 "manufacturer": "Shinko Technos",
 "manufacturer_slug": "shinko-technos",
 "model": "SGxL signal conditioner series (Modbus RTU)",
 "model_slug": "sgxl",
 "short_model": "SGxL",
 "aliases": [
  "SGBL",
  "SGCL",
  "SGDL",
  "SGIL",
  "SGLL",
  "SGML",
  "SGPL",
  "SGRL",
  "SGSL",
  "SGTL",
  "SGUL"
 ],
 "equipment_type": "Sensor (signal conditioner)",
 "applies_to": "Shinko SGxL signal conditioners (SGBL, SGCL, SGDL, SGIL, SGLL, SGML, SGPL, SGRL, SGSL, SGTL, SGUL); SGFL and SGJL are not covered. Manual No.SGxL1CE3.",
 "summary": "The SGxL family are signal conditioners that turn DC, thermocouple or RTD inputs into analog output signals, with an RS-485 Modbus RTU port. Every item is a signed 16-bit register. The map covers input and output range settings, filtering, manual output, communication settings, the measured input, output value and the status word.",
 "transport": [
  "RTU"
 ],
 "defaults": {
  "unit_id": 1,
  "baud": 38400,
  "parity": "Odd",
  "data_bits": 8,
  "stop_bits": 1,
  "tcp_port": null
 },
 "addressing": {
  "convention": "hex 0-based",
  "note": "Registers are listed as hex data items (0001H) that go into the request unchanged. The manual adds that the matching Modicon holding-register number is the item in decimal plus 40001 (0001H = 40002)."
 },
 "default_word_order": null,
 "firmware": null,
 "source": {
  "title": "Communication Instruction Manual SGxL",
  "doc_number": "No. SGxL1CE3",
  "revision_date": "2022-03",
  "url": "https://shinko-technos.co.jp/e/manual/english/SGxL1CE3.pdf",
  "pages": "Command table pp. 15-20; data notes p. 21; communication settings pp. 3-4"
 },
 "notes": [
  "Output 2 items (0040H-0050H) are left out: the manual marks them as console-software data that cannot be used.",
  "Input type codes are not listed here because the code table changes with model and input group (pp. 15-16).",
  "0001H-0002H accept single-register function 03/06 only; 0010H-0084H also accept function 10H; read-only items accept 03 or 04.",
  "All data are 16-bit two's complement and values with a decimal point are sent without it.",
  "Multi-Display character registers 0070H-0077H are omitted (front-panel label characters)."
 ],
 "integration": {
  "summary": "Wire RS-485, set the instrument number on the keypad (default 1, 38400 bps, 8 bits odd parity), then read input value 00B0H, output value 00B1H and status 00B2H.",
  "minimum_registers": [
   {
    "table": "holding_register",
    "address": 176,
    "why": "Measured input value"
   },
   {
    "table": "holding_register",
    "address": 177,
    "why": "Output 1 value"
   },
   {
    "table": "holding_register",
    "address": 178,
    "why": "Over/underscale and mode status"
   },
   {
    "table": "holding_register",
    "address": 19,
    "why": "Input decimal point"
   },
   {
    "table": "holding_register",
    "address": 20,
    "why": "Input value at 0% output"
   },
   {
    "table": "holding_register",
    "address": 21,
    "why": "Input value at 100% output"
   }
  ],
  "enable": "Modbus RTU is always on. Set instrument number, speed, data bit/parity, stop bit and response delay in Communication setting mode, then choose Save.",
  "watchdog": null,
  "quirks": [
   "Serial RS-485 and the console (USB tool cable) cannot be used together; unplug the tool cable for Modbus.",
   "Writing communication settings over the bus takes effect on the unit; update the master to match."
  ],
  "setup": [
   "Factory defaults: instrument number 1, 38400 bps, 8 data bits, odd parity, 1 stop bit, 10 ms response delay.",
   "Speeds 9600, 19200 or 38400 bps; up to 31 units on one line."
  ],
  "gotchas": [
   "Exception 18 (12H) is returned while the keypad is in setting mode.",
   "Non-volatile memory is good for about one million writes; 0002H is the exception and is not stored."
  ]
 },
 "registers": [
  {
   "table": "holding_register",
   "address": 1,
   "documented": "0001H",
   "name": "Default Display/Manual mode",
   "description": "Manual mode needs Auto/Manual (0064H) set to Manual.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Default Display",
    "1": "Manual mode"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2,
   "documented": "0002H",
   "name": "Output 1 output value",
   "description": "Manual output value; not stored in non-volatile memory.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 16,
   "documented": "0010H",
   "name": "Input group",
   "description": "Model-dependent; reads 0 where not available.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "DC signal input",
    "1": "Thermocouple input",
    "2": "RTD input"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 17,
   "documented": "0011H",
   "name": "Input type",
   "description": "Code list depends on model and input group; see manual p. 15-16.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 18,
   "documented": "0012H",
   "name": "Input unit",
   "description": "Model-dependent; reads 0 where not available.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "°C",
    "1": "°F"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 19,
   "documented": "0013H",
   "name": "Decimal point place",
   "description": "TC/RTD models allow only 0 or 1.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "No decimal point",
    "1": "1 digit",
    "2": "2 digits",
    "3": "3 digits"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 20,
   "documented": "0014H",
   "name": "Output 0% value",
   "description": "Input value giving 0% output; decimal point ignored.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 21,
   "documented": "0015H",
   "name": "Output 100% value",
   "description": "Input value giving 100% output; decimal point ignored.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 22,
   "documented": "0016H",
   "name": "Indication unit",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "No unit",
    "1": "%",
    "2": "mA",
    "3": "V",
    "4": "°C"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 23,
   "documented": "0017H",
   "name": "Square root function",
   "description": "Model-dependent; reads 0 where not available.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Disabled",
    "1": "Enabled"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 24,
   "documented": "0018H",
   "name": "Low level cutoff",
   "description": "Model-dependent; reads 0 where not available.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 32,
   "documented": "0020H",
   "name": "Output 1 type",
   "description": "Codes for all models except SGI. On SGI: 0 = 4-20 mA, 1 = 1-5 V.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "4 to 20 mA",
    "1": "0 to 20 mA",
    "2": "0 to 16 mA",
    "3": "2 to 10 mA",
    "4": "0 to 10 mA",
    "5": "0 to 10 mV",
    "6": "0 to 100 mV",
    "7": "0 to 1 V",
    "8": "0 to 5 V",
    "9": "1 to 5 V",
    "10": "0 to 10 V",
    "11": "-5 to 5 V"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 33,
   "documented": "0021H",
   "name": "Output 1 decimal point place",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "No decimal point",
    "1": "1 digit",
    "2": "2 digits",
    "3": "3 digits"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 34,
   "documented": "0022H",
   "name": "Output 1 indication at 0%",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 35,
   "documented": "0023H",
   "name": "Output 1 indication at 100%",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 36,
   "documented": "0024H",
   "name": "Output 1 low limit",
   "description": "Model-dependent; reads 0 where not available.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 37,
   "documented": "0025H",
   "name": "Output 1 high limit",
   "description": "Model-dependent; reads 0 where not available.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 38,
   "documented": "0026H",
   "name": "Output 1 low limit (outside rating)",
   "description": "Model-dependent; reads 0 where not available.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 39,
   "documented": "0027H",
   "name": "Output 1 high limit (outside rating)",
   "description": "Model-dependent; reads 0 where not available.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 40,
   "documented": "0028H",
   "name": "I/O characteristics",
   "description": "Model-dependent; reads 0 where not available.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "V characteristics",
    "1": "Parallel characteristics"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 41,
   "documented": "0029H",
   "name": "Output 1 split value",
   "description": "Model-dependent; reads 0 where not available.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 42,
   "documented": "002AH",
   "name": "Output 1 Normal/Reverse",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Normal",
    "1": "Reverse"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 43,
   "documented": "002BH",
   "name": "Output 1 ratio",
   "description": "Model-dependent; reads 0 where not available.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 44,
   "documented": "002CH",
   "name": "Output 1 bias",
   "description": "Model-dependent; reads 0 where not available.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 45,
   "documented": "002DH",
   "name": "Input point 1",
   "description": "Model-dependent; reads 0 where not available.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 46,
   "documented": "002EH",
   "name": "Output 1 output value 1",
   "description": "Model-dependent; reads 0 where not available.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 47,
   "documented": "002FH",
   "name": "Input point 2",
   "description": "Model-dependent; reads 0 where not available.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 48,
   "documented": "0030H",
   "name": "Output 1 output value 2",
   "description": "Model-dependent; reads 0 where not available.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 96,
   "documented": "0060H",
   "name": "Filter time constant",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 97,
   "documented": "0061H",
   "name": "Sensor correction",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 98,
   "documented": "0062H",
   "name": "Input disconnection status",
   "description": "Burnout direction. Model-dependent; reads 0 where not available.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Overscale",
    "1": "Underscale"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 99,
   "documented": "0063H",
   "name": "Indication time",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 100,
   "documented": "0064H",
   "name": "Auto/Manual",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Auto",
    "1": "Manual"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 101,
   "documented": "0065H",
   "name": "Ratio setting method",
   "description": "Model-dependent; reads 0 where not available.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Ratio setting",
    "1": "Output value setting"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 105,
   "documented": "0069H",
   "name": "Manual mode auto return time",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 128,
   "documented": "0080H",
   "name": "Instrument number",
   "description": "Slave address 1-247. Change the master to match after writing.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 129,
   "documented": "0081H",
   "name": "Communication speed",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "9600 bps",
    "1": "19200 bps",
    "2": "38400 bps"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 130,
   "documented": "0082H",
   "name": "Data bit/Parity",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "8 bits/No parity",
    "1": "8 bits/Even",
    "2": "8 bits/Odd"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 131,
   "documented": "0083H",
   "name": "Stop bit",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "1 bit",
    "1": "2 bits"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 132,
   "documented": "0084H",
   "name": "Response delay time",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "ms",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 160,
   "documented": "00A0H",
   "name": "Key operation change flag clearing",
   "description": "Write-only (function 06); any value other than 1 is rejected.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "W",
   "values": {
    "1": "Clear key operation change flag"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 176,
   "documented": "00B0H",
   "name": "Input value",
   "description": "Measured input; decimal point ignored, apply 0013H.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 177,
   "documented": "00B1H",
   "name": "Output 1 output value",
   "description": "Decimal point ignored, apply 0021H.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 178,
   "documented": "00B2H",
   "name": "Status flag",
   "description": "",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "0": "Input overscale",
    "1": "Input underscale",
    "11": "USB connection",
    "12": "Setting mode (0 = Default Display)",
    "13": "Manual mode (0 = Default Display)",
    "14": "Locked",
    "15": "Changed by key operation"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 208,
   "documented": "00D0H",
   "name": "Software version",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 210,
   "documented": "00D2H",
   "name": "Key operation changed item",
   "description": "Data item last changed on the keypad.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  }
 ],
 "page": "https://easymodbus.com/modbus-register-maps/shinko-technos/sgxl",
 "address_note": "address = 0-based Modbus wire (PDU) address; documented = as printed in the source.",
 "note": "Re-typed from the manufacturer's public documentation (see source) and verified against it. Registers vary by firmware and options; verify against the live device before writing."
}