 "manufacturer": "Shinko Technos",
 "manufacturer_slug": "shinko-technos",
 "model": "PCB1 programmable controller (C5W/C5 option)",
 "model_slug": "pcb1",
 "short_model": "PCB1",
 "aliases": [
  "PCB1"
 ],
 "equipment_type": "Sensor (programmable temperature controller)",
 "applies_to": "Shinko PCB1 programmable controllers with the C5W or C5 RS-485 option, native PCB1 command set; manual No. PCB1CE3.",
 "summary": "The PCB1 is a ramp/soak program controller with 10 patterns of 10 steps, 10 PID blocks and three event outputs. On RS-485 it speaks Shinko protocol or Modbus ASCII/RTU; every item is a signed 16-bit holding register. The map covers all pattern, event, wait and PID-block items, engineering settings, run/hold/advance commands and the read-only monitor block.",
 "transport": [
  "RTU",
  "ASCII"
 ],
 "defaults": {
  "unit_id": 0,
  "baud": 9600,
  "parity": "Even",
  "data_bits": 7,
  "stop_bits": 1,
  "tcp_port": null
 },
 "addressing": {
  "convention": "hex 0-based",
  "note": "Data items are hex (9000H) and are sent unchanged as the Modbus holding-register address. The manual says the Modicon number is the data item plus 40001. The RTU examples read PV at 9000H and write pattern 1 step 1 SV at 2100H (CRCs A90AH and 83E1H checked)."
 },
 "default_word_order": null,
 "firmware": null,
 "source": {
  "title": "Communication Instruction Manual PCB1 (C5W, C5)",
  "doc_number": "No. PCB1CE3",
  "revision_date": "2019-09",
  "url": "https://shinko-technos.co.jp/e/manual/english/PCB1CE3.pdf",
  "pages": "Command table pp. 24-37; data notes p. 44; communication settings pp. 4-5"
 },
 "notes": [
  "Addresses with a pattern or block number follow the manual's digit scheme: 2p00H (pattern p = 1-A), 3p00H, 5p00H, and 4k12H-4k16H for PID block k = 1-A. Step n of a pattern uses 2p00H + (n-1) x 3.",
  "The manual's PCD-33A compatible command set (section 7.2, 0001H-00A3H) is not repeated here; see the pcd-33a map for that layout.",
  "All data are 16-bit two's complement; values with a decimal point are sent as whole numbers.",
  "Units of PID times and limits are not printed in the command table.",
  "Changing an EV allocation clears that event's alarm value-0, hysteresis, delay and energized settings."
 ],
 "integration": {
  "summary": "Select MODBUS RTU mode in Engineering setting mode 1 and give the unit a non-zero instrument number; then poll PV 9000H, current step SV 9003H, pattern/step 9005H and status 900AH-900BH, and start/stop with 8001H.",
  "minimum_registers": [
   {
    "table": "holding_register",
    "address": 36864,
    "why": "Process value"
   },
   {
    "table": "holding_register",
    "address": 36867,
    "why": "Current step SV"
   },
   {
    "table": "holding_register",
    "address": 36869,
    "why": "Running pattern and step"
   },
   {
    "table": "holding_register",
    "address": 36875,
    "why": "Run/hold/wait status"
   },
   {
    "table": "holding_register",
    "address": 36874,
    "why": "Output, alarm and over/underscale flags"
   },
   {
    "table": "holding_register",
    "address": 32769,
    "why": "Program RUN/STOP"
   },
   {
    "table": "holding_register",
    "address": 32768,
    "why": "Pattern to run"
   },
   {
    "table": "holding_register",
    "address": 28675,
    "why": "Decimal point for scaling"
   }
  ],
  "enable": "Requires the C5W or C5 option. In Engineering setting mode 1 (down + MODE for about 3 s) set Communication protocol to MODBUS RTU (or ASCII), then instrument number, speed, data bit/parity and stop bit. These can only be set on the keypad.",
  "watchdog": null,
  "quirks": [
   "The manual's Modicon example writes 2100H as 42101, treating the hex digits as decimal; its example frames send 2100H itself as the PDU address (CRCs check), so use the hex data item directly.",
   "Instrument number 0 is the Modbus broadcast address; give each unit 1-95.",
   "The USB console cable and RS-485 cannot be used at the same time."
  ],
  "setup": [
   "Factory defaults: Shinko protocol, instrument number 0, 9600 bps, 7 bits/even parity, 1 stop bit, 10 ms response delay.",
   "For Modbus RTU choose an 8-bit data format (8 bits/no, even or odd parity).",
   "Do not fit a terminator; the unit has built-in pull-up/pull-down resistors."
  ],
  "gotchas": [
   "HOLD and ADVANCE return exception 17 (11H) while the program is stopped.",
   "Exception 18 (12H) is returned while the keypad is in setting mode.",
   "Non-volatile memory takes about one million writes; avoid cyclic writes of settings."
  ]
 },
 "registers": [
  {
   "table": "holding_register",
   "address": 8448,
   "documented": "2100H",
   "name": "P1 step 1 SV",
   "description": "Raw integer; apply decimal point place (7003H).",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8449,
   "documented": "2101H",
   "name": "P1 step 1 time",
   "description": "In the smaller unit of 7018H (minutes or seconds); FFFFH = hold.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8450,
   "documented": "2102H",
   "name": "P1 step 1 PID block",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "1": "Block 1",
    "2": "Block 2",
    "3": "Block 3",
    "4": "Block 4",
    "5": "Block 5",
    "6": "Block 6",
    "7": "Block 7",
    "8": "Block 8",
    "9": "Block 9",
    "10": "Block 10"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8451,
   "documented": "2103H",
   "name": "P1 step 2 SV",
   "description": "Raw integer; apply decimal point place (7003H).",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8452,
   "documented": "2104H",
   "name": "P1 step 2 time",
   "description": "In the smaller unit of 7018H (minutes or seconds); FFFFH = hold.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8453,
   "documented": "2105H",
   "name": "P1 step 2 PID block",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "1": "Block 1",
    "2": "Block 2",
    "3": "Block 3",
    "4": "Block 4",
    "5": "Block 5",
    "6": "Block 6",
    "7": "Block 7",
    "8": "Block 8",
    "9": "Block 9",
    "10": "Block 10"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8454,
   "documented": "2106H",
   "name": "P1 step 3 SV",
   "description": "Raw integer; apply decimal point place (7003H).",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8455,
   "documented": "2107H",
   "name": "P1 step 3 time",
   "description": "In the smaller unit of 7018H (minutes or seconds); FFFFH = hold.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8456,
   "documented": "2108H",
   "name": "P1 step 3 PID block",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "1": "Block 1",
    "2": "Block 2",
    "3": "Block 3",
    "4": "Block 4",
    "5": "Block 5",
    "6": "Block 6",
    "7": "Block 7",
    "8": "Block 8",
    "9": "Block 9",
    "10": "Block 10"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8457,
   "documented": "2109H",
   "name": "P1 step 4 SV",
   "description": "Raw integer; apply decimal point place (7003H).",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8458,
   "documented": "210AH",
   "name": "P1 step 4 time",
   "description": "In the smaller unit of 7018H (minutes or seconds); FFFFH = hold.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8459,
   "documented": "210BH",
   "name": "P1 step 4 PID block",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "1": "Block 1",
    "2": "Block 2",
    "3": "Block 3",
    "4": "Block 4",
    "5": "Block 5",
    "6": "Block 6",
    "7": "Block 7",
    "8": "Block 8",
    "9": "Block 9",
    "10": "Block 10"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8460,
   "documented": "210CH",
   "name": "P1 step 5 SV",
   "description": "Raw integer; apply decimal point place (7003H).",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8461,
   "documented": "210DH",
   "name": "P1 step 5 time",
   "description": "In the smaller unit of 7018H (minutes or seconds); FFFFH = hold.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8462,
   "documented": "210EH",
   "name": "P1 step 5 PID block",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "1": "Block 1",
    "2": "Block 2",
    "3": "Block 3",
    "4": "Block 4",
    "5": "Block 5",
    "6": "Block 6",
    "7": "Block 7",
    "8": "Block 8",
    "9": "Block 9",
    "10": "Block 10"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8463,
   "documented": "210FH",
   "name": "P1 step 6 SV",
   "description": "Raw integer; apply decimal point place (7003H).",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8464,
   "documented": "2110H",
   "name": "P1 step 6 time",
   "description": "In the smaller unit of 7018H (minutes or seconds); FFFFH = hold.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8465,
   "documented": "2111H",
   "name": "P1 step 6 PID block",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "1": "Block 1",
    "2": "Block 2",
    "3": "Block 3",
    "4": "Block 4",
    "5": "Block 5",
    "6": "Block 6",
    "7": "Block 7",
    "8": "Block 8",
    "9": "Block 9",
    "10": "Block 10"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8466,
   "documented": "2112H",
   "name": "P1 step 7 SV",
   "description": "Raw integer; apply decimal point place (7003H).",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8467,
   "documented": "2113H",
   "name": "P1 step 7 time",
   "description": "In the smaller unit of 7018H (minutes or seconds); FFFFH = hold.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8468,
   "documented": "2114H",
   "name": "P1 step 7 PID block",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "1": "Block 1",
    "2": "Block 2",
    "3": "Block 3",
    "4": "Block 4",
    "5": "Block 5",
    "6": "Block 6",
    "7": "Block 7",
    "8": "Block 8",
    "9": "Block 9",
    "10": "Block 10"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8469,
   "documented": "2115H",
   "name": "P1 step 8 SV",
   "description": "Raw integer; apply decimal point place (7003H).",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8470,
   "documented": "2116H",
   "name": "P1 step 8 time",
   "description": "In the smaller unit of 7018H (minutes or seconds); FFFFH = hold.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8471,
   "documented": "2117H",
   "name": "P1 step 8 PID block",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "1": "Block 1",
    "2": "Block 2",
    "3": "Block 3",
    "4": "Block 4",
    "5": "Block 5",
    "6": "Block 6",
    "7": "Block 7",
    "8": "Block 8",
    "9": "Block 9",
    "10": "Block 10"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8472,
   "documented": "2118H",
   "name": "P1 step 9 SV",
   "description": "Raw integer; apply decimal point place (7003H).",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8473,
   "documented": "2119H",
   "name": "P1 step 9 time",
   "description": "In the smaller unit of 7018H (minutes or seconds); FFFFH = hold.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8474,
   "documented": "211AH",
   "name": "P1 step 9 PID block",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "1": "Block 1",
    "2": "Block 2",
    "3": "Block 3",
    "4": "Block 4",
    "5": "Block 5",
    "6": "Block 6",
    "7": "Block 7",
    "8": "Block 8",
    "9": "Block 9",
    "10": "Block 10"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8475,
   "documented": "211BH",
   "name": "P1 step 10 SV",
   "description": "Raw integer; apply decimal point place (7003H).",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8476,
   "documented": "211CH",
   "name": "P1 step 10 time",
   "description": "In the smaller unit of 7018H (minutes or seconds); FFFFH = hold.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8477,
   "documented": "211DH",
   "name": "P1 step 10 PID block",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "1": "Block 1",
    "2": "Block 2",
    "3": "Block 3",
    "4": "Block 4",
    "5": "Block 5",
    "6": "Block 6",
    "7": "Block 7",
    "8": "Block 8",
    "9": "Block 9",
    "10": "Block 10"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8478,
   "documented": "211EH",
   "name": "P1 number of repetitions",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8479,
   "documented": "211FH",
   "name": "P1 pattern link",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Disabled",
    "1": "Enabled"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8704,
   "documented": "2200H",
   "name": "P2 step 1 SV",
   "description": "Raw integer; apply decimal point place (7003H).",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8705,
   "documented": "2201H",
   "name": "P2 step 1 time",
   "description": "In the smaller unit of 7018H (minutes or seconds); FFFFH = hold.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8706,
   "documented": "2202H",
   "name": "P2 step 1 PID block",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "1": "Block 1",
    "2": "Block 2",
    "3": "Block 3",
    "4": "Block 4",
    "5": "Block 5",
    "6": "Block 6",
    "7": "Block 7",
    "8": "Block 8",
    "9": "Block 9",
    "10": "Block 10"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8707,
   "documented": "2203H",
   "name": "P2 step 2 SV",
   "description": "Raw integer; apply decimal point place (7003H).",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8708,
   "documented": "2204H",
   "name": "P2 step 2 time",
   "description": "In the smaller unit of 7018H (minutes or seconds); FFFFH = hold.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8709,
   "documented": "2205H",
   "name": "P2 step 2 PID block",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "1": "Block 1",
    "2": "Block 2",
    "3": "Block 3",
    "4": "Block 4",
    "5": "Block 5",
    "6": "Block 6",
    "7": "Block 7",
    "8": "Block 8",
    "9": "Block 9",
    "10": "Block 10"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8710,
   "documented": "2206H",
   "name": "P2 step 3 SV",
   "description": "Raw integer; apply decimal point place (7003H).",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8711,
   "documented": "2207H",
   "name": "P2 step 3 time",
   "description": "In the smaller unit of 7018H (minutes or seconds); FFFFH = hold.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8712,
   "documented": "2208H",
   "name": "P2 step 3 PID block",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "1": "Block 1",
    "2": "Block 2",
    "3": "Block 3",
    "4": "Block 4",
    "5": "Block 5",
    "6": "Block 6",
    "7": "Block 7",
    "8": "Block 8",
    "9": "Block 9",
    "10": "Block 10"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8713,
   "documented": "2209H",
   "name": "P2 step 4 SV",
   "description": "Raw integer; apply decimal point place (7003H).",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8714,
   "documented": "220AH",
   "name": "P2 step 4 time",
   "description": "In the smaller unit of 7018H (minutes or seconds); FFFFH = hold.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8715,
   "documented": "220BH",
   "name": "P2 step 4 PID block",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "1": "Block 1",
    "2": "Block 2",
    "3": "Block 3",
    "4": "Block 4",
    "5": "Block 5",
    "6": "Block 6",
    "7": "Block 7",
    "8": "Block 8",
    "9": "Block 9",
    "10": "Block 10"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8716,
   "documented": "220CH",
   "name": "P2 step 5 SV",
   "description": "Raw integer; apply decimal point place (7003H).",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8717,
   "documented": "220DH",
   "name": "P2 step 5 time",
   "description": "In the smaller unit of 7018H (minutes or seconds); FFFFH = hold.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8718,
   "documented": "220EH",
   "name": "P2 step 5 PID block",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "1": "Block 1",
    "2": "Block 2",
    "3": "Block 3",
    "4": "Block 4",
    "5": "Block 5",
    "6": "Block 6",
    "7": "Block 7",
    "8": "Block 8",
    "9": "Block 9",
    "10": "Block 10"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8719,
   "documented": "220FH",
   "name": "P2 step 6 SV",
   "description": "Raw integer; apply decimal point place (7003H).",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8720,
   "documented": "2210H",
   "name": "P2 step 6 time",
   "description": "In the smaller unit of 7018H (minutes or seconds); FFFFH = hold.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8721,
   "documented": "2211H",
   "name": "P2 step 6 PID block",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "1": "Block 1",
    "2": "Block 2",
    "3": "Block 3",
    "4": "Block 4",
    "5": "Block 5",
    "6": "Block 6",
    "7": "Block 7",
    "8": "Block 8",
    "9": "Block 9",
    "10": "Block 10"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8722,
   "documented": "2212H",
   "name": "P2 step 7 SV",
   "description": "Raw integer; apply decimal point place (7003H).",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8723,
   "documented": "2213H",
   "name": "P2 step 7 time",
   "description": "In the smaller unit of 7018H (minutes or seconds); FFFFH = hold.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8724,
   "documented": "2214H",
   "name": "P2 step 7 PID block",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "1": "Block 1",
    "2": "Block 2",
    "3": "Block 3",
    "4": "Block 4",
    "5": "Block 5",
    "6": "Block 6",
    "7": "Block 7",
    "8": "Block 8",
    "9": "Block 9",
    "10": "Block 10"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8725,
   "documented": "2215H",
   "name": "P2 step 8 SV",
   "description": "Raw integer; apply decimal point place (7003H).",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8726,
   "documented": "2216H",
   "name": "P2 step 8 time",
   "description": "In the smaller unit of 7018H (minutes or seconds); FFFFH = hold.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8727,
   "documented": "2217H",
   "name": "P2 step 8 PID block",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "1": "Block 1",
    "2": "Block 2",
    "3": "Block 3",
    "4": "Block 4",
    "5": "Block 5",
    "6": "Block 6",
    "7": "Block 7",
    "8": "Block 8",
    "9": "Block 9",
    "10": "Block 10"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8728,
   "documented": "2218H",
   "name": "P2 step 9 SV",
   "description": "Raw integer; apply decimal point place (7003H).",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8729,
   "documented": "2219H",
   "name": "P2 step 9 time",
   "description": "In the smaller unit of 7018H (minutes or seconds); FFFFH = hold.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8730,
   "documented": "221AH",
   "name": "P2 step 9 PID block",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "1": "Block 1",
    "2": "Block 2",
    "3": "Block 3",
    "4": "Block 4",
    "5": "Block 5",
    "6": "Block 6",
    "7": "Block 7",
    "8": "Block 8",
    "9": "Block 9",
    "10": "Block 10"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8731,
   "documented": "221BH",
   "name": "P2 step 10 SV",
   "description": "Raw integer; apply decimal point place (7003H).",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8732,
   "documented": "221CH",
   "name": "P2 step 10 time",
   "description": "In the smaller unit of 7018H (minutes or seconds); FFFFH = hold.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8733,
   "documented": "221DH",
   "name": "P2 step 10 PID block",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "1": "Block 1",
    "2": "Block 2",
    "3": "Block 3",
    "4": "Block 4",
    "5": "Block 5",
    "6": "Block 6",
    "7": "Block 7",
    "8": "Block 8",
    "9": "Block 9",
    "10": "Block 10"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8734,
   "documented": "221EH",
   "name": "P2 number of repetitions",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8735,
   "documented": "221FH",
   "name": "P2 pattern link",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Disabled",
    "1": "Enabled"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8960,
   "documented": "2300H",
   "name": "P3 step 1 SV",
   "description": "Raw integer; apply decimal point place (7003H).",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8961,
   "documented": "2301H",
   "name": "P3 step 1 time",
   "description": "In the smaller unit of 7018H (minutes or seconds); FFFFH = hold.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8962,
   "documented": "2302H",
   "name": "P3 step 1 PID block",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "1": "Block 1",
    "2": "Block 2",
    "3": "Block 3",
    "4": "Block 4",
    "5": "Block 5",
    "6": "Block 6",
    "7": "Block 7",
    "8": "Block 8",
    "9": "Block 9",
    "10": "Block 10"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8963,
   "documented": "2303H",
   "name": "P3 step 2 SV",
   "description": "Raw integer; apply decimal point place (7003H).",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8964,
   "documented": "2304H",
   "name": "P3 step 2 time",
   "description": "In the smaller unit of 7018H (minutes or seconds); FFFFH = hold.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8965,
   "documented": "2305H",
   "name": "P3 step 2 PID block",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "1": "Block 1",
    "2": "Block 2",
    "3": "Block 3",
    "4": "Block 4",
    "5": "Block 5",
    "6": "Block 6",
    "7": "Block 7",
    "8": "Block 8",
    "9": "Block 9",
    "10": "Block 10"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8966,
   "documented": "2306H",
   "name": "P3 step 3 SV",
   "description": "Raw integer; apply decimal point place (7003H).",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8967,
   "documented": "2307H",
   "name": "P3 step 3 time",
   "description": "In the smaller unit of 7018H (minutes or seconds); FFFFH = hold.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8968,
   "documented": "2308H",
   "name": "P3 step 3 PID block",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "1": "Block 1",
    "2": "Block 2",
    "3": "Block 3",
    "4": "Block 4",
    "5": "Block 5",
    "6": "Block 6",
    "7": "Block 7",
    "8": "Block 8",
    "9": "Block 9",
    "10": "Block 10"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8969,
   "documented": "2309H",
   "name": "P3 step 4 SV",
   "description": "Raw integer; apply decimal point place (7003H).",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8970,
   "documented": "230AH",
   "name": "P3 step 4 time",
   "description": "In the smaller unit of 7018H (minutes or seconds); FFFFH = hold.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8971,
   "documented": "230BH",
   "name": "P3 step 4 PID block",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "1": "Block 1",
    "2": "Block 2",
    "3": "Block 3",
    "4": "Block 4",
    "5": "Block 5",
    "6": "Block 6",
    "7": "Block 7",
    "8": "Block 8",
    "9": "Block 9",
    "10": "Block 10"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8972,
   "documented": "230CH",
   "name": "P3 step 5 SV",
   "description": "Raw integer; apply decimal point place (7003H).",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8973,
   "documented": "230DH",
   "name": "P3 step 5 time",
   "description": "In the smaller unit of 7018H (minutes or seconds); FFFFH = hold.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8974,
   "documented": "230EH",
   "name": "P3 step 5 PID block",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "1": "Block 1",
    "2": "Block 2",
    "3": "Block 3",
    "4": "Block 4",
    "5": "Block 5",
    "6": "Block 6",
    "7": "Block 7",
    "8": "Block 8",
    "9": "Block 9",
    "10": "Block 10"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8975,
   "documented": "230FH",
   "name": "P3 step 6 SV",
   "description": "Raw integer; apply decimal point place (7003H).",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8976,
   "documented": "2310H",
   "name": "P3 step 6 time",
   "description": "In the smaller unit of 7018H (minutes or seconds); FFFFH = hold.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8977,
   "documented": "2311H",
   "name": "P3 step 6 PID block",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "1": "Block 1",
    "2": "Block 2",
    "3": "Block 3",
    "4": "Block 4",
    "5": "Block 5",
    "6": "Block 6",
    "7": "Block 7",
    "8": "Block 8",
    "9": "Block 9",
    "10": "Block 10"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8978,
   "documented": "2312H",
   "name": "P3 step 7 SV",
   "description": "Raw integer; apply decimal point place (7003H).",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8979,
   "documented": "2313H",
   "name": "P3 step 7 time",
   "description": "In the smaller unit of 7018H (minutes or seconds); FFFFH = hold.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8980,
   "documented": "2314H",
   "name": "P3 step 7 PID block",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "1": "Block 1",
    "2": "Block 2",
    "3": "Block 3",
    "4": "Block 4",
    "5": "Block 5",
    "6": "Block 6",
    "7": "Block 7",
    "8": "Block 8",
    "9": "Block 9",
    "10": "Block 10"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8981,
   "documented": "2315H",
   "name": "P3 step 8 SV",
   "description": "Raw integer; apply decimal point place (7003H).",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8982,
   "documented": "2316H",
   "name": "P3 step 8 time",
   "description": "In the smaller unit of 7018H (minutes or seconds); FFFFH = hold.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8983,
   "documented": "2317H",
   "name": "P3 step 8 PID block",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "1": "Block 1",
    "2": "Block 2",
    "3": "Block 3",
    "4": "Block 4",
    "5": "Block 5",
    "6": "Block 6",
    "7": "Block 7",
    "8": "Block 8",
    "9": "Block 9",
    "10": "Block 10"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8984,
   "documented": "2318H",
   "name": "P3 step 9 SV",
   "description": "Raw integer; apply decimal point place (7003H).",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8985,
   "documented": "2319H",
   "name": "P3 step 9 time",
   "description": "In the smaller unit of 7018H (minutes or seconds); FFFFH = hold.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8986,
   "documented": "231AH",
   "name": "P3 step 9 PID block",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "1": "Block 1",
    "2": "Block 2",
    "3": "Block 3",
    "4": "Block 4",
    "5": "Block 5",
    "6": "Block 6",
    "7": "Block 7",
    "8": "Block 8",
    "9": "Block 9",
    "10": "Block 10"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8987,
   "documented": "231BH",
   "name": "P3 step 10 SV",
   "description": "Raw integer; apply decimal point place (7003H).",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8988,
   "documented": "231CH",
   "name": "P3 step 10 time",
   "description": "In the smaller unit of 7018H (minutes or seconds); FFFFH = hold.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8989,
   "documented": "231DH",
   "name": "P3 step 10 PID block",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "1": "Block 1",
    "2": "Block 2",
    "3": "Block 3",
    "4": "Block 4",
    "5": "Block 5",
    "6": "Block 6",
    "7": "Block 7",
    "8": "Block 8",
    "9": "Block 9",
    "10": "Block 10"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8990,
   "documented": "231EH",
   "name": "P3 number of repetitions",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8991,
   "documented": "231FH",
   "name": "P3 pattern link",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Disabled",
    "1": "Enabled"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 9216,
   "documented": "2400H",
   "name": "P4 step 1 SV",
   "description": "Raw integer; apply decimal point place (7003H).",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 9217,
   "documented": "2401H",
   "name": "P4 step 1 time",
   "description": "In the smaller unit of 7018H (minutes or seconds); FFFFH = hold.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 9218,
   "documented": "2402H",
   "name": "P4 step 1 PID block",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "1": "Block 1",
    "2": "Block 2",
    "3": "Block 3",
    "4": "Block 4",
    "5": "Block 5",
    "6": "Block 6",
    "7": "Block 7",
    "8": "Block 8",
    "9": "Block 9",
    "10": "Block 10"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 9219,
   "documented": "2403H",
   "name": "P4 step 2 SV",
   "description": "Raw integer; apply decimal point place (7003H).",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 9220,
   "documented": "2404H",
   "name": "P4 step 2 time",
   "description": "In the smaller unit of 7018H (minutes or seconds); FFFFH = hold.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 9221,
   "documented": "2405H",
   "name": "P4 step 2 PID block",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "1": "Block 1",
    "2": "Block 2",
    "3": "Block 3",
    "4": "Block 4",
    "5": "Block 5",
    "6": "Block 6",
    "7": "Block 7",
    "8": "Block 8",
    "9": "Block 9",
    "10": "Block 10"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 9222,
   "documented": "2406H",
   "name": "P4 step 3 SV",
   "description": "Raw integer; apply decimal point place (7003H).",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 9223,
   "documented": "2407H",
   "name": "P4 step 3 time",
   "description": "In the smaller unit of 7018H (minutes or seconds); FFFFH = hold.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 9224,
   "documented": "2408H",
   "name": "P4 step 3 PID block",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "1": "Block 1",
    "2": "Block 2",
    "3": "Block 3",
    "4": "Block 4",
    "5": "Block 5",
    "6": "Block 6",
    "7": "Block 7",
    "8": "Block 8",
    "9": "Block 9",
    "10": "Block 10"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 9225,
   "documented": "2409H",
   "name": "P4 step 4 SV",
   "description": "Raw integer; apply decimal point place (7003H).",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 9226,
   "documented": "240AH",
   "name": "P4 step 4 time",
   "description": "In the smaller unit of 7018H (minutes or seconds); FFFFH = hold.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 9227,
   "documented": "240BH",
   "name": "P4 step 4 PID block",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "1": "Block 1",
    "2": "Block 2",
    "3": "Block 3",
    "4": "Block 4",
    "5": "Block 5",
    "6": "Block 6",
    "7": "Block 7",
    "8": "Block 8",
    "9": "Block 9",
    "10": "Block 10"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 9228,
   "documented": "240CH",
   "name": "P4 step 5 SV",
   "description": "Raw integer; apply decimal point place (7003H).",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 9229,
   "documented": "240DH",
   "name": "P4 step 5 time",
   "description": "In the smaller unit of 7018H (minutes or seconds); FFFFH = hold.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 9230,
   "documented": "240EH",
   "name": "P4 step 5 PID block",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "1": "Block 1",
    "2": "Block 2",
    "3": "Block 3",
    "4": "Block 4",
    "5": "Block 5",
    "6": "Block 6",
    "7": "Block 7",
    "8": "Block 8",
    "9": "Block 9",
    "10": "Block 10"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 9231,
   "documented": "240FH",
   "name": "P4 step 6 SV",
   "description": "Raw integer; apply decimal point place (7003H).",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 9232,
   "documented": "2410H",
   "name": "P4 step 6 time",
   "description": "In the smaller unit of 7018H (minutes or seconds); FFFFH = hold.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 9233,
   "documented": "2411H",
   "name": "P4 step 6 PID block",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "1": "Block 1",
    "2": "Block 2",
    "3": "Block 3",
    "4": "Block 4",
    "5": "Block 5",
    "6": "Block 6",
    "7": "Block 7",
    "8": "Block 8",
    "9": "Block 9",
    "10": "Block 10"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 9234,
   "documented": "2412H",
   "name": "P4 step 7 SV",
   "description": "Raw integer; apply decimal point place (7003H).",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 9235,
   "documented": "2413H",
   "name": "P4 step 7 time",
   "description": "In the smaller unit of 7018H (minutes or seconds); FFFFH = hold.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 9236,
   "documented": "2414H",
   "name": "P4 step 7 PID block",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "1": "Block 1",
    "2": "Block 2",
    "3": "Block 3",
    "4": "Block 4",
    "5": "Block 5",
    "6": "Block 6",
    "7": "Block 7",
    "8": "Block 8",
    "9": "Block 9",
    "10": "Block 10"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 9237,
   "documented": "2415H",
   "name": "P4 step 8 SV",
   "description": "Raw integer; apply decimal point place (7003H).",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 9238,
   "documented": "2416H",
   "name": "P4 step 8 time",
   "description": "In the smaller unit of 7018H (minutes or seconds); FFFFH = hold.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 9239,
   "documented": "2417H",
   "name": "P4 step 8 PID block",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "1": "Block 1",
    "2": "Block 2",
    "3": "Block 3",
    "4": "Block 4",
    "5": "Block 5",
    "6": "Block 6",
    "7": "Block 7",
    "8": "Block 8",
    "9": "Block 9",
    "10": "Block 10"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 9240,
   "documented": "2418H",
   "name": "P4 step 9 SV",
   "description": "Raw integer; apply decimal point place (7003H).",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 9241,
   "documented": "2419H",
   "name": "P4 step 9 time",
   "description": "In the smaller unit of 7018H (minutes or seconds); FFFFH = hold.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 9242,
   "documented": "241AH",
   "name": "P4 step 9 PID block",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "1": "Block 1",
    "2": "Block 2",
    "3": "Block 3",
    "4": "Block 4",
    "5": "Block 5",
    "6": "Block 6",
    "7": "Block 7",
    "8": "Block 8",
    "9": "Block 9",
    "10": "Block 10"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 9243,
   "documented": "241BH",
   "name": "P4 step 10 SV",
   "description": "Raw integer; apply decimal point place (7003H).",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 9244,
   "documented": "241CH",
   "name": "P4 step 10 time",
   "description": "In the smaller unit of 7018H (minutes or seconds); FFFFH = hold.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 9245,
   "documented": "241DH",
   "name": "P4 step 10 PID block",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "1": "Block 1",
    "2": "Block 2",
    "3": "Block 3",
    "4": "Block 4",
    "5": "Block 5",
    "6": "Block 6",
    "7": "Block 7",
    "8": "Block 8",
    "9": "Block 9",
    "10": "Block 10"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 9246,
   "documented": "241EH",
   "name": "P4 number of repetitions",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 9247,
   "documented": "241FH",
   "name": "P4 pattern link",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Disabled",
    "1": "Enabled"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 9472,
   "documented": "2500H",
   "name": "P5 step 1 SV",
   "description": "Raw integer; apply decimal point place (7003H).",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 9473,
   "documented": "2501H",
   "name": "P5 step 1 time",
   "description": "In the smaller unit of 7018H (minutes or seconds); FFFFH = hold.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 9474,
   "documented": "2502H",
   "name": "P5 step 1 PID block",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "1": "Block 1",
    "2": "Block 2",
    "3": "Block 3",
    "4": "Block 4",
    "5": "Block 5",
    "6": "Block 6",
    "7": "Block 7",
    "8": "Block 8",
    "9": "Block 9",
    "10": "Block 10"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 9475,
   "documented": "2503H",
   "name": "P5 step 2 SV",
   "description": "Raw integer; apply decimal point place (7003H).",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 9476,
   "documented": "2504H",
   "name": "P5 step 2 time",
   "description": "In the smaller unit of 7018H (minutes or seconds); FFFFH = hold.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 9477,
   "documented": "2505H",
   "name": "P5 step 2 PID block",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "1": "Block 1",
    "2": "Block 2",
    "3": "Block 3",
    "4": "Block 4",
    "5": "Block 5",
    "6": "Block 6",
    "7": "Block 7",
    "8": "Block 8",
    "9": "Block 9",
    "10": "Block 10"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 9478,
   "documented": "2506H",
   "name": "P5 step 3 SV",
   "description": "Raw integer; apply decimal point place (7003H).",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 9479,
   "documented": "2507H",
   "name": "P5 step 3 time",
   "description": "In the smaller unit of 7018H (minutes or seconds); FFFFH = hold.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 9480,
   "documented": "2508H",
   "name": "P5 step 3 PID block",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "1": "Block 1",
    "2": "Block 2",
    "3": "Block 3",
    "4": "Block 4",
    "5": "Block 5",
    "6": "Block 6",
    "7": "Block 7",
    "8": "Block 8",
    "9": "Block 9",
    "10": "Block 10"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 9481,
   "documented": "2509H",
   "name": "P5 step 4 SV",
   "description": "Raw integer; apply decimal point place (7003H).",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 9482,
   "documented": "250AH",
   "name": "P5 step 4 time",
   "description": "In the smaller unit of 7018H (minutes or seconds); FFFFH = hold.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 9483,
   "documented": "250BH",
   "name": "P5 step 4 PID block",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "1": "Block 1",
    "2": "Block 2",
    "3": "Block 3",
    "4": "Block 4",
    "5": "Block 5",
    "6": "Block 6",
    "7": "Block 7",
    "8": "Block 8",
    "9": "Block 9",
    "10": "Block 10"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 9484,
   "documented": "250CH",
   "name": "P5 step 5 SV",
   "description": "Raw integer; apply decimal point place (7003H).",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 9485,
   "documented": "250DH",
   "name": "P5 step 5 time",
   "description": "In the smaller unit of 7018H (minutes or seconds); FFFFH = hold.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 9486,
   "documented": "250EH",
   "name": "P5 step 5 PID block",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "1": "Block 1",
    "2": "Block 2",
    "3": "Block 3",
    "4": "Block 4",
    "5": "Block 5",
    "6": "Block 6",
    "7": "Block 7",
    "8": "Block 8",
    "9": "Block 9",
    "10": "Block 10"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 9487,
   "documented": "250FH",
   "name": "P5 step 6 SV",
   "description": "Raw integer; apply decimal point place (7003H).",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 9488,
   "documented": "2510H",
   "name": "P5 step 6 time",
   "description": "In the smaller unit of 7018H (minutes or seconds); FFFFH = hold.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 9489,
   "documented": "2511H",
   "name": "P5 step 6 PID block",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "1": "Block 1",
    "2": "Block 2",
    "3": "Block 3",
    "4": "Block 4",
    "5": "Block 5",
    "6": "Block 6",
    "7": "Block 7",
    "8": "Block 8",
    "9": "Block 9",
    "10": "Block 10"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 9490,
   "documented": "2512H",
   "name": "P5 step 7 SV",
   "description": "Raw integer; apply decimal point place (7003H).",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 9491,
   "documented": "2513H",
   "name": "P5 step 7 time",
   "description": "In the smaller unit of 7018H (minutes or seconds); FFFFH = hold.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 9492,
   "documented": "2514H",
   "name": "P5 step 7 PID block",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "1": "Block 1",
    "2": "Block 2",
    "3": "Block 3",
    "4": "Block 4",
    "5": "Block 5",
    "6": "Block 6",
    "7": "Block 7",
    "8": "Block 8",
    "9": "Block 9",
    "10": "Block 10"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 9493,
   "documented": "2515H",
   "name": "P5 step 8 SV",
   "description": "Raw integer; apply decimal point place (7003H).",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 9494,
   "documented": "2516H",
   "name": "P5 step 8 time",
   "description": "In the smaller unit of 7018H (minutes or seconds); FFFFH = hold.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 9495,
   "documented": "2517H",
   "name": "P5 step 8 PID block",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "1": "Block 1",
    "2": "Block 2",
    "3": "Block 3",
    "4": "Block 4",
    "5": "Block 5",
    "6": "Block 6",
    "7": "Block 7",
    "8": "Block 8",
    "9": "Block 9",
    "10": "Block 10"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 9496,
   "documented": "2518H",
   "name": "P5 step 9 SV",
   "description": "Raw integer; apply decimal point place (7003H).",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 9497,
   "documented": "2519H",
   "name": "P5 step 9 time",
   "description": "In the smaller unit of 7018H (minutes or seconds); FFFFH = hold.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 9498,
   "documented": "251AH",
   "name": "P5 step 9 PID block",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "1": "Block 1",
    "2": "Block 2",
    "3": "Block 3",
    "4": "Block 4",
    "5": "Block 5",
    "6": "Block 6",
    "7": "Block 7",
    "8": "Block 8",
    "9": "Block 9",
    "10": "Block 10"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 9499,
   "documented": "251BH",
   "name": "P5 step 10 SV",
   "description": "Raw integer; apply decimal point place (7003H).",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 9500,
   "documented": "251CH",
   "name": "P5 step 10 time",
   "description": "In the smaller unit of 7018H (minutes or seconds); FFFFH = hold.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 9501,
   "documented": "251DH",
   "name": "P5 step 10 PID block",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "1": "Block 1",
    "2": "Block 2",
    "3": "Block 3",
    "4": "Block 4",
    "5": "Block 5",
    "6": "Block 6",
    "7": "Block 7",
    "8": "Block 8",
    "9": "Block 9",
    "10": "Block 10"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 9502,
   "documented": "251EH",
   "name": "P5 number of repetitions",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 9503,
   "documented": "251FH",
   "name": "P5 pattern link",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Disabled",
    "1": "Enabled"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 9728,
   "documented": "2600H",
   "name": "P6 step 1 SV",
   "description": "Raw integer; apply decimal point place (7003H).",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 9729,
   "documented": "2601H",
   "name": "P6 step 1 time",
   "description": "In the smaller unit of 7018H (minutes or seconds); FFFFH = hold.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 9730,
   "documented": "2602H",
   "name": "P6 step 1 PID block",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "1": "Block 1",
    "2": "Block 2",
    "3": "Block 3",
    "4": "Block 4",
    "5": "Block 5",
    "6": "Block 6",
    "7": "Block 7",
    "8": "Block 8",
    "9": "Block 9",
    "10": "Block 10"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 9731,
   "documented": "2603H",
   "name": "P6 step 2 SV",
   "description": "Raw integer; apply decimal point place (7003H).",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 9732,
   "documented": "2604H",
   "name": "P6 step 2 time",
   "description": "In the smaller unit of 7018H (minutes or seconds); FFFFH = hold.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 9733,
   "documented": "2605H",
   "name": "P6 step 2 PID block",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "1": "Block 1",
    "2": "Block 2",
    "3": "Block 3",
    "4": "Block 4",
    "5": "Block 5",
    "6": "Block 6",
    "7": "Block 7",
    "8": "Block 8",
    "9": "Block 9",
    "10": "Block 10"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 9734,
   "documented": "2606H",
   "name": "P6 step 3 SV",
   "description": "Raw integer; apply decimal point place (7003H).",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 9735,
   "documented": "2607H",
   "name": "P6 step 3 time",
   "description": "In the smaller unit of 7018H (minutes or seconds); FFFFH = hold.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 9736,
   "documented": "2608H",
   "name": "P6 step 3 PID block",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "1": "Block 1",
    "2": "Block 2",
    "3": "Block 3",
    "4": "Block 4",
    "5": "Block 5",
    "6": "Block 6",
    "7": "Block 7",
    "8": "Block 8",
    "9": "Block 9",
    "10": "Block 10"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 9737,
   "documented": "2609H",
   "name": "P6 step 4 SV",
   "description": "Raw integer; apply decimal point place (7003H).",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 9738,
   "documented": "260AH",
   "name": "P6 step 4 time",
   "description": "In the smaller unit of 7018H (minutes or seconds); FFFFH = hold.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 9739,
   "documented": "260BH",
   "name": "P6 step 4 PID block",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "1": "Block 1",
    "2": "Block 2",
    "3": "Block 3",
    "4": "Block 4",
    "5": "Block 5",
    "6": "Block 6",
    "7": "Block 7",
    "8": "Block 8",
    "9": "Block 9",
    "10": "Block 10"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 9740,
   "documented": "260CH",
   "name": "P6 step 5 SV",
   "description": "Raw integer; apply decimal point place (7003H).",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 9741,
   "documented": "260DH",
   "name": "P6 step 5 time",
   "description": "In the smaller unit of 7018H (minutes or seconds); FFFFH = hold.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 9742,
   "documented": "260EH",
   "name": "P6 step 5 PID block",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "1": "Block 1",
    "2": "Block 2",
    "3": "Block 3",
    "4": "Block 4",
    "5": "Block 5",
    "6": "Block 6",
    "7": "Block 7",
    "8": "Block 8",
    "9": "Block 9",
    "10": "Block 10"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 9743,
   "documented": "260FH",
   "name": "P6 step 6 SV",
   "description": "Raw integer; apply decimal point place (7003H).",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 9744,
   "documented": "2610H",
   "name": "P6 step 6 time",
   "description": "In the smaller unit of 7018H (minutes or seconds); FFFFH = hold.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 9745,
   "documented": "2611H",
   "name": "P6 step 6 PID block",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "1": "Block 1",
    "2": "Block 2",
    "3": "Block 3",
    "4": "Block 4",
    "5": "Block 5",
    "6": "Block 6",
    "7": "Block 7",
    "8": "Block 8",
    "9": "Block 9",
    "10": "Block 10"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 9746,
   "documented": "2612H",
   "name": "P6 step 7 SV",
   "description": "Raw integer; apply decimal point place (7003H).",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 9747,
   "documented": "2613H",
   "name": "P6 step 7 time",
   "description": "In the smaller unit of 7018H (minutes or seconds); FFFFH = hold.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 9748,
   "documented": "2614H",
   "name": "P6 step 7 PID block",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "1": "Block 1",
    "2": "Block 2",
    "3": "Block 3",
    "4": "Block 4",
    "5": "Block 5",
    "6": "Block 6",
    "7": "Block 7",
    "8": "Block 8",
    "9": "Block 9",
    "10": "Block 10"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 9749,
   "documented": "2615H",
   "name": "P6 step 8 SV",
   "description": "Raw integer; apply decimal point place (7003H).",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 9750,
   "documented": "2616H",
   "name": "P6 step 8 time",
   "description": "In the smaller unit of 7018H (minutes or seconds); FFFFH = hold.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 9751,
   "documented": "2617H",
   "name": "P6 step 8 PID block",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "1": "Block 1",
    "2": "Block 2",
    "3": "Block 3",
    "4": "Block 4",
    "5": "Block 5",
    "6": "Block 6",
    "7": "Block 7",
    "8": "Block 8",
    "9": "Block 9",
    "10": "Block 10"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 9752,
   "documented": "2618H",
   "name": "P6 step 9 SV",
   "description": "Raw integer; apply decimal point place (7003H).",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 9753,
   "documented": "2619H",
   "name": "P6 step 9 time",
   "description": "In the smaller unit of 7018H (minutes or seconds); FFFFH = hold.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 9754,
   "documented": "261AH",
   "name": "P6 step 9 PID block",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "1": "Block 1",
    "2": "Block 2",
    "3": "Block 3",
    "4": "Block 4",
    "5": "Block 5",
    "6": "Block 6",
    "7": "Block 7",
    "8": "Block 8",
    "9": "Block 9",
    "10": "Block 10"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 9755,
   "documented": "261BH",
   "name": "P6 step 10 SV",
   "description": "Raw integer; apply decimal point place (7003H).",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 9756,
   "documented": "261CH",
   "name": "P6 step 10 time",
   "description": "In the smaller unit of 7018H (minutes or seconds); FFFFH = hold.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 9757,
   "documented": "261DH",
   "name": "P6 step 10 PID block",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "1": "Block 1",
    "2": "Block 2",
    "3": "Block 3",
    "4": "Block 4",
    "5": "Block 5",
    "6": "Block 6",
    "7": "Block 7",
    "8": "Block 8",
    "9": "Block 9",
    "10": "Block 10"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 9758,
   "documented": "261EH",
   "name": "P6 number of repetitions",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 9759,
   "documented": "261FH",
   "name": "P6 pattern link",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Disabled",
    "1": "Enabled"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 9984,
   "documented": "2700H",
   "name": "P7 step 1 SV",
   "description": "Raw integer; apply decimal point place (7003H).",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 9985,
   "documented": "2701H",
   "name": "P7 step 1 time",
   "description": "In the smaller unit of 7018H (minutes or seconds); FFFFH = hold.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 9986,
   "documented": "2702H",
   "name": "P7 step 1 PID block",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "1": "Block 1",
    "2": "Block 2",
    "3": "Block 3",
    "4": "Block 4",
    "5": "Block 5",
    "6": "Block 6",
    "7": "Block 7",
    "8": "Block 8",
    "9": "Block 9",
    "10": "Block 10"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 9987,
   "documented": "2703H",
   "name": "P7 step 2 SV",
   "description": "Raw integer; apply decimal point place (7003H).",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 9988,
   "documented": "2704H",
   "name": "P7 step 2 time",
   "description": "In the smaller unit of 7018H (minutes or seconds); FFFFH = hold.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 9989,
   "documented": "2705H",
   "name": "P7 step 2 PID block",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "1": "Block 1",
    "2": "Block 2",
    "3": "Block 3",
    "4": "Block 4",
    "5": "Block 5",
    "6": "Block 6",
    "7": "Block 7",
    "8": "Block 8",
    "9": "Block 9",
    "10": "Block 10"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 9990,
   "documented": "2706H",
   "name": "P7 step 3 SV",
   "description": "Raw integer; apply decimal point place (7003H).",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 9991,
   "documented": "2707H",
   "name": "P7 step 3 time",
   "description": "In the smaller unit of 7018H (minutes or seconds); FFFFH = hold.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 9992,
   "documented": "2708H",
   "name": "P7 step 3 PID block",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "1": "Block 1",
    "2": "Block 2",
    "3": "Block 3",
    "4": "Block 4",
    "5": "Block 5",
    "6": "Block 6",
    "7": "Block 7",
    "8": "Block 8",
    "9": "Block 9",
    "10": "Block 10"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 9993,
   "documented": "2709H",
   "name": "P7 step 4 SV",
   "description": "Raw integer; apply decimal point place (7003H).",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 9994,
   "documented": "270AH",
   "name": "P7 step 4 time",
   "description": "In the smaller unit of 7018H (minutes or seconds); FFFFH = hold.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 9995,
   "documented": "270BH",
   "name": "P7 step 4 PID block",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "1": "Block 1",
    "2": "Block 2",
    "3": "Block 3",
    "4": "Block 4",
    "5": "Block 5",
    "6": "Block 6",
    "7": "Block 7",
    "8": "Block 8",
    "9": "Block 9",
    "10": "Block 10"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 9996,
   "documented": "270CH",
   "name": "P7 step 5 SV",
   "description": "Raw integer; apply decimal point place (7003H).",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 9997,
   "documented": "270DH",
   "name": "P7 step 5 time",
   "description": "In the smaller unit of 7018H (minutes or seconds); FFFFH = hold.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 9998,
   "documented": "270EH",
   "name": "P7 step 5 PID block",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "1": "Block 1",
    "2": "Block 2",
    "3": "Block 3",
    "4": "Block 4",
    "5": "Block 5",
    "6": "Block 6",
    "7": "Block 7",
    "8": "Block 8",
    "9": "Block 9",
    "10": "Block 10"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 9999,
   "documented": "270FH",
   "name": "P7 step 6 SV",
   "description": "Raw integer; apply decimal point place (7003H).",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 10000,
   "documented": "2710H",
   "name": "P7 step 6 time",
   "description": "In the smaller unit of 7018H (minutes or seconds); FFFFH = hold.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 10001,
   "documented": "2711H",
   "name": "P7 step 6 PID block",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "1": "Block 1",
    "2": "Block 2",
    "3": "Block 3",
    "4": "Block 4",
    "5": "Block 5",
    "6": "Block 6",
    "7": "Block 7",
    "8": "Block 8",
    "9": "Block 9",
    "10": "Block 10"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 10002,
   "documented": "2712H",
   "name": "P7 step 7 SV",
   "description": "Raw integer; apply decimal point place (7003H).",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 10003,
   "documented": "2713H",
   "name": "P7 step 7 time",
   "description": "In the smaller unit of 7018H (minutes or seconds); FFFFH = hold.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 10004,
   "documented": "2714H",
   "name": "P7 step 7 PID block",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "1": "Block 1",
    "2": "Block 2",
    "3": "Block 3",
    "4": "Block 4",
    "5": "Block 5",
    "6": "Block 6",
    "7": "Block 7",
    "8": "Block 8",
    "9": "Block 9",
    "10": "Block 10"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 10005,
   "documented": "2715H",
   "name": "P7 step 8 SV",
   "description": "Raw integer; apply decimal point place (7003H).",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 10006,
   "documented": "2716H",
   "name": "P7 step 8 time",
   "description": "In the smaller unit of 7018H (minutes or seconds); FFFFH = hold.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 10007,
   "documented": "2717H",
   "name": "P7 step 8 PID block",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "1": "Block 1",
    "2": "Block 2",
    "3": "Block 3",
    "4": "Block 4",
    "5": "Block 5",
    "6": "Block 6",
    "7": "Block 7",
    "8": "Block 8",
    "9": "Block 9",
    "10": "Block 10"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 10008,
   "documented": "2718H",
   "name": "P7 step 9 SV",
   "description": "Raw integer; apply decimal point place (7003H).",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 10009,
   "documented": "2719H",
   "name": "P7 step 9 time",
   "description": "In the smaller unit of 7018H (minutes or seconds); FFFFH = hold.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 10010,
   "documented": "271AH",
   "name": "P7 step 9 PID block",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "1": "Block 1",
    "2": "Block 2",
    "3": "Block 3",
    "4": "Block 4",
    "5": "Block 5",
    "6": "Block 6",
    "7": "Block 7",
    "8": "Block 8",
    "9": "Block 9",
    "10": "Block 10"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 10011,
   "documented": "271BH",
   "name": "P7 step 10 SV",
   "description": "Raw integer; apply decimal point place (7003H).",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 10012,
   "documented": "271CH",
   "name": "P7 step 10 time",
   "description": "In the smaller unit of 7018H (minutes or seconds); FFFFH = hold.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 10013,
   "documented": "271DH",
   "name": "P7 step 10 PID block",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "1": "Block 1",
    "2": "Block 2",
    "3": "Block 3",
    "4": "Block 4",
    "5": "Block 5",
    "6": "Block 6",
    "7": "Block 7",
    "8": "Block 8",
    "9": "Block 9",
    "10": "Block 10"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 10014,
   "documented": "271EH",
   "name": "P7 number of repetitions",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 10015,
   "documented": "271FH",
   "name": "P7 pattern link",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Disabled",
    "1": "Enabled"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 10240,
   "documented": "2800H",
   "name": "P8 step 1 SV",
   "description": "Raw integer; apply decimal point place (7003H).",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 10241,
   "documented": "2801H",
   "name": "P8 step 1 time",
   "description": "In the smaller unit of 7018H (minutes or seconds); FFFFH = hold.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 10242,
   "documented": "2802H",
   "name": "P8 step 1 PID block",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "1": "Block 1",
    "2": "Block 2",
    "3": "Block 3",
    "4": "Block 4",
    "5": "Block 5",
    "6": "Block 6",
    "7": "Block 7",
    "8": "Block 8",
    "9": "Block 9",
    "10": "Block 10"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 10243,
   "documented": "2803H",
   "name": "P8 step 2 SV",
   "description": "Raw integer; apply decimal point place (7003H).",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 10244,
   "documented": "2804H",
   "name": "P8 step 2 time",
   "description": "In the smaller unit of 7018H (minutes or seconds); FFFFH = hold.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 10245,
   "documented": "2805H",
   "name": "P8 step 2 PID block",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "1": "Block 1",
    "2": "Block 2",
    "3": "Block 3",
    "4": "Block 4",
    "5": "Block 5",
    "6": "Block 6",
    "7": "Block 7",
    "8": "Block 8",
    "9": "Block 9",
    "10": "Block 10"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 10246,
   "documented": "2806H",
   "name": "P8 step 3 SV",
   "description": "Raw integer; apply decimal point place (7003H).",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 10247,
   "documented": "2807H",
   "name": "P8 step 3 time",
   "description": "In the smaller unit of 7018H (minutes or seconds); FFFFH = hold.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 10248,
   "documented": "2808H",
   "name": "P8 step 3 PID block",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "1": "Block 1",
    "2": "Block 2",
    "3": "Block 3",
    "4": "Block 4",
    "5": "Block 5",
    "6": "Block 6",
    "7": "Block 7",
    "8": "Block 8",
    "9": "Block 9",
    "10": "Block 10"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 10249,
   "documented": "2809H",
   "name": "P8 step 4 SV",
   "description": "Raw integer; apply decimal point place (7003H).",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 10250,
   "documented": "280AH",
   "name": "P8 step 4 time",
   "description": "In the smaller unit of 7018H (minutes or seconds); FFFFH = hold.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 10251,
   "documented": "280BH",
   "name": "P8 step 4 PID block",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "1": "Block 1",
    "2": "Block 2",
    "3": "Block 3",
    "4": "Block 4",
    "5": "Block 5",
    "6": "Block 6",
    "7": "Block 7",
    "8": "Block 8",
    "9": "Block 9",
    "10": "Block 10"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 10252,
   "documented": "280CH",
   "name": "P8 step 5 SV",
   "description": "Raw integer; apply decimal point place (7003H).",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 10253,
   "documented": "280DH",
   "name": "P8 step 5 time",
   "description": "In the smaller unit of 7018H (minutes or seconds); FFFFH = hold.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 10254,
   "documented": "280EH",
   "name": "P8 step 5 PID block",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "1": "Block 1",
    "2": "Block 2",
    "3": "Block 3",
    "4": "Block 4",
    "5": "Block 5",
    "6": "Block 6",
    "7": "Block 7",
    "8": "Block 8",
    "9": "Block 9",
    "10": "Block 10"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 10255,
   "documented": "280FH",
   "name": "P8 step 6 SV",
   "description": "Raw integer; apply decimal point place (7003H).",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 10256,
   "documented": "2810H",
   "name": "P8 step 6 time",
   "description": "In the smaller unit of 7018H (minutes or seconds); FFFFH = hold.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 10257,
   "documented": "2811H",
   "name": "P8 step 6 PID block",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "1": "Block 1",
    "2": "Block 2",
    "3": "Block 3",
    "4": "Block 4",
    "5": "Block 5",
    "6": "Block 6",
    "7": "Block 7",
    "8": "Block 8",
    "9": "Block 9",
    "10": "Block 10"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 10258,
   "documented": "2812H",
   "name": "P8 step 7 SV",
   "description": "Raw integer; apply decimal point place (7003H).",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 10259,
   "documented": "2813H",
   "name": "P8 step 7 time",
   "description": "In the smaller unit of 7018H (minutes or seconds); FFFFH = hold.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 10260,
   "documented": "2814H",
   "name": "P8 step 7 PID block",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "1": "Block 1",
    "2": "Block 2",
    "3": "Block 3",
    "4": "Block 4",
    "5": "Block 5",
    "6": "Block 6",
    "7": "Block 7",
    "8": "Block 8",
    "9": "Block 9",
    "10": "Block 10"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 10261,
   "documented": "2815H",
   "name": "P8 step 8 SV",
   "description": "Raw integer; apply decimal point place (7003H).",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 10262,
   "documented": "2816H",
   "name": "P8 step 8 time",
   "description": "In the smaller unit of 7018H (minutes or seconds); FFFFH = hold.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 10263,
   "documented": "2817H",
   "name": "P8 step 8 PID block",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "1": "Block 1",
    "2": "Block 2",
    "3": "Block 3",
    "4": "Block 4",
    "5": "Block 5",
    "6": "Block 6",
    "7": "Block 7",
    "8": "Block 8",
    "9": "Block 9",
    "10": "Block 10"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 10264,
   "documented": "2818H",
   "name": "P8 step 9 SV",
   "description": "Raw integer; apply decimal point place (7003H).",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 10265,
   "documented": "2819H",
   "name": "P8 step 9 time",
   "description": "In the smaller unit of 7018H (minutes or seconds); FFFFH = hold.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 10266,
   "documented": "281AH",
   "name": "P8 step 9 PID block",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "1": "Block 1",
    "2": "Block 2",
    "3": "Block 3",
    "4": "Block 4",
    "5": "Block 5",
    "6": "Block 6",
    "7": "Block 7",
    "8": "Block 8",
    "9": "Block 9",
    "10": "Block 10"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 10267,
   "documented": "281BH",
   "name": "P8 step 10 SV",
   "description": "Raw integer; apply decimal point place (7003H).",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 10268,
   "documented": "281CH",
   "name": "P8 step 10 time",
   "description": "In the smaller unit of 7018H (minutes or seconds); FFFFH = hold.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 10269,
   "documented": "281DH",
   "name": "P8 step 10 PID block",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "1": "Block 1",
    "2": "Block 2",
    "3": "Block 3",
    "4": "Block 4",
    "5": "Block 5",
    "6": "Block 6",
    "7": "Block 7",
    "8": "Block 8",
    "9": "Block 9",
    "10": "Block 10"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 10270,
   "documented": "281EH",
   "name": "P8 number of repetitions",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 10271,
   "documented": "281FH",
   "name": "P8 pattern link",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Disabled",
    "1": "Enabled"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 10496,
   "documented": "2900H",
   "name": "P9 step 1 SV",
   "description": "Raw integer; apply decimal point place (7003H).",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 10497,
   "documented": "2901H",
   "name": "P9 step 1 time",
   "description": "In the smaller unit of 7018H (minutes or seconds); FFFFH = hold.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 10498,
   "documented": "2902H",
   "name": "P9 step 1 PID block",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "1": "Block 1",
    "2": "Block 2",
    "3": "Block 3",
    "4": "Block 4",
    "5": "Block 5",
    "6": "Block 6",
    "7": "Block 7",
    "8": "Block 8",
    "9": "Block 9",
    "10": "Block 10"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 10499,
   "documented": "2903H",
   "name": "P9 step 2 SV",
   "description": "Raw integer; apply decimal point place (7003H).",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 10500,
   "documented": "2904H",
   "name": "P9 step 2 time",
   "description": "In the smaller unit of 7018H (minutes or seconds); FFFFH = hold.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 10501,
   "documented": "2905H",
   "name": "P9 step 2 PID block",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "1": "Block 1",
    "2": "Block 2",
    "3": "Block 3",
    "4": "Block 4",
    "5": "Block 5",
    "6": "Block 6",
    "7": "Block 7",
    "8": "Block 8",
    "9": "Block 9",
    "10": "Block 10"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 10502,
   "documented": "2906H",
   "name": "P9 step 3 SV",
   "description": "Raw integer; apply decimal point place (7003H).",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 10503,
   "documented": "2907H",
   "name": "P9 step 3 time",
   "description": "In the smaller unit of 7018H (minutes or seconds); FFFFH = hold.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 10504,
   "documented": "2908H",
   "name": "P9 step 3 PID block",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "1": "Block 1",
    "2": "Block 2",
    "3": "Block 3",
    "4": "Block 4",
    "5": "Block 5",
    "6": "Block 6",
    "7": "Block 7",
    "8": "Block 8",
    "9": "Block 9",
    "10": "Block 10"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 10505,
   "documented": "2909H",
   "name": "P9 step 4 SV",
   "description": "Raw integer; apply decimal point place (7003H).",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 10506,
   "documented": "290AH",
   "name": "P9 step 4 time",
   "description": "In the smaller unit of 7018H (minutes or seconds); FFFFH = hold.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 10507,
   "documented": "290BH",
   "name": "P9 step 4 PID block",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "1": "Block 1",
    "2": "Block 2",
    "3": "Block 3",
    "4": "Block 4",
    "5": "Block 5",
    "6": "Block 6",
    "7": "Block 7",
    "8": "Block 8",
    "9": "Block 9",
    "10": "Block 10"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 10508,
   "documented": "290CH",
   "name": "P9 step 5 SV",
   "description": "Raw integer; apply decimal point place (7003H).",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 10509,
   "documented": "290DH",
   "name": "P9 step 5 time",
   "description": "In the smaller unit of 7018H (minutes or seconds); FFFFH = hold.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 10510,
   "documented": "290EH",
   "name": "P9 step 5 PID block",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "1": "Block 1",
    "2": "Block 2",
    "3": "Block 3",
    "4": "Block 4",
    "5": "Block 5",
    "6": "Block 6",
    "7": "Block 7",
    "8": "Block 8",
    "9": "Block 9",
    "10": "Block 10"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 10511,
   "documented": "290FH",
   "name": "P9 step 6 SV",
   "description": "Raw integer; apply decimal point place (7003H).",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 10512,
   "documented": "2910H",
   "name": "P9 step 6 time",
   "description": "In the smaller unit of 7018H (minutes or seconds); FFFFH = hold.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 10513,
   "documented": "2911H",
   "name": "P9 step 6 PID block",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "1": "Block 1",
    "2": "Block 2",
    "3": "Block 3",
    "4": "Block 4",
    "5": "Block 5",
    "6": "Block 6",
    "7": "Block 7",
    "8": "Block 8",
    "9": "Block 9",
    "10": "Block 10"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 10514,
   "documented": "2912H",
   "name": "P9 step 7 SV",
   "description": "Raw integer; apply decimal point place (7003H).",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 10515,
   "documented": "2913H",
   "name": "P9 step 7 time",
   "description": "In the smaller unit of 7018H (minutes or seconds); FFFFH = hold.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 10516,
   "documented": "2914H",
   "name": "P9 step 7 PID block",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "1": "Block 1",
    "2": "Block 2",
    "3": "Block 3",
    "4": "Block 4",
    "5": "Block 5",
    "6": "Block 6",
    "7": "Block 7",
    "8": "Block 8",
    "9": "Block 9",
    "10": "Block 10"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 10517,
   "documented": "2915H",
   "name": "P9 step 8 SV",
   "description": "Raw integer; apply decimal point place (7003H).",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 10518,
   "documented": "2916H",
   "name": "P9 step 8 time",
   "description": "In the smaller unit of 7018H (minutes or seconds); FFFFH = hold.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 10519,
   "documented": "2917H",
   "name": "P9 step 8 PID block",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "1": "Block 1",
    "2": "Block 2",
    "3": "Block 3",
    "4": "Block 4",
    "5": "Block 5",
    "6": "Block 6",
    "7": "Block 7",
    "8": "Block 8",
    "9": "Block 9",
    "10": "Block 10"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 10520,
   "documented": "2918H",
   "name": "P9 step 9 SV",
   "description": "Raw integer; apply decimal point place (7003H).",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 10521,
   "documented": "2919H",
   "name": "P9 step 9 time",
   "description": "In the smaller unit of 7018H (minutes or seconds); FFFFH = hold.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 10522,
   "documented": "291AH",
   "name": "P9 step 9 PID block",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "1": "Block 1",
    "2": "Block 2",
    "3": "Block 3",
    "4": "Block 4",
    "5": "Block 5",
    "6": "Block 6",
    "7": "Block 7",
    "8": "Block 8",
    "9": "Block 9",
    "10": "Block 10"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 10523,
   "documented": "291BH",
   "name": "P9 step 10 SV",
   "description": "Raw integer; apply decimal point place (7003H).",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 10524,
   "documented": "291CH",
   "name": "P9 step 10 time",
   "description": "In the smaller unit of 7018H (minutes or seconds); FFFFH = hold.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 10525,
   "documented": "291DH",
   "name": "P9 step 10 PID block",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "1": "Block 1",
    "2": "Block 2",
    "3": "Block 3",
    "4": "Block 4",
    "5": "Block 5",
    "6": "Block 6",
    "7": "Block 7",
    "8": "Block 8",
    "9": "Block 9",
    "10": "Block 10"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 10526,
   "documented": "291EH",
   "name": "P9 number of repetitions",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 10527,
   "documented": "291FH",
   "name": "P9 pattern link",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Disabled",
    "1": "Enabled"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 10752,
   "documented": "2A00H",
   "name": "P10 step 1 SV",
   "description": "Raw integer; apply decimal point place (7003H).",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 10753,
   "documented": "2A01H",
   "name": "P10 step 1 time",
   "description": "In the smaller unit of 7018H (minutes or seconds); FFFFH = hold.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 10754,
   "documented": "2A02H",
   "name": "P10 step 1 PID block",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "1": "Block 1",
    "2": "Block 2",
    "3": "Block 3",
    "4": "Block 4",
    "5": "Block 5",
    "6": "Block 6",
    "7": "Block 7",
    "8": "Block 8",
    "9": "Block 9",
    "10": "Block 10"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 10755,
   "documented": "2A03H",
   "name": "P10 step 2 SV",
   "description": "Raw integer; apply decimal point place (7003H).",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 10756,
   "documented": "2A04H",
   "name": "P10 step 2 time",
   "description": "In the smaller unit of 7018H (minutes or seconds); FFFFH = hold.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 10757,
   "documented": "2A05H",
   "name": "P10 step 2 PID block",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "1": "Block 1",
    "2": "Block 2",
    "3": "Block 3",
    "4": "Block 4",
    "5": "Block 5",
    "6": "Block 6",
    "7": "Block 7",
    "8": "Block 8",
    "9": "Block 9",
    "10": "Block 10"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 10758,
   "documented": "2A06H",
   "name": "P10 step 3 SV",
   "description": "Raw integer; apply decimal point place (7003H).",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 10759,
   "documented": "2A07H",
   "name": "P10 step 3 time",
   "description": "In the smaller unit of 7018H (minutes or seconds); FFFFH = hold.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 10760,
   "documented": "2A08H",
   "name": "P10 step 3 PID block",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "1": "Block 1",
    "2": "Block 2",
    "3": "Block 3",
    "4": "Block 4",
    "5": "Block 5",
    "6": "Block 6",
    "7": "Block 7",
    "8": "Block 8",
    "9": "Block 9",
    "10": "Block 10"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 10761,
   "documented": "2A09H",
   "name": "P10 step 4 SV",
   "description": "Raw integer; apply decimal point place (7003H).",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 10762,
   "documented": "2A0AH",
   "name": "P10 step 4 time",
   "description": "In the smaller unit of 7018H (minutes or seconds); FFFFH = hold.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 10763,
   "documented": "2A0BH",
   "name": "P10 step 4 PID block",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "1": "Block 1",
    "2": "Block 2",
    "3": "Block 3",
    "4": "Block 4",
    "5": "Block 5",
    "6": "Block 6",
    "7": "Block 7",
    "8": "Block 8",
    "9": "Block 9",
    "10": "Block 10"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 10764,
   "documented": "2A0CH",
   "name": "P10 step 5 SV",
   "description": "Raw integer; apply decimal point place (7003H).",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 10765,
   "documented": "2A0DH",
   "name": "P10 step 5 time",
   "description": "In the smaller unit of 7018H (minutes or seconds); FFFFH = hold.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 10766,
   "documented": "2A0EH",
   "name": "P10 step 5 PID block",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "1": "Block 1",
    "2": "Block 2",
    "3": "Block 3",
    "4": "Block 4",
    "5": "Block 5",
    "6": "Block 6",
    "7": "Block 7",
    "8": "Block 8",
    "9": "Block 9",
    "10": "Block 10"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 10767,
   "documented": "2A0FH",
   "name": "P10 step 6 SV",
   "description": "Raw integer; apply decimal point place (7003H).",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 10768,
   "documented": "2A10H",
   "name": "P10 step 6 time",
   "description": "In the smaller unit of 7018H (minutes or seconds); FFFFH = hold.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 10769,
   "documented": "2A11H",
   "name": "P10 step 6 PID block",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "1": "Block 1",
    "2": "Block 2",
    "3": "Block 3",
    "4": "Block 4",
    "5": "Block 5",
    "6": "Block 6",
    "7": "Block 7",
    "8": "Block 8",
    "9": "Block 9",
    "10": "Block 10"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 10770,
   "documented": "2A12H",
   "name": "P10 step 7 SV",
   "description": "Raw integer; apply decimal point place (7003H).",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 10771,
   "documented": "2A13H",
   "name": "P10 step 7 time",
   "description": "In the smaller unit of 7018H (minutes or seconds); FFFFH = hold.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 10772,
   "documented": "2A14H",
   "name": "P10 step 7 PID block",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "1": "Block 1",
    "2": "Block 2",
    "3": "Block 3",
    "4": "Block 4",
    "5": "Block 5",
    "6": "Block 6",
    "7": "Block 7",
    "8": "Block 8",
    "9": "Block 9",
    "10": "Block 10"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 10773,
   "documented": "2A15H",
   "name": "P10 step 8 SV",
   "description": "Raw integer; apply decimal point place (7003H).",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 10774,
   "documented": "2A16H",
   "name": "P10 step 8 time",
   "description": "In the smaller unit of 7018H (minutes or seconds); FFFFH = hold.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 10775,
   "documented": "2A17H",
   "name": "P10 step 8 PID block",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "1": "Block 1",
    "2": "Block 2",
    "3": "Block 3",
    "4": "Block 4",
    "5": "Block 5",
    "6": "Block 6",
    "7": "Block 7",
    "8": "Block 8",
    "9": "Block 9",
    "10": "Block 10"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 10776,
   "documented": "2A18H",
   "name": "P10 step 9 SV",
   "description": "Raw integer; apply decimal point place (7003H).",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 10777,
   "documented": "2A19H",
   "name": "P10 step 9 time",
   "description": "In the smaller unit of 7018H (minutes or seconds); FFFFH = hold.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 10778,
   "documented": "2A1AH",
   "name": "P10 step 9 PID block",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "1": "Block 1",
    "2": "Block 2",
    "3": "Block 3",
    "4": "Block 4",
    "5": "Block 5",
    "6": "Block 6",
    "7": "Block 7",
    "8": "Block 8",
    "9": "Block 9",
    "10": "Block 10"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 10779,
   "documented": "2A1BH",
   "name": "P10 step 10 SV",
   "description": "Raw integer; apply decimal point place (7003H).",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 10780,
   "documented": "2A1CH",
   "name": "P10 step 10 time",
   "description": "In the smaller unit of 7018H (minutes or seconds); FFFFH = hold.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 10781,
   "documented": "2A1DH",
   "name": "P10 step 10 PID block",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "1": "Block 1",
    "2": "Block 2",
    "3": "Block 3",
    "4": "Block 4",
    "5": "Block 5",
    "6": "Block 6",
    "7": "Block 7",
    "8": "Block 8",
    "9": "Block 9",
    "10": "Block 10"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 10782,
   "documented": "2A1EH",
   "name": "P10 number of repetitions",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 10783,
   "documented": "2A1FH",
   "name": "P10 pattern link",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Disabled",
    "1": "Enabled"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 12544,
   "documented": "3100H",
   "name": "P1 EV1 alarm value",
   "description": "Raw integer; apply decimal point place (7003H).",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 12545,
   "documented": "3101H",
   "name": "P1 EV1 high limit alarm value",
   "description": "Raw integer; apply decimal point place (7003H).",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 12546,
   "documented": "3102H",
   "name": "P1 TS1 output OFF time",
   "description": "Time signal; smaller unit of 7018H.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 12547,
   "documented": "3103H",
   "name": "P1 TS1 output ON time",
   "description": "Time signal; smaller unit of 7018H.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 12548,
   "documented": "3104H",
   "name": "P1 EV2 alarm value",
   "description": "Raw integer; apply decimal point place (7003H).",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 12549,
   "documented": "3105H",
   "name": "P1 EV2 high limit alarm value",
   "description": "Raw integer; apply decimal point place (7003H).",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 12550,
   "documented": "3106H",
   "name": "P1 TS2 output OFF time",
   "description": "Time signal; smaller unit of 7018H.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 12551,
   "documented": "3107H",
   "name": "P1 TS2 output ON time",
   "description": "Time signal; smaller unit of 7018H.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 12552,
   "documented": "3108H",
   "name": "P1 EV3 alarm value",
   "description": "Raw integer; apply decimal point place (7003H).",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 12553,
   "documented": "3109H",
   "name": "P1 EV3 high limit alarm value",
   "description": "Raw integer; apply decimal point place (7003H).",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 12554,
   "documented": "310AH",
   "name": "P1 TS3 output OFF time",
   "description": "Time signal; smaller unit of 7018H.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 12555,
   "documented": "310BH",
   "name": "P1 TS3 output ON time",
   "description": "Time signal; smaller unit of 7018H.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 12800,
   "documented": "3200H",
   "name": "P2 EV1 alarm value",
   "description": "Raw integer; apply decimal point place (7003H).",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 12801,
   "documented": "3201H",
   "name": "P2 EV1 high limit alarm value",
   "description": "Raw integer; apply decimal point place (7003H).",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 12802,
   "documented": "3202H",
   "name": "P2 TS1 output OFF time",
   "description": "Time signal; smaller unit of 7018H.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 12803,
   "documented": "3203H",
   "name": "P2 TS1 output ON time",
   "description": "Time signal; smaller unit of 7018H.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 12804,
   "documented": "3204H",
   "name": "P2 EV2 alarm value",
   "description": "Raw integer; apply decimal point place (7003H).",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 12805,
   "documented": "3205H",
   "name": "P2 EV2 high limit alarm value",
   "description": "Raw integer; apply decimal point place (7003H).",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 12806,
   "documented": "3206H",
   "name": "P2 TS2 output OFF time",
   "description": "Time signal; smaller unit of 7018H.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 12807,
   "documented": "3207H",
   "name": "P2 TS2 output ON time",
   "description": "Time signal; smaller unit of 7018H.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 12808,
   "documented": "3208H",
   "name": "P2 EV3 alarm value",
   "description": "Raw integer; apply decimal point place (7003H).",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 12809,
   "documented": "3209H",
   "name": "P2 EV3 high limit alarm value",
   "description": "Raw integer; apply decimal point place (7003H).",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 12810,
   "documented": "320AH",
   "name": "P2 TS3 output OFF time",
   "description": "Time signal; smaller unit of 7018H.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 12811,
   "documented": "320BH",
   "name": "P2 TS3 output ON time",
   "description": "Time signal; smaller unit of 7018H.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 13056,
   "documented": "3300H",
   "name": "P3 EV1 alarm value",
   "description": "Raw integer; apply decimal point place (7003H).",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 13057,
   "documented": "3301H",
   "name": "P3 EV1 high limit alarm value",
   "description": "Raw integer; apply decimal point place (7003H).",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 13058,
   "documented": "3302H",
   "name": "P3 TS1 output OFF time",
   "description": "Time signal; smaller unit of 7018H.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 13059,
   "documented": "3303H",
   "name": "P3 TS1 output ON time",
   "description": "Time signal; smaller unit of 7018H.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 13060,
   "documented": "3304H",
   "name": "P3 EV2 alarm value",
   "description": "Raw integer; apply decimal point place (7003H).",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 13061,
   "documented": "3305H",
   "name": "P3 EV2 high limit alarm value",
   "description": "Raw integer; apply decimal point place (7003H).",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 13062,
   "documented": "3306H",
   "name": "P3 TS2 output OFF time",
   "description": "Time signal; smaller unit of 7018H.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 13063,
   "documented": "3307H",
   "name": "P3 TS2 output ON time",
   "description": "Time signal; smaller unit of 7018H.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 13064,
   "documented": "3308H",
   "name": "P3 EV3 alarm value",
   "description": "Raw integer; apply decimal point place (7003H).",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 13065,
   "documented": "3309H",
   "name": "P3 EV3 high limit alarm value",
   "description": "Raw integer; apply decimal point place (7003H).",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 13066,
   "documented": "330AH",
   "name": "P3 TS3 output OFF time",
   "description": "Time signal; smaller unit of 7018H.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 13067,
   "documented": "330BH",
   "name": "P3 TS3 output ON time",
   "description": "Time signal; smaller unit of 7018H.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 13312,
   "documented": "3400H",
   "name": "P4 EV1 alarm value",
   "description": "Raw integer; apply decimal point place (7003H).",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 13313,
   "documented": "3401H",
   "name": "P4 EV1 high limit alarm value",
   "description": "Raw integer; apply decimal point place (7003H).",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 13314,
   "documented": "3402H",
   "name": "P4 TS1 output OFF time",
   "description": "Time signal; smaller unit of 7018H.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 13315,
   "documented": "3403H",
   "name": "P4 TS1 output ON time",
   "description": "Time signal; smaller unit of 7018H.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 13316,
   "documented": "3404H",
   "name": "P4 EV2 alarm value",
   "description": "Raw integer; apply decimal point place (7003H).",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 13317,
   "documented": "3405H",
   "name": "P4 EV2 high limit alarm value",
   "description": "Raw integer; apply decimal point place (7003H).",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 13318,
   "documented": "3406H",
   "name": "P4 TS2 output OFF time",
   "description": "Time signal; smaller unit of 7018H.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 13319,
   "documented": "3407H",
   "name": "P4 TS2 output ON time",
   "description": "Time signal; smaller unit of 7018H.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 13320,
   "documented": "3408H",
   "name": "P4 EV3 alarm value",
   "description": "Raw integer; apply decimal point place (7003H).",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 13321,
   "documented": "3409H",
   "name": "P4 EV3 high limit alarm value",
   "description": "Raw integer; apply decimal point place (7003H).",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 13322,
   "documented": "340AH",
   "name": "P4 TS3 output OFF time",
   "description": "Time signal; smaller unit of 7018H.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 13323,
   "documented": "340BH",
   "name": "P4 TS3 output ON time",
   "description": "Time signal; smaller unit of 7018H.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 13568,
   "documented": "3500H",
   "name": "P5 EV1 alarm value",
   "description": "Raw integer; apply decimal point place (7003H).",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 13569,
   "documented": "3501H",
   "name": "P5 EV1 high limit alarm value",
   "description": "Raw integer; apply decimal point place (7003H).",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 13570,
   "documented": "3502H",
   "name": "P5 TS1 output OFF time",
   "description": "Time signal; smaller unit of 7018H.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 13571,
   "documented": "3503H",
   "name": "P5 TS1 output ON time",
   "description": "Time signal; smaller unit of 7018H.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 13572,
   "documented": "3504H",
   "name": "P5 EV2 alarm value",
   "description": "Raw integer; apply decimal point place (7003H).",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 13573,
   "documented": "3505H",
   "name": "P5 EV2 high limit alarm value",
   "description": "Raw integer; apply decimal point place (7003H).",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 13574,
   "documented": "3506H",
   "name": "P5 TS2 output OFF time",
   "description": "Time signal; smaller unit of 7018H.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 13575,
   "documented": "3507H",
   "name": "P5 TS2 output ON time",
   "description": "Time signal; smaller unit of 7018H.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 13576,
   "documented": "3508H",
   "name": "P5 EV3 alarm value",
   "description": "Raw integer; apply decimal point place (7003H).",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 13577,
   "documented": "3509H",
   "name": "P5 EV3 high limit alarm value",
   "description": "Raw integer; apply decimal point place (7003H).",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 13578,
   "documented": "350AH",
   "name": "P5 TS3 output OFF time",
   "description": "Time signal; smaller unit of 7018H.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 13579,
   "documented": "350BH",
   "name": "P5 TS3 output ON time",
   "description": "Time signal; smaller unit of 7018H.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 13824,
   "documented": "3600H",
   "name": "P6 EV1 alarm value",
   "description": "Raw integer; apply decimal point place (7003H).",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 13825,
   "documented": "3601H",
   "name": "P6 EV1 high limit alarm value",
   "description": "Raw integer; apply decimal point place (7003H).",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 13826,
   "documented": "3602H",
   "name": "P6 TS1 output OFF time",
   "description": "Time signal; smaller unit of 7018H.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 13827,
   "documented": "3603H",
   "name": "P6 TS1 output ON time",
   "description": "Time signal; smaller unit of 7018H.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 13828,
   "documented": "3604H",
   "name": "P6 EV2 alarm value",
   "description": "Raw integer; apply decimal point place (7003H).",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 13829,
   "documented": "3605H",
   "name": "P6 EV2 high limit alarm value",
   "description": "Raw integer; apply decimal point place (7003H).",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 13830,
   "documented": "3606H",
   "name": "P6 TS2 output OFF time",
   "description": "Time signal; smaller unit of 7018H.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 13831,
   "documented": "3607H",
   "name": "P6 TS2 output ON time",
   "description": "Time signal; smaller unit of 7018H.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 13832,
   "documented": "3608H",
   "name": "P6 EV3 alarm value",
   "description": "Raw integer; apply decimal point place (7003H).",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 13833,
   "documented": "3609H",
   "name": "P6 EV3 high limit alarm value",
   "description": "Raw integer; apply decimal point place (7003H).",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 13834,
   "documented": "360AH",
   "name": "P6 TS3 output OFF time",
   "description": "Time signal; smaller unit of 7018H.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 13835,
   "documented": "360BH",
   "name": "P6 TS3 output ON time",
   "description": "Time signal; smaller unit of 7018H.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 14080,
   "documented": "3700H",
   "name": "P7 EV1 alarm value",
   "description": "Raw integer; apply decimal point place (7003H).",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 14081,
   "documented": "3701H",
   "name": "P7 EV1 high limit alarm value",
   "description": "Raw integer; apply decimal point place (7003H).",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 14082,
   "documented": "3702H",
   "name": "P7 TS1 output OFF time",
   "description": "Time signal; smaller unit of 7018H.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 14083,
   "documented": "3703H",
   "name": "P7 TS1 output ON time",
   "description": "Time signal; smaller unit of 7018H.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 14084,
   "documented": "3704H",
   "name": "P7 EV2 alarm value",
   "description": "Raw integer; apply decimal point place (7003H).",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 14085,
   "documented": "3705H",
   "name": "P7 EV2 high limit alarm value",
   "description": "Raw integer; apply decimal point place (7003H).",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 14086,
   "documented": "3706H",
   "name": "P7 TS2 output OFF time",
   "description": "Time signal; smaller unit of 7018H.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 14087,
   "documented": "3707H",
   "name": "P7 TS2 output ON time",
   "description": "Time signal; smaller unit of 7018H.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 14088,
   "documented": "3708H",
   "name": "P7 EV3 alarm value",
   "description": "Raw integer; apply decimal point place (7003H).",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 14089,
   "documented": "3709H",
   "name": "P7 EV3 high limit alarm value",
   "description": "Raw integer; apply decimal point place (7003H).",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 14090,
   "documented": "370AH",
   "name": "P7 TS3 output OFF time",
   "description": "Time signal; smaller unit of 7018H.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 14091,
   "documented": "370BH",
   "name": "P7 TS3 output ON time",
   "description": "Time signal; smaller unit of 7018H.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 14336,
   "documented": "3800H",
   "name": "P8 EV1 alarm value",
   "description": "Raw integer; apply decimal point place (7003H).",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 14337,
   "documented": "3801H",
   "name": "P8 EV1 high limit alarm value",
   "description": "Raw integer; apply decimal point place (7003H).",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 14338,
   "documented": "3802H",
   "name": "P8 TS1 output OFF time",
   "description": "Time signal; smaller unit of 7018H.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 14339,
   "documented": "3803H",
   "name": "P8 TS1 output ON time",
   "description": "Time signal; smaller unit of 7018H.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 14340,
   "documented": "3804H",
   "name": "P8 EV2 alarm value",
   "description": "Raw integer; apply decimal point place (7003H).",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 14341,
   "documented": "3805H",
   "name": "P8 EV2 high limit alarm value",
   "description": "Raw integer; apply decimal point place (7003H).",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 14342,
   "documented": "3806H",
   "name": "P8 TS2 output OFF time",
   "description": "Time signal; smaller unit of 7018H.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 14343,
   "documented": "3807H",
   "name": "P8 TS2 output ON time",
   "description": "Time signal; smaller unit of 7018H.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 14344,
   "documented": "3808H",
   "name": "P8 EV3 alarm value",
   "description": "Raw integer; apply decimal point place (7003H).",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 14345,
   "documented": "3809H",
   "name": "P8 EV3 high limit alarm value",
   "description": "Raw integer; apply decimal point place (7003H).",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 14346,
   "documented": "380AH",
   "name": "P8 TS3 output OFF time",
   "description": "Time signal; smaller unit of 7018H.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 14347,
   "documented": "380BH",
   "name": "P8 TS3 output ON time",
   "description": "Time signal; smaller unit of 7018H.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 14592,
   "documented": "3900H",
   "name": "P9 EV1 alarm value",
   "description": "Raw integer; apply decimal point place (7003H).",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 14593,
   "documented": "3901H",
   "name": "P9 EV1 high limit alarm value",
   "description": "Raw integer; apply decimal point place (7003H).",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 14594,
   "documented": "3902H",
   "name": "P9 TS1 output OFF time",
   "description": "Time signal; smaller unit of 7018H.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 14595,
   "documented": "3903H",
   "name": "P9 TS1 output ON time",
   "description": "Time signal; smaller unit of 7018H.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 14596,
   "documented": "3904H",
   "name": "P9 EV2 alarm value",
   "description": "Raw integer; apply decimal point place (7003H).",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 14597,
   "documented": "3905H",
   "name": "P9 EV2 high limit alarm value",
   "description": "Raw integer; apply decimal point place (7003H).",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 14598,
   "documented": "3906H",
   "name": "P9 TS2 output OFF time",
   "description": "Time signal; smaller unit of 7018H.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 14599,
   "documented": "3907H",
   "name": "P9 TS2 output ON time",
   "description": "Time signal; smaller unit of 7018H.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 14600,
   "documented": "3908H",
   "name": "P9 EV3 alarm value",
   "description": "Raw integer; apply decimal point place (7003H).",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 14601,
   "documented": "3909H",
   "name": "P9 EV3 high limit alarm value",
   "description": "Raw integer; apply decimal point place (7003H).",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 14602,
   "documented": "390AH",
   "name": "P9 TS3 output OFF time",
   "description": "Time signal; smaller unit of 7018H.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 14603,
   "documented": "390BH",
   "name": "P9 TS3 output ON time",
   "description": "Time signal; smaller unit of 7018H.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 14848,
   "documented": "3A00H",
   "name": "P10 EV1 alarm value",
   "description": "Raw integer; apply decimal point place (7003H).",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 14849,
   "documented": "3A01H",
   "name": "P10 EV1 high limit alarm value",
   "description": "Raw integer; apply decimal point place (7003H).",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 14850,
   "documented": "3A02H",
   "name": "P10 TS1 output OFF time",
   "description": "Time signal; smaller unit of 7018H.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 14851,
   "documented": "3A03H",
   "name": "P10 TS1 output ON time",
   "description": "Time signal; smaller unit of 7018H.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 14852,
   "documented": "3A04H",
   "name": "P10 EV2 alarm value",
   "description": "Raw integer; apply decimal point place (7003H).",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 14853,
   "documented": "3A05H",
   "name": "P10 EV2 high limit alarm value",
   "description": "Raw integer; apply decimal point place (7003H).",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 14854,
   "documented": "3A06H",
   "name": "P10 TS2 output OFF time",
   "description": "Time signal; smaller unit of 7018H.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 14855,
   "documented": "3A07H",
   "name": "P10 TS2 output ON time",
   "description": "Time signal; smaller unit of 7018H.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 14856,
   "documented": "3A08H",
   "name": "P10 EV3 alarm value",
   "description": "Raw integer; apply decimal point place (7003H).",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 14857,
   "documented": "3A09H",
   "name": "P10 EV3 high limit alarm value",
   "description": "Raw integer; apply decimal point place (7003H).",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 14858,
   "documented": "3A0AH",
   "name": "P10 TS3 output OFF time",
   "description": "Time signal; smaller unit of 7018H.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 14859,
   "documented": "3A0BH",
   "name": "P10 TS3 output ON time",
   "description": "Time signal; smaller unit of 7018H.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 16384,
   "documented": "4000H",
   "name": "AT Perform/Cancel",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "AT Cancel",
    "1": "AT Perform"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 16385,
   "documented": "4001H",
   "name": "PID block number",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "1": "Block 1",
    "2": "Block 2",
    "3": "Block 3",
    "4": "Block 4",
    "5": "Block 5",
    "6": "Block 6",
    "7": "Block 7",
    "8": "Block 8",
    "9": "Block 9",
    "10": "Block 10"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 16386,
   "documented": "4002H",
   "name": "OUT1 proportional cycle",
   "description": "0-120 s; 0 means 0.5 s.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "s",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 16387,
   "documented": "4003H",
   "name": "OUT1 ON/OFF hysteresis",
   "description": "Raw integer; apply decimal point place (7003H).",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 16388,
   "documented": "4004H",
   "name": "OUT1 high limit",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 16389,
   "documented": "4005H",
   "name": "OUT1 low limit",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 16390,
   "documented": "4006H",
   "name": "OUT1 rate-of-change",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 16391,
   "documented": "4007H",
   "name": "OUT2 cooling method",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Air cooling",
    "1": "Oil cooling",
    "2": "Water cooling"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 16392,
   "documented": "4008H",
   "name": "OUT2 proportional cycle",
   "description": "0-120 s; 0 means 0.5 s.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "s",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 16393,
   "documented": "4009H",
   "name": "OUT2 ON/OFF hysteresis",
   "description": "Raw integer; apply decimal point place (7003H).",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 16394,
   "documented": "400AH",
   "name": "OUT2 high limit",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 16395,
   "documented": "400BH",
   "name": "OUT2 low limit",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 16396,
   "documented": "400CH",
   "name": "Overlap/Dead band",
   "description": "Raw integer; apply decimal point place (7003H).",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 16397,
   "documented": "400DH",
   "name": "Direct/Reverse action",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Reverse action",
    "1": "Direct action"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 16398,
   "documented": "400EH",
   "name": "Heater burnout alarm 1 value",
   "description": "Decimal point ignored.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 16399,
   "documented": "400FH",
   "name": "Heater burnout alarm 2 value",
   "description": "Decimal point ignored.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 16400,
   "documented": "4010H",
   "name": "Loop break alarm time",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 16401,
   "documented": "4011H",
   "name": "Loop break alarm band",
   "description": "Raw integer; apply decimal point place (7003H).",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 16658,
   "documented": "4112H",
   "name": "Block 1 OUT1 proportional band",
   "description": "Decimal point ignored.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 16659,
   "documented": "4113H",
   "name": "Block 1 integral time",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 16660,
   "documented": "4114H",
   "name": "Block 1 derivative time",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 16661,
   "documented": "4115H",
   "name": "Block 1 ARW",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 16662,
   "documented": "4116H",
   "name": "Block 1 OUT2 proportional band",
   "description": "Decimal point ignored.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 16914,
   "documented": "4212H",
   "name": "Block 2 OUT1 proportional band",
   "description": "Decimal point ignored.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 16915,
   "documented": "4213H",
   "name": "Block 2 integral time",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 16916,
   "documented": "4214H",
   "name": "Block 2 derivative time",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 16917,
   "documented": "4215H",
   "name": "Block 2 ARW",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 16918,
   "documented": "4216H",
   "name": "Block 2 OUT2 proportional band",
   "description": "Decimal point ignored.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 17170,
   "documented": "4312H",
   "name": "Block 3 OUT1 proportional band",
   "description": "Decimal point ignored.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 17171,
   "documented": "4313H",
   "name": "Block 3 integral time",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 17172,
   "documented": "4314H",
   "name": "Block 3 derivative time",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 17173,
   "documented": "4315H",
   "name": "Block 3 ARW",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 17174,
   "documented": "4316H",
   "name": "Block 3 OUT2 proportional band",
   "description": "Decimal point ignored.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 17426,
   "documented": "4412H",
   "name": "Block 4 OUT1 proportional band",
   "description": "Decimal point ignored.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 17427,
   "documented": "4413H",
   "name": "Block 4 integral time",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 17428,
   "documented": "4414H",
   "name": "Block 4 derivative time",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 17429,
   "documented": "4415H",
   "name": "Block 4 ARW",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 17430,
   "documented": "4416H",
   "name": "Block 4 OUT2 proportional band",
   "description": "Decimal point ignored.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 17682,
   "documented": "4512H",
   "name": "Block 5 OUT1 proportional band",
   "description": "Decimal point ignored.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 17683,
   "documented": "4513H",
   "name": "Block 5 integral time",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 17684,
   "documented": "4514H",
   "name": "Block 5 derivative time",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 17685,
   "documented": "4515H",
   "name": "Block 5 ARW",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 17686,
   "documented": "4516H",
   "name": "Block 5 OUT2 proportional band",
   "description": "Decimal point ignored.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 17938,
   "documented": "4612H",
   "name": "Block 6 OUT1 proportional band",
   "description": "Decimal point ignored.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 17939,
   "documented": "4613H",
   "name": "Block 6 integral time",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 17940,
   "documented": "4614H",
   "name": "Block 6 derivative time",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 17941,
   "documented": "4615H",
   "name": "Block 6 ARW",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 17942,
   "documented": "4616H",
   "name": "Block 6 OUT2 proportional band",
   "description": "Decimal point ignored.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 18194,
   "documented": "4712H",
   "name": "Block 7 OUT1 proportional band",
   "description": "Decimal point ignored.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 18195,
   "documented": "4713H",
   "name": "Block 7 integral time",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 18196,
   "documented": "4714H",
   "name": "Block 7 derivative time",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 18197,
   "documented": "4715H",
   "name": "Block 7 ARW",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 18198,
   "documented": "4716H",
   "name": "Block 7 OUT2 proportional band",
   "description": "Decimal point ignored.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 18450,
   "documented": "4812H",
   "name": "Block 8 OUT1 proportional band",
   "description": "Decimal point ignored.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 18451,
   "documented": "4813H",
   "name": "Block 8 integral time",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 18452,
   "documented": "4814H",
   "name": "Block 8 derivative time",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 18453,
   "documented": "4815H",
   "name": "Block 8 ARW",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 18454,
   "documented": "4816H",
   "name": "Block 8 OUT2 proportional band",
   "description": "Decimal point ignored.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 18706,
   "documented": "4912H",
   "name": "Block 9 OUT1 proportional band",
   "description": "Decimal point ignored.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 18707,
   "documented": "4913H",
   "name": "Block 9 integral time",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 18708,
   "documented": "4914H",
   "name": "Block 9 derivative time",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 18709,
   "documented": "4915H",
   "name": "Block 9 ARW",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 18710,
   "documented": "4916H",
   "name": "Block 9 OUT2 proportional band",
   "description": "Decimal point ignored.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 18962,
   "documented": "4A12H",
   "name": "Block 10 OUT1 proportional band",
   "description": "Decimal point ignored.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 18963,
   "documented": "4A13H",
   "name": "Block 10 integral time",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 18964,
   "documented": "4A14H",
   "name": "Block 10 derivative time",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 18965,
   "documented": "4A15H",
   "name": "Block 10 ARW",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 18966,
   "documented": "4A16H",
   "name": "Block 10 OUT2 proportional band",
   "description": "Decimal point ignored.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 20736,
   "documented": "5100H",
   "name": "P1 wait value",
   "description": "Raw integer; apply decimal point place (7003H).",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 20737,
   "documented": "5101H",
   "name": "P1 step 1 wait function",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Disabled",
    "1": "Enabled"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 20738,
   "documented": "5102H",
   "name": "P1 step 2 wait function",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Disabled",
    "1": "Enabled"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 20739,
   "documented": "5103H",
   "name": "P1 step 3 wait function",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Disabled",
    "1": "Enabled"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 20740,
   "documented": "5104H",
   "name": "P1 step 4 wait function",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Disabled",
    "1": "Enabled"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 20741,
   "documented": "5105H",
   "name": "P1 step 5 wait function",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Disabled",
    "1": "Enabled"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 20742,
   "documented": "5106H",
   "name": "P1 step 6 wait function",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Disabled",
    "1": "Enabled"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 20743,
   "documented": "5107H",
   "name": "P1 step 7 wait function",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Disabled",
    "1": "Enabled"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 20744,
   "documented": "5108H",
   "name": "P1 step 8 wait function",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Disabled",
    "1": "Enabled"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 20745,
   "documented": "5109H",
   "name": "P1 step 9 wait function",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Disabled",
    "1": "Enabled"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 20746,
   "documented": "510AH",
   "name": "P1 step 10 wait function",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Disabled",
    "1": "Enabled"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 20992,
   "documented": "5200H",
   "name": "P2 wait value",
   "description": "Raw integer; apply decimal point place (7003H).",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 20993,
   "documented": "5201H",
   "name": "P2 step 1 wait function",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Disabled",
    "1": "Enabled"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 20994,
   "documented": "5202H",
   "name": "P2 step 2 wait function",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Disabled",
    "1": "Enabled"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 20995,
   "documented": "5203H",
   "name": "P2 step 3 wait function",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Disabled",
    "1": "Enabled"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 20996,
   "documented": "5204H",
   "name": "P2 step 4 wait function",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Disabled",
    "1": "Enabled"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 20997,
   "documented": "5205H",
   "name": "P2 step 5 wait function",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Disabled",
    "1": "Enabled"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 20998,
   "documented": "5206H",
   "name": "P2 step 6 wait function",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Disabled",
    "1": "Enabled"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 20999,
   "documented": "5207H",
   "name": "P2 step 7 wait function",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Disabled",
    "1": "Enabled"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 21000,
   "documented": "5208H",
   "name": "P2 step 8 wait function",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Disabled",
    "1": "Enabled"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 21001,
   "documented": "5209H",
   "name": "P2 step 9 wait function",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Disabled",
    "1": "Enabled"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 21002,
   "documented": "520AH",
   "name": "P2 step 10 wait function",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Disabled",
    "1": "Enabled"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 21248,
   "documented": "5300H",
   "name": "P3 wait value",
   "description": "Raw integer; apply decimal point place (7003H).",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 21249,
   "documented": "5301H",
   "name": "P3 step 1 wait function",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Disabled",
    "1": "Enabled"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 21250,
   "documented": "5302H",
   "name": "P3 step 2 wait function",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Disabled",
    "1": "Enabled"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 21251,
   "documented": "5303H",
   "name": "P3 step 3 wait function",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Disabled",
    "1": "Enabled"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 21252,
   "documented": "5304H",
   "name": "P3 step 4 wait function",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Disabled",
    "1": "Enabled"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 21253,
   "documented": "5305H",
   "name": "P3 step 5 wait function",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Disabled",
    "1": "Enabled"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 21254,
   "documented": "5306H",
   "name": "P3 step 6 wait function",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Disabled",
    "1": "Enabled"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 21255,
   "documented": "5307H",
   "name": "P3 step 7 wait function",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Disabled",
    "1": "Enabled"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 21256,
   "documented": "5308H",
   "name": "P3 step 8 wait function",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Disabled",
    "1": "Enabled"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 21257,
   "documented": "5309H",
   "name": "P3 step 9 wait function",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Disabled",
    "1": "Enabled"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 21258,
   "documented": "530AH",
   "name": "P3 step 10 wait function",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Disabled",
    "1": "Enabled"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 21504,
   "documented": "5400H",
   "name": "P4 wait value",
   "description": "Raw integer; apply decimal point place (7003H).",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 21505,
   "documented": "5401H",
   "name": "P4 step 1 wait function",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Disabled",
    "1": "Enabled"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 21506,
   "documented": "5402H",
   "name": "P4 step 2 wait function",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Disabled",
    "1": "Enabled"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 21507,
   "documented": "5403H",
   "name": "P4 step 3 wait function",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Disabled",
    "1": "Enabled"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 21508,
   "documented": "5404H",
   "name": "P4 step 4 wait function",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Disabled",
    "1": "Enabled"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 21509,
   "documented": "5405H",
   "name": "P4 step 5 wait function",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Disabled",
    "1": "Enabled"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 21510,
   "documented": "5406H",
   "name": "P4 step 6 wait function",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Disabled",
    "1": "Enabled"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 21511,
   "documented": "5407H",
   "name": "P4 step 7 wait function",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Disabled",
    "1": "Enabled"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 21512,
   "documented": "5408H",
   "name": "P4 step 8 wait function",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Disabled",
    "1": "Enabled"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 21513,
   "documented": "5409H",
   "name": "P4 step 9 wait function",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Disabled",
    "1": "Enabled"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 21514,
   "documented": "540AH",
   "name": "P4 step 10 wait function",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Disabled",
    "1": "Enabled"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 21760,
   "documented": "5500H",
   "name": "P5 wait value",
   "description": "Raw integer; apply decimal point place (7003H).",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 21761,
   "documented": "5501H",
   "name": "P5 step 1 wait function",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Disabled",
    "1": "Enabled"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 21762,
   "documented": "5502H",
   "name": "P5 step 2 wait function",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Disabled",
    "1": "Enabled"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 21763,
   "documented": "5503H",
   "name": "P5 step 3 wait function",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Disabled",
    "1": "Enabled"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 21764,
   "documented": "5504H",
   "name": "P5 step 4 wait function",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Disabled",
    "1": "Enabled"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 21765,
   "documented": "5505H",
   "name": "P5 step 5 wait function",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Disabled",
    "1": "Enabled"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 21766,
   "documented": "5506H",
   "name": "P5 step 6 wait function",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Disabled",
    "1": "Enabled"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 21767,
   "documented": "5507H",
   "name": "P5 step 7 wait function",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Disabled",
    "1": "Enabled"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 21768,
   "documented": "5508H",
   "name": "P5 step 8 wait function",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Disabled",
    "1": "Enabled"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 21769,
   "documented": "5509H",
   "name": "P5 step 9 wait function",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Disabled",
    "1": "Enabled"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 21770,
   "documented": "550AH",
   "name": "P5 step 10 wait function",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Disabled",
    "1": "Enabled"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 22016,
   "documented": "5600H",
   "name": "P6 wait value",
   "description": "Raw integer; apply decimal point place (7003H).",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 22017,
   "documented": "5601H",
   "name": "P6 step 1 wait function",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Disabled",
    "1": "Enabled"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 22018,
   "documented": "5602H",
   "name": "P6 step 2 wait function",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Disabled",
    "1": "Enabled"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 22019,
   "documented": "5603H",
   "name": "P6 step 3 wait function",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Disabled",
    "1": "Enabled"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 22020,
   "documented": "5604H",
   "name": "P6 step 4 wait function",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Disabled",
    "1": "Enabled"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 22021,
   "documented": "5605H",
   "name": "P6 step 5 wait function",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Disabled",
    "1": "Enabled"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 22022,
   "documented": "5606H",
   "name": "P6 step 6 wait function",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Disabled",
    "1": "Enabled"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 22023,
   "documented": "5607H",
   "name": "P6 step 7 wait function",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Disabled",
    "1": "Enabled"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 22024,
   "documented": "5608H",
   "name": "P6 step 8 wait function",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Disabled",
    "1": "Enabled"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 22025,
   "documented": "5609H",
   "name": "P6 step 9 wait function",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Disabled",
    "1": "Enabled"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 22026,
   "documented": "560AH",
   "name": "P6 step 10 wait function",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Disabled",
    "1": "Enabled"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 22272,
   "documented": "5700H",
   "name": "P7 wait value",
   "description": "Raw integer; apply decimal point place (7003H).",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 22273,
   "documented": "5701H",
   "name": "P7 step 1 wait function",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Disabled",
    "1": "Enabled"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 22274,
   "documented": "5702H",
   "name": "P7 step 2 wait function",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Disabled",
    "1": "Enabled"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 22275,
   "documented": "5703H",
   "name": "P7 step 3 wait function",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Disabled",
    "1": "Enabled"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 22276,
   "documented": "5704H",
   "name": "P7 step 4 wait function",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Disabled",
    "1": "Enabled"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 22277,
   "documented": "5705H",
   "name": "P7 step 5 wait function",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Disabled",
    "1": "Enabled"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 22278,
   "documented": "5706H",
   "name": "P7 step 6 wait function",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Disabled",
    "1": "Enabled"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 22279,
   "documented": "5707H",
   "name": "P7 step 7 wait function",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Disabled",
    "1": "Enabled"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 22280,
   "documented": "5708H",
   "name": "P7 step 8 wait function",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Disabled",
    "1": "Enabled"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 22281,
   "documented": "5709H",
   "name": "P7 step 9 wait function",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Disabled",
    "1": "Enabled"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 22282,
   "documented": "570AH",
   "name": "P7 step 10 wait function",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Disabled",
    "1": "Enabled"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 22528,
   "documented": "5800H",
   "name": "P8 wait value",
   "description": "Raw integer; apply decimal point place (7003H).",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 22529,
   "documented": "5801H",
   "name": "P8 step 1 wait function",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Disabled",
    "1": "Enabled"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 22530,
   "documented": "5802H",
   "name": "P8 step 2 wait function",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Disabled",
    "1": "Enabled"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 22531,
   "documented": "5803H",
   "name": "P8 step 3 wait function",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Disabled",
    "1": "Enabled"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 22532,
   "documented": "5804H",
   "name": "P8 step 4 wait function",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Disabled",
    "1": "Enabled"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 22533,
   "documented": "5805H",
   "name": "P8 step 5 wait function",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Disabled",
    "1": "Enabled"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 22534,
   "documented": "5806H",
   "name": "P8 step 6 wait function",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Disabled",
    "1": "Enabled"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 22535,
   "documented": "5807H",
   "name": "P8 step 7 wait function",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Disabled",
    "1": "Enabled"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 22536,
   "documented": "5808H",
   "name": "P8 step 8 wait function",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Disabled",
    "1": "Enabled"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 22537,
   "documented": "5809H",
   "name": "P8 step 9 wait function",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Disabled",
    "1": "Enabled"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 22538,
   "documented": "580AH",
   "name": "P8 step 10 wait function",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Disabled",
    "1": "Enabled"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 22784,
   "documented": "5900H",
   "name": "P9 wait value",
   "description": "Raw integer; apply decimal point place (7003H).",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 22785,
   "documented": "5901H",
   "name": "P9 step 1 wait function",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Disabled",
    "1": "Enabled"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 22786,
   "documented": "5902H",
   "name": "P9 step 2 wait function",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Disabled",
    "1": "Enabled"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 22787,
   "documented": "5903H",
   "name": "P9 step 3 wait function",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Disabled",
    "1": "Enabled"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 22788,
   "documented": "5904H",
   "name": "P9 step 4 wait function",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Disabled",
    "1": "Enabled"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 22789,
   "documented": "5905H",
   "name": "P9 step 5 wait function",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Disabled",
    "1": "Enabled"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 22790,
   "documented": "5906H",
   "name": "P9 step 6 wait function",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Disabled",
    "1": "Enabled"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 22791,
   "documented": "5907H",
   "name": "P9 step 7 wait function",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Disabled",
    "1": "Enabled"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 22792,
   "documented": "5908H",
   "name": "P9 step 8 wait function",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Disabled",
    "1": "Enabled"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 22793,
   "documented": "5909H",
   "name": "P9 step 9 wait function",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Disabled",
    "1": "Enabled"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 22794,
   "documented": "590AH",
   "name": "P9 step 10 wait function",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Disabled",
    "1": "Enabled"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 23040,
   "documented": "5A00H",
   "name": "P10 wait value",
   "description": "Raw integer; apply decimal point place (7003H).",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 23041,
   "documented": "5A01H",
   "name": "P10 step 1 wait function",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Disabled",
    "1": "Enabled"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 23042,
   "documented": "5A02H",
   "name": "P10 step 2 wait function",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Disabled",
    "1": "Enabled"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 23043,
   "documented": "5A03H",
   "name": "P10 step 3 wait function",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Disabled",
    "1": "Enabled"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 23044,
   "documented": "5A04H",
   "name": "P10 step 4 wait function",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Disabled",
    "1": "Enabled"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 23045,
   "documented": "5A05H",
   "name": "P10 step 5 wait function",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Disabled",
    "1": "Enabled"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 23046,
   "documented": "5A06H",
   "name": "P10 step 6 wait function",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Disabled",
    "1": "Enabled"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 23047,
   "documented": "5A07H",
   "name": "P10 step 7 wait function",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Disabled",
    "1": "Enabled"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 23048,
   "documented": "5A08H",
   "name": "P10 step 8 wait function",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Disabled",
    "1": "Enabled"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 23049,
   "documented": "5A09H",
   "name": "P10 step 9 wait function",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Disabled",
    "1": "Enabled"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 23050,
   "documented": "5A0AH",
   "name": "P10 step 10 wait function",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Disabled",
    "1": "Enabled"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 24576,
   "documented": "6000H",
   "name": "Set value lock",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Unlock",
    "1": "Lock 1",
    "2": "Lock 2",
    "3": "Lock 3",
    "4": "Lock 4",
    "5": "Lock 5"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 24577,
   "documented": "6001H",
   "name": "Changeable in set value lock",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Step SV + step time",
    "1": "Step SV + step time + EV alarm value"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 24578,
   "documented": "6002H",
   "name": "Sensor correction coefficient",
   "description": "Decimal point ignored.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 24579,
   "documented": "6003H",
   "name": "Sensor correction",
   "description": "Raw integer; apply decimal point place (7003H).",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 24580,
   "documented": "6004H",
   "name": "PV filter time constant",
   "description": "Decimal point ignored.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 24581,
   "documented": "6005H",
   "name": "Response delay time",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "ms",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 24582,
   "documented": "6006H",
   "name": "SVTC bias",
   "description": "Raw integer; apply decimal point place (7003H).",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 28672,
   "documented": "7000H",
   "name": "Input type",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "K -200 to 1370 C",
    "1": "K -200.0 to 400.0 C",
    "2": "J -200 to 1000 C",
    "3": "R 0 to 1760 C",
    "4": "S 0 to 1760 C",
    "5": "B 0 to 1820 C",
    "6": "E -200 to 800 C",
    "7": "T -200.0 to 400.0 C",
    "8": "N -200 to 1300 C",
    "9": "PL-II 0 to 1390 C",
    "10": "C (W/Re5-26) 0 to 2315 C",
    "11": "Pt100 -200.0 to 850.0 C",
    "12": "JPt100 -200.0 to 500.0 C",
    "13": "Pt100 -200 to 850 C",
    "14": "JPt100 -200 to 500 C",
    "15": "K -328 to 2498 F",
    "16": "K -328.0 to 752.0 F",
    "17": "J -328 to 1832 F",
    "18": "R 32 to 3200 F",
    "19": "S 32 to 3200 F",
    "20": "B 32 to 3308 F",
    "21": "E -328 to 1472 F",
    "22": "T -328.0 to 752.0 F",
    "23": "N -328 to 2372 F",
    "24": "PL-II 32 to 2534 F",
    "25": "C (W/Re5-26) 32 to 4199 F",
    "26": "Pt100 -328.0 to 1562.0 F",
    "27": "JPt100 -328.0 to 932.0 F",
    "28": "Pt100 -328 to 1562 F",
    "29": "JPt100 -328 to 932 F",
    "30": "4 to 20 mA (-2000 to 10000)",
    "31": "0 to 20 mA (-2000 to 10000)",
    "32": "0 to 1 V (-2000 to 10000)",
    "33": "0 to 5 V (-2000 to 10000)",
    "34": "1 to 5 V (-2000 to 10000)",
    "35": "0 to 10 V (-2000 to 10000)"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 28673,
   "documented": "7001H",
   "name": "Scaling high limit",
   "description": "Raw integer; apply decimal point place (7003H).",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 28674,
   "documented": "7002H",
   "name": "Scaling low limit",
   "description": "Raw integer; apply decimal point place (7003H).",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 28675,
   "documented": "7003H",
   "name": "Decimal point place",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "No decimal point",
    "1": "1 digit",
    "2": "2 digits",
    "3": "3 digits"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 28676,
   "documented": "7004H",
   "name": "Event output EV1 allocation",
   "description": "Changing it clears this event's alarm settings.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "No event",
    "1": "High limit alarm",
    "2": "Low limit alarm",
    "3": "High/Low limits alarm",
    "4": "High/Low limits independent alarm",
    "5": "High/Low limit range alarm",
    "6": "High/Low limit range independent alarm",
    "7": "Process high alarm",
    "8": "Process low alarm",
    "9": "High limit with standby alarm",
    "10": "Low limit with standby alarm",
    "11": "High/Low limits with standby alarm",
    "12": "High/Low limits with standby independent alarm",
    "13": "Heater burnout alarm output",
    "14": "Loop break alarm output",
    "15": "Time signal output",
    "16": "Output during AT",
    "17": "Pattern end output",
    "18": "Output by communication command (8004H)",
    "19": "RUN output"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 28677,
   "documented": "7005H",
   "name": "EV1 alarm value 0 enabled",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Disabled",
    "1": "Enabled"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 28678,
   "documented": "7006H",
   "name": "EV1 alarm hysteresis",
   "description": "Raw integer; apply decimal point place (7003H).",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 28679,
   "documented": "7007H",
   "name": "EV1 alarm delay time",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 28680,
   "documented": "7008H",
   "name": "EV1 alarm energized/de-energized",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Energized",
    "1": "De-energized"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 28681,
   "documented": "7009H",
   "name": "Event output EV2 allocation",
   "description": "Changing it clears this event's alarm settings.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "No event",
    "1": "High limit alarm",
    "2": "Low limit alarm",
    "3": "High/Low limits alarm",
    "4": "High/Low limits independent alarm",
    "5": "High/Low limit range alarm",
    "6": "High/Low limit range independent alarm",
    "7": "Process high alarm",
    "8": "Process low alarm",
    "9": "High limit with standby alarm",
    "10": "Low limit with standby alarm",
    "11": "High/Low limits with standby alarm",
    "12": "High/Low limits with standby independent alarm",
    "13": "Heater burnout alarm output",
    "14": "Loop break alarm output",
    "15": "Time signal output",
    "16": "Output during AT",
    "17": "Pattern end output",
    "18": "Output by communication command (8004H)",
    "19": "RUN output",
    "20": "Heating/Cooling control output"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 28682,
   "documented": "700AH",
   "name": "EV2 alarm value 0 enabled",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Disabled",
    "1": "Enabled"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 28683,
   "documented": "700BH",
   "name": "EV2 alarm hysteresis",
   "description": "Raw integer; apply decimal point place (7003H).",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 28684,
   "documented": "700CH",
   "name": "EV2 alarm delay time",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 28685,
   "documented": "700DH",
   "name": "EV2 alarm energized/de-energized",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Energized",
    "1": "De-energized"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 28686,
   "documented": "700EH",
   "name": "Event output EV3 allocation",
   "description": "Changing it clears this event's alarm settings.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "No event",
    "1": "High limit alarm",
    "2": "Low limit alarm",
    "3": "High/Low limits alarm",
    "4": "High/Low limits independent alarm",
    "5": "High/Low limit range alarm",
    "6": "High/Low limit range independent alarm",
    "7": "Process high alarm",
    "8": "Process low alarm",
    "9": "High limit with standby alarm",
    "10": "Low limit with standby alarm",
    "11": "High/Low limits with standby alarm",
    "12": "High/Low limits with standby independent alarm",
    "13": "Heater burnout alarm output",
    "14": "Loop break alarm output",
    "15": "Time signal output",
    "16": "Output during AT",
    "17": "Pattern end output",
    "18": "Output by communication command (8004H)",
    "19": "RUN output"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 28687,
   "documented": "700FH",
   "name": "EV3 alarm value 0 enabled",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Disabled",
    "1": "Enabled"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 28688,
   "documented": "7010H",
   "name": "EV3 alarm hysteresis",
   "description": "Raw integer; apply decimal point place (7003H).",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 28689,
   "documented": "7011H",
   "name": "EV3 alarm delay time",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 28690,
   "documented": "7012H",
   "name": "EV3 alarm energized/de-energized",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Energized",
    "1": "De-energized"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 28691,
   "documented": "7013H",
   "name": "Event input DI1 allocation",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "No event",
    "1": "Pattern number selection",
    "2": "Direct/Reverse action",
    "3": "Program control RUN/STOP",
    "4": "Program control holding/not holding",
    "5": "Program control advance function"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 28692,
   "documented": "7014H",
   "name": "Event input DI2 allocation",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "No event",
    "1": "Pattern number selection",
    "2": "Direct/Reverse action",
    "3": "Program control RUN/STOP",
    "4": "Program control holding/not holding",
    "5": "Program control advance function"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 28693,
   "documented": "7015H",
   "name": "Transmission output",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "PV transmission",
    "1": "SV transmission",
    "2": "MV transmission"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 28694,
   "documented": "7016H",
   "name": "Transmission output high limit",
   "description": "Decimal point ignored.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 28695,
   "documented": "7017H",
   "name": "Transmission output low limit",
   "description": "Decimal point ignored.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 28696,
   "documented": "7018H",
   "name": "Step time unit",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Hours:Minutes",
    "1": "Minutes:Seconds"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 28697,
   "documented": "7019H",
   "name": "Power restore action",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Stop",
    "1": "Continue (resume)",
    "2": "Suspend (hold)"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 28698,
   "documented": "701AH",
   "name": "Step SV when program control starts",
   "description": "Raw integer; apply decimal point place (7003H).",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 28699,
   "documented": "701BH",
   "name": "Program control start type",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "PV start",
    "1": "PVR start",
    "2": "SV start"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 28700,
   "documented": "701CH",
   "name": "Pattern end output time",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 28701,
   "documented": "701DH",
   "name": "AT bias",
   "description": "Raw integer; apply decimal point place (7003H).",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 28702,
   "documented": "701EH",
   "name": "Output status on input error",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Output OFF",
    "1": "Output ON"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 28703,
   "documented": "701FH",
   "name": "Indication time",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "s",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 28704,
   "documented": "7020H",
   "name": "Error indication",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Disabled",
    "1": "Enabled"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 32768,
   "documented": "8000H",
   "name": "Pattern number for operation",
   "description": "Writable only in program STOP and when DI selects pattern 1.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "1": "Pattern 1",
    "2": "Pattern 2",
    "3": "Pattern 3",
    "4": "Pattern 4",
    "5": "Pattern 5",
    "6": "Pattern 6",
    "7": "Pattern 7",
    "8": "Pattern 8",
    "9": "Pattern 9",
    "10": "Pattern 10"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 32769,
   "documented": "8001H",
   "name": "Program control RUN/STOP",
   "description": "Write-only (06/10H).",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "W",
   "values": {
    "0": "STOP",
    "1": "RUN (cancels HOLD)"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 32770,
   "documented": "8002H",
   "name": "Program control HOLD",
   "description": "Write-only; rejected in STOP.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "W",
   "values": {
    "1": "HOLD"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 32771,
   "documented": "8003H",
   "name": "Program control ADVANCE",
   "description": "Write-only; rejected in STOP.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "W",
   "values": {
    "1": "ADVANCE"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 32772,
   "documented": "8004H",
   "name": "Output by communication",
   "description": "Drives EV outputs allocated to 'output by communication'.",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "W",
   "values": null,
   "bits": {
    "0": "EV1 output",
    "1": "EV2 output",
    "2": "EV3 output"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 32773,
   "documented": "8005H",
   "name": "Key operation change flag clearing",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "W",
   "values": {
    "1": "Clear flag"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 36864,
   "documented": "9000H",
   "name": "PV",
   "description": "Process value. Raw integer; apply decimal point place (7003H).",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 36865,
   "documented": "9001H",
   "name": "OUT1 MV",
   "description": "Decimal point ignored.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 36866,
   "documented": "9002H",
   "name": "OUT2 MV",
   "description": "Decimal point ignored.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 36867,
   "documented": "9003H",
   "name": "Current step SV",
   "description": "Raw integer; apply decimal point place (7003H).",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 36868,
   "documented": "9004H",
   "name": "Current step remaining time",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 36869,
   "documented": "9005H",
   "name": "Current pattern and step",
   "description": "Lowest hex digit = pattern, next hex digit = step (0 when stopped).",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 36870,
   "documented": "9006H",
   "name": "Current number of repetitions",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 36871,
   "documented": "9007H",
   "name": "Pattern selected by event input",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 36872,
   "documented": "9008H",
   "name": "CT1 current value",
   "description": "Decimal point ignored.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 36873,
   "documented": "9009H",
   "name": "CT2 current value",
   "description": "Decimal point ignored.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 36874,
   "documented": "900AH",
   "name": "Status flag",
   "description": "",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "0": "OUT1 on",
    "1": "OUT2 on",
    "2": "EV1 output on",
    "3": "EV2 output on",
    "4": "EV3 output on",
    "6": "Loop break alarm output",
    "7": "Overscale",
    "8": "Underscale",
    "9": "Heater burnout alarm output",
    "15": "Changed by keypad"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 36875,
   "documented": "900BH",
   "name": "Current unit status",
   "description": "",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "0": "Program control (fixed)",
    "1": "AT performing",
    "2": "Program control RUN",
    "3": "HOLD",
    "4": "WAIT",
    "5": "Pattern end output on"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 36876,
   "documented": "900CH",
   "name": "Error status flag 1",
   "description": "",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "0": "Error 01",
    "1": "Error 02",
    "4": "Error 05",
    "5": "Error 06",
    "6": "Error 07",
    "9": "Error 10"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 36877,
   "documented": "900DH",
   "name": "Error status flag 2",
   "description": "",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "3": "Error 20"
   },
   "offset": 0
  }
 ],
 "page": "https://easymodbus.com/modbus-register-maps/shinko-technos/pcb1",
 "address_note": "address = 0-based Modbus wire (PDU) address; documented = as printed in the source.",
 "note": "Re-typed from the manufacturer's public documentation (see source) and verified against it. Registers vary by firmware and options; verify against the live device before writing."
}