 "manufacturer": "Siemens",
 "manufacturer_slug": "siemens",
 "model": "QFA3150/MO room humidity and temperature sensor (Modbus RTU)",
 "model_slug": "qfa3150-mo",
 "short_model": "QFA3150/MO",
 "aliases": [
  "QFA3150/MO",
  "S55720-S535"
 ],
 "equipment_type": "Sensor (room humidity / temperature)",
 "applies_to": "Siemens QFA3150/MO room relative humidity and temperature sensor, basic documentation edition a (2021-01).",
 "summary": "The QFA3150/MO is a wall-mounted room sensor for temperature and relative humidity with a Modbus RTU (RS-485) slave port. Readings and settings are 16-bit holding registers. The map covers the two measurements with their reliability flags, the temperature unit, the communication settings and the firmware version.",
 "transport": [
  "RTU"
 ],
 "defaults": {
  "unit_id": 1,
  "baud": null,
  "parity": "Even",
  "data_bits": 8,
  "stop_bits": 1,
  "tcp_port": null
 },
 "addressing": {
  "convention": "1-based",
  "note": "The source states that register numbers count from 1, so register 1 (temperature) is wire address 0."
 },
 "default_word_order": null,
 "firmware": null,
 "source": {
  "title": "QFA3150/MO Room relative humidity and temperature sensor Modbus RTU (RS-485) Basic Documentation",
  "doc_number": "A6V12297475_en--_a",
  "revision_date": "2021-01-20",
  "url": "https://sid.siemens.com/api/khub/documents/wrAPGtzMEtAbUJc00QyHYA/content",
  "pages": "p. 7 (configuration parameters), p. 8 (Modbus registers), pp. 9-11 (DIP switches)"
 },
 "notes": [
  "Only 16-bit registers are published.",
  "Default baud is Auto; default format 1-8-E-1; default address 1.",
  "Registers 764-766 are read-only to the master while DIP2 switch 7 is ON.",
  "Temperature is treated as signed because the published range goes below zero."
 ],
 "registers": [
  {
   "table": "holding_register",
   "address": 0,
   "documented": "1",
   "name": "Temperature value",
   "description": "Signed, hundredths of a degree in the selected unit.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "°C / °F",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1,
   "documented": "2",
   "name": "Temperature reliability",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "No error",
    "1": "Bad reliability / unavailable"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2,
   "documented": "3",
   "name": "Relative humidity value",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 3,
   "documented": "4",
   "name": "Humidity reliability",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "No error",
    "1": "Bad reliability / unavailable"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 400,
   "documented": "401",
   "name": "System unit",
   "description": "Temperature unit.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Celsius",
    "1": "Fahrenheit"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 763,
   "documented": "764",
   "name": "Modbus address",
   "description": "1-247.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 764,
   "documented": "765",
   "name": "Baud rate",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Auto",
    "1": "9600",
    "2": "19200",
    "3": "38400",
    "4": "57600",
    "5": "76800",
    "6": "115200"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 765,
   "documented": "766",
   "name": "Transmission format",
   "description": "Start-data-parity-stop bits.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "1-8-E-1",
    "1": "1-8-O-1",
    "2": "1-8-N-1",
    "3": "1-8-N-2"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1285,
   "documented": "1286",
   "name": "SW version major/minor",
   "description": "Major in high byte, minor in low byte.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1286,
   "documented": "1287",
   "name": "SW version build",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  }
 ],
 "integration": {
  "summary": "With DIP2 switch 7 OFF the sensor answers at address 1, 8E1, auto baud; read holding registers 0-3 with function 03.",
  "minimum_registers": [
   {
    "table": "holding_register",
    "address": 0,
    "why": "Temperature"
   },
   {
    "table": "holding_register",
    "address": 2,
    "why": "Relative humidity"
   },
   {
    "table": "holding_register",
    "address": 1,
    "why": "Temperature reliability"
   },
   {
    "table": "holding_register",
    "address": 3,
    "why": "Humidity reliability"
   }
  ],
  "enable": "DIP2 switch 7 OFF = configure over Modbus (registers 764-766); ON = DIP switch configuration (DIP1 address, DIP2 baud/parity/stop).",
  "watchdog": null,
  "quirks": [
   "Register number minus 1 = wire address.",
   "Temperature follows the unit in register 401."
  ],
  "setup": [
   "Bus termination is set with a jumper."
  ],
  "gotchas": [
   "Invalid DIP address: new communication settings are not applied."
  ]
 },
 "page": "https://easymodbus.com/modbus-register-maps/siemens/qfa3150-mo",
 "address_note": "address = 0-based Modbus wire (PDU) address; documented = as printed in the source.",
 "note": "Re-typed from the manufacturer's public documentation (see source) and verified against it. Registers vary by firmware and options; verify against the live device before writing."
}