 "manufacturer": "Siemens",
 "manufacturer_slug": "siemens",
 "model": "QFM9150/MO and QPM9152/MO duct sensors (Modbus RTU)",
 "model_slug": "qfm9150-mo-qpm9152-mo",
 "short_model": "QFM9150/MO",
 "aliases": [
  "QFM9150/MO",
  "QPM9152/MO",
  "S55720-S584",
  "S55720-S585"
 ],
 "equipment_type": "Sensor (duct humidity / temperature / CO2 / VOC)",
 "applies_to": "Siemens QFM9150/MO duct humidity/temperature sensor and QPM9152/MO duct air quality (CO2, VOC, humidity, temperature) sensor, basic documentation edition a (2022-12).",
 "summary": "These Siemens duct sensors talk Modbus RTU over RS-485 and share one holding-register map. The QFM9150/MO measures temperature and relative humidity; the QPM9152/MO adds CO2, an IAQ index and a VOC value. Each reading has a reliability register next to it. The map covers all published measurement, offset, unit, communication and version registers.",
 "transport": [
  "RTU"
 ],
 "defaults": {
  "unit_id": 1,
  "baud": null,
  "parity": "Even",
  "data_bits": 8,
  "stop_bits": 1,
  "tcp_port": null
 },
 "addressing": {
  "convention": "1-based",
  "note": "The register table prints register numbers and states that numbering starts at 1, so register 1 (temperature) is wire address 0 and register 764 (Modbus address) is wire address 763."
 },
 "default_word_order": null,
 "firmware": null,
 "source": {
  "title": "Duct sensors QFM9150/MO, QPM9152/MO Basic Documentation",
  "doc_number": "A6V13841469_en--_a",
  "revision_date": "2022-12",
  "url": "https://sid.siemens.com/r/A6V13841469",
  "pages": "section Modbus registers; Modbus configuration parameters; DIP switch configuration"
 },
 "notes": [
  "All registers are single 16-bit holding registers; no 32-bit values are published.",
  "CO2, IAQ and VOC registers (5-8, 15-16, 212, 225-227) only carry data on the QPM9152/MO.",
  "Baud rate default is 0 = Auto (the sensor takes the master baud rate). Default format 1-8-E-1.",
  "Registers 764-768 cannot be written by the master while DIP2 switch 7 is ON (DIP-switch configuration mode). Address 246 cannot be set from the master.",
  "Temperature and offset registers are treated as signed because the published ranges go below zero.",
  "Software version example from the source: [2.01.33] = 0x02010021 (major byte, minor byte, then a 16-bit build).",
  "Register 767 is marked reserve and is left out."
 ],
 "registers": [
  {
   "table": "holding_register",
   "address": 0,
   "documented": "1",
   "name": "Temperature value",
   "description": "Signed, hundredths of a degree in the selected unit.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "°C / °F",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1,
   "documented": "2",
   "name": "Temperature reliability",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "No error",
    "1": "Bad reliability / unavailable"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2,
   "documented": "3",
   "name": "Relative humidity value",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 3,
   "documented": "4",
   "name": "Humidity reliability",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "No error",
    "1": "Bad reliability / unavailable"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 4,
   "documented": "5",
   "name": "CO2 value",
   "description": "QPM9152/MO only.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "ppm",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 5,
   "documented": "6",
   "name": "CO2 reliability",
   "description": "QPM9152/MO only.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "No error",
    "1": "Bad reliability / unavailable"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 6,
   "documented": "7",
   "name": "IAQ value",
   "description": "Indoor air quality index, QPM9152/MO only.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 7,
   "documented": "8",
   "name": "IAQ reliability",
   "description": "QPM9152/MO only.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "No error",
    "1": "Bad reliability / unavailable"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 14,
   "documented": "15",
   "name": "VOC value",
   "description": "QPM9152/MO only.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 15,
   "documented": "16",
   "name": "VOC reliability",
   "description": "QPM9152/MO only.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "No error",
    "1": "Bad reliability / unavailable"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 211,
   "documented": "212",
   "name": "VOC sensitivity",
   "description": "QPM9152/MO only.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Slow",
    "1": "Medium",
    "2": "Fast"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 222,
   "documented": "223",
   "name": "Temperature offset",
   "description": "Range -100 to 100.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "°C / °F",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 223,
   "documented": "224",
   "name": "Relative humidity offset",
   "description": "Range -100 to 100.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "%",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 224,
   "documented": "225",
   "name": "CO2 offset",
   "description": "Range -2000 to 2000, QPM9152/MO only.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "ppm",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 225,
   "documented": "226",
   "name": "IAQ offset",
   "description": "Range -100 to 100, QPM9152/MO only.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "%",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 226,
   "documented": "227",
   "name": "VOC pure offset",
   "description": "Range -100 to 100, QPM9152/MO only.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "%",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 400,
   "documented": "401",
   "name": "System unit",
   "description": "Temperature unit for values and offsets.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Celsius",
    "1": "Fahrenheit"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 763,
   "documented": "764",
   "name": "Modbus address",
   "description": "1-247; 246 is reserved for on-event addressing.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 764,
   "documented": "765",
   "name": "Baud rate",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Auto",
    "1": "9600",
    "2": "19200",
    "3": "38400",
    "4": "57600",
    "5": "76800",
    "6": "115200"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 765,
   "documented": "766",
   "name": "Transmission format",
   "description": "Start-data-parity-stop bits.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "1-8-E-1",
    "1": "1-8-O-1",
    "2": "1-8-N-1",
    "3": "1-8-N-2"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 767,
   "documented": "768",
   "name": "Bus configuration command",
   "description": "Used for on-event addressing (Climatix).",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Ready",
    "1": "Load",
    "2": "Discard"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1285,
   "documented": "1286",
   "name": "SW version major/minor",
   "description": "Major in high byte, minor in low byte.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1286,
   "documented": "1287",
   "name": "SW version build",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  }
 ],
 "integration": {
  "summary": "Leave DIP2 switch 7 OFF, wire A/B to the RS-485 bus, set the address over Modbus (default 1, 8E1, auto baud) and poll holding registers 0-15 with function 03.",
  "minimum_registers": [
   {
    "table": "holding_register",
    "address": 0,
    "why": "Temperature"
   },
   {
    "table": "holding_register",
    "address": 2,
    "why": "Relative humidity"
   },
   {
    "table": "holding_register",
    "address": 4,
    "why": "CO2 (QPM9152/MO)"
   },
   {
    "table": "holding_register",
    "address": 14,
    "why": "VOC (QPM9152/MO)"
   },
   {
    "table": "holding_register",
    "address": 1,
    "why": "Temperature reliability"
   },
   {
    "table": "holding_register",
    "address": 400,
    "why": "Temperature unit"
   }
  ],
  "enable": "DIP2 switch 7 OFF (default) lets the master configure address, baud and format via registers 764-768; ON uses the DIP switches (DIP1 = address, DIP2 = baud/parity/stop).",
  "watchdog": null,
  "quirks": [
   "Register number minus 1 = wire address.",
   "The temperature register follows the unit chosen in register 401 (°C or °F).",
   "Address 246 is reserved for Climatix on-event addressing."
  ],
  "setup": [
   "Bus termination is a jumper (OFF by default).",
   "A push-button hold of 10-13 s resets address, baud and format to factory defaults."
  ],
  "gotchas": [
   "If an invalid address is set by DIP switch, new values for registers 764-768 are not applied."
  ]
 },
 "page": "https://easymodbus.com/modbus-register-maps/siemens/qfm9150-mo-qpm9152-mo",
 "address_note": "address = 0-based Modbus wire (PDU) address; documented = as printed in the source.",
 "note": "Re-typed from the manufacturer's public documentation (see source) and verified against it. Registers vary by firmware and options; verify against the live device before writing."
}