documented": "000DH",
   "name": "A1 type",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "No alarm action",
    "1": "High limit alarm",
    "2": "Low limit alarm",
    "3": "High limit with standby",
    "4": "Low limit with standby"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 14,
   "documented": "000EH",
   "name": "A2 type",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "No alarm action",
    "1": "High limit alarm",
    "2": "Low limit alarm",
    "3": "High limit with standby",
    "4": "Low limit with standby"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 15,
   "documented": "000FH",
   "name": "A3 type",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "No alarm action",
    "1": "High limit alarm",
    "2": "Low limit alarm",
    "3": "High limit with standby",
    "4": "Low limit with standby",
    "5": "High/Low limit range alarm"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 16,
   "documented": "0010H",
   "name": "Transmission output 1 high limit",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 17,
   "documented": "0011H",
   "name": "Transmission output 1 low limit",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 18,
   "documented": "0012H",
   "name": "A1 energized/de-energized",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Energized",
    "1": "De-energized"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 19,
   "documented": "0013H",
   "name": "A2 energized/de-energized",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Energized",
    "1": "De-energized"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 20,
   "documented": "0014H",
   "name": "A3 energized/de-energized",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Energized",
    "1": "De-energized"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 21,
   "documented": "0015H",
   "name": "A1 delay time",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 22,
   "documented": "0016H",
   "name": "A2 delay time",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 23,
   "documented": "0017H",
   "name": "A3 delay time",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 25,
   "documented": "0019H",
   "name": "Input type",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "K -200 to 1370 C",
    "1": "K -200.0 to 400.0 C",
    "2": "J -200 to 1000 C",
    "3": "R 0 to 1760 C",
    "4": "S 0 to 1760 C",
    "5": "B 0 to 1820 C",
    "6": "E -200 to 800 C",
    "7": "T -200.0 to 400.0 C",
    "8": "N -200 to 1300 C",
    "9": "PL-II 0 to 1390 C",
    "10": "C (W/Re5-26) 0 to 2315 C",
    "11": "Pt100 -200.0 to 850.0 C",
    "12": "JPt100 -200.0 to 500.0 C",
    "13": "Pt100 -200 to 850 C",
    "14": "JPt100 -200 to 500 C",
    "15": "K -320 to 2500 F",
    "16": "K -200.0 to 750.0 F",
    "17": "J -320 to 1800 F",
    "18": "R 0 to 3200 F",
    "19": "S 0 to 3200 F",
    "20": "B 0 to 3300 F",
    "21": "E -320 to 1500 F",
    "22": "T -200.0 to 750.0 F",
    "23": "N -320 to 2300 F",
    "24": "PL-II 0 to 2500 F",
    "25": "C (W/Re5-26) 0 to 4200 F",
    "26": "Pt100 -200.0 to 1000.0 F",
    "27": "JPt100 -200.0 to 900.0 F",
    "28": "Pt100 -300 to 1500 F",
    "29": "JPt100 -300 to 900 F",
    "30": "4-20 mA DC (external shunt)",
    "31": "0-20 mA DC (external shunt)",
    "32": "0-1 V DC",
    "33": "0-5 V DC",
    "34": "1-5 V DC",
    "35": "0-10 V DC",
    "36": "4-20 mA DC (built-in shunt)",
    "37": "0-20 mA DC (built-in shunt)"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 112,
   "documented": "0070H",
   "name": "Key operation change flag clearing",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "W",
   "values": {
    "0": "No action",
    "1": "Clear the flag"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 128,
   "documented": "0080H",
   "name": "PV",
   "description": "Process value. Decimal point ignored: Raw integer; apply the decimal point setting.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 129,
   "documented": "0081H",
   "name": "Status flag",
   "description": "",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "0": "A1 output on",
    "1": "A2 output on",
    "2": "A3 output on",
    "3": "Overscale",
    "4": "Underscale",
    "15": "Settings changed by keypad"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 161,
   "documented": "00A1H",
   "name": "Unit specification flag",
   "description": "",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "0": "A1 available",
    "1": "A2 available",
    "2": "A3 available",
    "3": "Communication available",
    "4": "Transmission output 1 available"
   },
   "offset": 0
  }
 ],
 "page": "https://easymodbus.com/modbus-register-maps/shinko-technos/jir-301-m",
 "address_note": "address = 0-based Modbus wire (PDU) address; documented = as printed in the source.",
 "note": "Re-typed from the manufacturer's public documentation (see source) and verified against it. Registers vary by firmware and options; verify against the live device before writing."
}