 "manufacturer": "Sinclair",
 "manufacturer_slug": "sinclair",
 "model": "UNI SPLIT DC inverter indoor units (integrated Modbus RTU)",
 "model_slug": "uni-split",
 "short_model": "UNI SPLIT",
 "aliases": [
  "Sinclair UNI SPLIT",
  "UNI SPLIT Modbus",
  "All DC Inverter UNI SPLIT"
 ],
 "equipment_type": "VRF / split AC gateway (built-in indoor-unit Modbus)",
 "applies_to": "Sinclair All DC Inverter UNI SPLIT indoor units with the built-in Modbus RTU interface, per the UNI SPLIT Modbus user's manual.",
 "summary": "Sinclair's UNI SPLIT DC inverter indoor units have a Modbus RTU slave built into the indoor controller, so no separate gateway is needed; up to 255 units share one RS-485 line. Settings and analog values are 16-bit words (holding registers) and flags are coils. This map covers on/off, mode, fan, setpoint, swing, temperatures, remote locks and shields, feature flags, and the indoor, outdoor and inverter-drive fault bits.",
 "transport": [
  "RTU"
 ],
 "defaults": {
  "unit_id": null,
  "baud": 9600,
  "parity": "None",
  "data_bits": 8,
  "stop_bits": 1,
  "tcp_port": null
 },
 "addressing": {
  "convention": "0-based",
  "note": "Word and bit addresses start at 0 and go on the wire unchanged: 'Word 20' is holding register address 20 and 'Bit17' is coil address 17. The manual's read example (start address 00 01 for words 1-2) confirms the numbering."
 },
 "default_word_order": null,
 "firmware": null,
 "source": {
  "title": "User's manual UNI SPLIT Modbus",
  "doc_number": null,
  "revision_date": null,
  "url": "https://www.sinclair-solutions.com/files/user-manual-en/accessories/sinclair-um-uni-split-modbus-protocol-en.pdf",
  "pages": "pp. 2-3 (function codes), p. 7 (serial settings), pp. 8-12 (frame formats and examples), pp. 13-14 (precautions), pp. 15-43 (word and bit tables)"
 },
 "notes": [
  "All values are 16-bit words or single bits; there are no 32-bit values.",
  "Function codes listed: 01 read coils, 03 read registers, 0F write coils and 10 write registers. Single-write codes 05 and 06 are not listed.",
  "Reserved words and bits are left out, as are a few bits printed with no name (for example Bit125 and Bits 201-204 and 207, which have no value meaning).",
  "When energy saving is active in cooling (or heating), a remote setpoint below the cooling lower limit (or above the heating upper limit) is ignored. The two energy-saving bits (32 and 33) must be set or cleared together.",
  "After power-up, the module answers with exception 04 until it has valid data from the unit; 04 later means the module has lost contact with the air conditioner.",
  "Several fault bits are printed with '1: yes 0: on', which reads as a typo for '0: no'; they are given here as 1 = fault."
 ],
 "registers": [
  {
   "table": "coil",
   "address": 8,
   "documented": "Bit8",
   "name": "ODU present flag",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": {
    "0": "No",
    "1": "Yes"
   },
   "bits": null
  },
  {
   "table": "coil",
   "address": 9,
   "documented": "Bit9",
   "name": "Master wired controller present flag",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": {
    "0": "No",
    "1": "Yes"
   },
   "bits": null
  },
  {
   "table": "coil",
   "address": 13,
   "documented": "Bit13",
   "name": "Slave wired controller present flag",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": {
    "0": "No",
    "1": "Yes"
   },
   "bits": null
  },
  {
   "table": "coil",
   "address": 17,
   "documented": "Bit17",
   "name": "Remote lock",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Not locked",
    "1": "Locked by remote monitoring"
   },
   "bits": null
  },
  {
   "table": "coil",
   "address": 18,
   "documented": "Bit18",
   "name": "Remote temperature shield",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "0": "No shield",
    "1": "Shield"
   },
   "bits": null
  },
  {
   "table": "coil",
   "address": 19,
   "documented": "Bit19",
   "name": "Remote mode shield",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "0": "No shield",
    "1": "Shield"
   },
   "bits": null
  },
  {
   "table": "coil",
   "address": 20,
   "documented": "Bit20",
   "name": "Remote on/off shield",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "0": "No shield",
    "1": "Shield"
   },
   "bits": null
  },
  {
   "table": "coil",
   "address": 21,
   "documented": "Bit21",
   "name": "Remote energy-saving shield",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "0": "No shield",
    "1": "Shield"
   },
   "bits": null
  },
  {
   "table": "coil",
   "address": 24,
   "documented": "Bit24",
   "name": "Absence mode",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Off",
    "1": "On"
   },
   "bits": null
  },
  {
   "table": "coil",
   "address": 25,
   "documented": "Bit25",
   "name": "Healthy function",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Off",
    "1": "On"
   },
   "bits": null
  },
  {
   "table": "coil",
   "address": 26,
   "documented": "Bit26",
   "name": "I-Demand (comfort energy saving)",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Off",
    "1": "On"
   },
   "bits": null
  },
  {
   "table": "coil",
   "address": 27,
   "documented": "Bit27",
   "name": "Turbo",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Off",
    "1": "On"
   },
   "bits": null
  },
  {
   "table": "coil",
   "address": 28,
   "documented": "Bit28",
   "name": "Electric heating permission",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "0": "E-heating permitted",
    "1": "E-heating not permitted"
   },
   "bits": null
  },
  {
   "table": "coil",
   "address": 29,
   "documented": "Bit29",
   "name": "X-fan",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Off",
    "1": "On"
   },
   "bits": null
  },
  {
   "table": "coil",
   "address": 30,
   "documented": "Bit30",
   "name": "Silent",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Off",
    "1": "On"
   },
   "bits": null
  },
  {
   "table": "coil",
   "address": 31,
   "documented": "Bit31",
   "name": "Low-temperature drying mode",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Off",
    "1": "On"
   },
   "bits": null
  },
  {
   "table": "coil",
   "address": 32,
   "documented": "Bit32",
   "name": "Energy saving in cooling active",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Off",
    "1": "On"
   },
   "bits": null
  },
  {
   "table": "coil",
   "address": 33,
   "documented": "Bit33",
   "name": "Energy saving in heating active",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Off",
    "1": "On"
   },
   "bits": null
  },
  {
   "table": "coil",
   "address": 34,
   "documented": "Bit34",
   "name": "Button lock (child lock)",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Off",
    "1": "On"
   },
   "bits": null
  },
  {
   "table": "coil",
   "address": 35,
   "documented": "Bit35",
   "name": "On/off memory",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Memorise",
    "1": "Do not memorise"
   },
   "bits": null
  },
  {
   "table": "coil",
   "address": 36,
   "documented": "Bit36",
   "name": "Temperature unit flag",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "0": "°C",
    "1": "°F"
   },
   "bits": null
  },
  {
   "table": "coil",
   "address": 40,
   "documented": "Bit40",
   "name": "Timer status",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": {
    "0": "No timer",
    "1": "Timer set"
   },
   "bits": null
  },
  {
   "table": "coil",
   "address": 46,
   "documented": "Bit46",
   "name": "Gate control system fitted",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": {
    "0": "No",
    "1": "Yes"
   },
   "bits": null
  },
  {
   "table": "coil",
   "address": 47,
   "documented": "Bit47",
   "name": "Presence sensor module fitted",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": {
    "0": "No",
    "1": "Yes"
   },
   "bits": null
  },
  {
   "table": "coil",
   "address": 49,
   "documented": "Bit49",
   "name": "Timer on flag",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": {
    "0": "Not active",
    "1": "Active"
   },
   "bits": null
  },
  {
   "table": "coil",
   "address": 50,
   "documented": "Bit50",
   "name": "Timer off flag",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": {
    "0": "Not active",
    "1": "Active"
   },
   "bits": null
  },
  {
   "table": "coil",
   "address": 51,
   "documented": "Bit51",
   "name": "Indoor temperature source in current mode",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": {
    "0": "Return-air temperature",
    "1": "Wired controller temperature"
   },
   "bits": null
  },
  {
   "table": "coil",
   "address": 55,
   "documented": "Bit55",
   "name": "Low standby power (1 W) mode",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": {
    "0": "Mode 1",
    "1": "Mode 2"
   },
   "bits": null
  },
  {
   "table": "coil",
   "address": 65,
   "documented": "Bit65",
   "name": "Wired controller temp sensor error",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": {
    "0": "Normal",
    "1": "Fault"
   },
   "bits": null
  },
  {
   "table": "coil",
   "address": 70,
   "documented": "Bit70",
   "name": "Wired controller memory chip error",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": {
    "0": "Normal",
    "1": "Fault"
   },
   "bits": null
  },
  {
   "table": "coil",
   "address": 72,
   "documented": "Bit72",
   "name": "Cancel timer",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Do not cancel",
    "1": "Cancel"
   },
   "bits": null
  },
  {
   "table": "coil",
   "address": 74,
   "documented": "Bit74",
   "name": "Up/down swing mode",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Mode 1: simple swing",
    "1": "Mode 2: fixed angle and small-area swing"
   },
   "bits": null
  },
  {
   "table": "coil",
   "address": 91,
   "documented": "Bit91",
   "name": "Electric heating",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": {
    "0": "Off",
    "1": "On"
   },
   "bits": null
  },
  {
   "table": "coil",
   "address": 92,
   "documented": "Bit92",
   "name": "Water pump",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": {
    "0": "Off",
    "1": "On"
   },
   "bits": null
  },
  {
   "table": "coil",
   "address": 93,
   "documented": "Bit93",
   "name": "Fresh air valve switch",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": {
    "0": "Off",
    "1": "On"
   },
   "bits": null
  },
  {
   "table": "coil",
   "address": 94,
   "documented": "Bit94",
   "name": "Cold plasma generator",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": {
    "0": "Off",
    "1": "On"
   },
   "bits": null
  },
  {
   "table": "coil",
   "address": 95,
   "documented": "Bit95",
   "name": "Error output status",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": {
    "0": "No",
    "1": "Yes"
   },
   "bits": null
  },
  {
   "table": "coil",
   "address": 97,
   "documented": "Bit97",
   "name": "Indoor evaporator temp sensor error",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": {
    "0": "Normal",
    "1": "Fault"
   },
   "bits": null
  },
  {
   "table": "coil",
   "address": 98,
   "documented": "Bit98",
   "name": "Indoor return-air temp sensor error",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": {
    "0": "Normal",
    "1": "Fault"
   },
   "bits": null
  },
  {
   "table": "coil",
   "address": 99,
   "documented": "Bit99",
   "name": "Light-board ambient temp sensor error",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": {
    "0": "Normal",
    "1": "Fault"
   },
   "bits": null
  },
  {
   "table": "coil",
   "address": 101,
   "documented": "Bit101",
   "name": "Water overflow protection",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": {
    "0": "Normal",
    "1": "Fault"
   },
   "bits": null
  },
  {
   "table": "coil",
   "address": 102,
   "documented": "Bit102",
   "name": "IDU memory chip error",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": {
    "0": "Normal",
    "1": "Fault"
   },
   "bits": null
  },
  {
   "table": "coil",
   "address": 104,
   "documented": "Bit104",
   "name": "Jumper cap error (IDU)",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": {
    "0": "Normal",
    "1": "Fault"
   },
   "bits": null
  },
  {
   "table": "coil",
   "address": 105,
   "documented": "Bit105",
   "name": "Indoor fan error",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": {
    "0": "Normal",
    "1": "Fault"
   },
   "bits": null
  },
  {
   "table": "coil",
   "address": 112,
   "documented": "Bit112",
   "name": "Key card status",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": {
    "0": "Card out",
    "1": "Card in"
   },
   "bits": null
  },
  {
   "table": "coil",
   "address": 113,
   "documented": "Bit113",
   "name": "Room occupied",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": {
    "0": "No",
    "1": "Yes"
   },
   "bits": null
  },
  {
   "table": "coil",
   "address": 114,
   "documented": "Bit114",
   "name": "Static pressure type",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": {
    "0": "Low static",
    "1": "High static"
   },
   "bits": null
  },
  {
   "table": "coil",
   "address": 120,
   "documented": "Bit120",
   "name": "Comms failure with master wired controller",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": {
    "0": "Normal",
    "1": "Fault"
   },
   "bits": null
  },
  {
   "table": "coil",
   "address": 121,
   "documented": "Bit121",
   "name": "Comms failure with slave wired controller",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": {
    "0": "Normal",
    "1": "Fault"
   },
   "bits": null
  },
  {
   "table": "coil",
   "address": 122,
   "documented": "Bit122",
   "name": "Comms failure with ODU",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": {
    "0": "Normal",
    "1": "Fault"
   },
   "bits": null
  },
  {
   "table": "coil",
   "address": 147,
   "documented": "Bit147",
   "name": "Outdoor fan status",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": {
    "0": "Off",
    "1": "On"
   },
   "bits": null
  },
  {
   "table": "coil",
   "address": 150,
   "documented": "Bit150",
   "name": "4-way valve status",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": {
    "0": "Off",
    "1": "On"
   },
   "bits": null
  },
  {
   "table": "coil",
   "address": 151,
   "documented": "Bit151",
   "name": "Compressor status",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": {
    "0": "Off",
    "1": "On"
   },
   "bits": null
  },
  {
   "table": "coil",
   "address": 152,
   "documented": "Bit152",
   "name": "Discharge temperature protection",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": {
    "0": "Normal",
    "1": "Fault"
   },
   "bits": null
  },
  {
   "table": "coil",
   "address": 153,
   "documented": "Bit153",
   "name": "Refrigerant shortage protection",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": {
    "0": "Normal",
    "1": "Fault"
   },
   "bits": null
  },
  {
   "table": "coil",
   "address": 154,
   "documented": "Bit154",
   "name": "DC fan motor protection",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": {
    "0": "Normal",
    "1": "Fault"
   },
   "bits": null
  },
  {
   "table": "coil",
   "address": 155,
   "documented": "Bit155",
   "name": "4-way valve reversing error protection",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": {
    "0": "Normal",
    "1": "Fault"
   },
   "bits": null
  },
  {
   "table": "coil",
   "address": 156,
   "documented": "Bit156",
   "name": "Over-power protection",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": {
    "0": "Normal",
    "1": "Fault"
   },
   "bits": null
  },
  {
   "table": "coil",
   "address": 157,
   "documented": "Bit157",
   "name": "Overload protection",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": {
    "0": "Normal",
    "1": "Fault"
   },
   "bits": null
  },
  {
   "table": "coil",
   "address": 158,
   "documented": "Bit158",
   "name": "Low pressure protection",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": {
    "0": "Normal",
    "1": "Fault"
   },
   "bits": null
  },
  {
   "table": "coil",
   "address": 159,
   "documented": "Bit159",
   "name": "High pressure protection",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": {
    "0": "Normal",
    "1": "Fault"
   },
   "bits": null
  },
  {
   "table": "coil",
   "address": 160,
   "documented": "Bit160",
   "name": "Evaporator anti-freeze protection",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": {
    "0": "Normal",
    "1": "Fault"
   },
   "bits": null
  },
  {
   "table": "coil",
   "address": 161,
   "documented": "Bit161",
   "name": "Outdoor ambient temp sensor error",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": {
    "0": "Normal",
    "1": "Fault"
   },
   "bits": null
  },
  {
   "table": "coil",
   "address": 162,
   "documented": "Bit162",
   "name": "Discharge temp sensor error",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": {
    "0": "Normal",
    "1": "Fault"
   },
   "bits": null
  },
  {
   "table": "coil",
   "address": 163,
   "documented": "Bit163",
   "name": "Condenser temp sensor error",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": {
    "0": "Normal",
    "1": "Fault"
   },
   "bits": null
  },
  {
   "table": "coil",
   "address": 164,
   "documented": "Bit164",
   "name": "Outdoor coil pipe temp sensor error",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": {
    "0": "Normal",
    "1": "Fault"
   },
   "bits": null
  },
  {
   "table": "coil",
   "address": 165,
   "documented": "Bit165",
   "name": "Jumper cap error (ODU)",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": {
    "0": "Normal",
    "1": "Fault"
   },
   "bits": null
  },
  {
   "table": "coil",
   "address": 166,
   "documented": "Bit166",
   "name": "ODU memory chip error",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": {
    "0": "Normal",
    "1": "Fault"
   },
   "bits": null
  },
  {
   "table": "coil",
   "address": 174,
   "documented": "Bit174",
   "name": "Drive communication failure",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": {
    "0": "Normal",
    "1": "Fault"
   },
   "bits": null
  },
  {
   "table": "coil",
   "address": 176,
   "documented": "Bit176",
   "name": "SAVE status",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": {
    "0": "Off",
    "1": "On"
   },
   "bits": null
  },
  {
   "table": "coil",
   "address": 177,
   "documented": "Bit177",
   "name": "Cooling-only flag",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": {
    "0": "Heat pump (cool and heat)",
    "1": "Cooling only"
   },
   "bits": null
  },
  {
   "table": "coil",
   "address": 179,
   "documented": "Bit179",
   "name": "System defrosting",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": {
    "0": "No",
    "1": "Yes"
   },
   "bits": null
  },
  {
   "table": "coil",
   "address": 182,
   "documented": "Bit182",
   "name": "Low power consumption status",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": {
    "0": "Not ready",
    "1": "Ready"
   },
   "bits": null
  },
  {
   "table": "coil",
   "address": 183,
   "documented": "Bit183",
   "name": "AC input phase sequence protection",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": {
    "0": "Normal",
    "1": "Fault"
   },
   "bits": null
  },
  {
   "table": "coil",
   "address": 184,
   "documented": "Bit184",
   "name": "Drive DC bus undervoltage / voltage drop",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": {
    "0": "Normal",
    "1": "Fault"
   },
   "bits": null
  },
  {
   "table": "coil",
   "address": 185,
   "documented": "Bit185",
   "name": "Drive DC bus overvoltage",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": {
    "0": "Normal",
    "1": "Fault"
   },
   "bits": null
  },
  {
   "table": "coil",
   "address": 186,
   "documented": "Bit186",
   "name": "Drive AC input current protection",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": {
    "0": "Normal",
    "1": "Fault"
   },
   "bits": null
  },
  {
   "table": "coil",
   "address": 187,
   "documented": "Bit187",
   "name": "Drive IPM protection",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": {
    "0": "Normal",
    "1": "Fault"
   },
   "bits": null
  },
  {
   "table": "coil",
   "address": 188,
   "documented": "Bit188",
   "name": "Drive PFC protection",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": {
    "0": "Normal",
    "1": "Fault"
   },
   "bits": null
  },
  {
   "table": "coil",
   "address": 189,
   "documented": "Bit189",
   "name": "Compressor startup failure",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": {
    "0": "Normal",
    "1": "Fault"
   },
   "bits": null
  },
  {
   "table": "coil",
   "address": 190,
   "documented": "Bit190",
   "name": "Compressor phase loss protection",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": {
    "0": "Normal",
    "1": "Fault"
   },
   "bits": null
  },
  {
   "table": "coil",
   "address": 191,
   "documented": "Bit191",
   "name": "Drive module reset",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": {
    "0": "Normal",
    "1": "Fault"
   },
   "bits": null
  },
  {
   "table": "coil",
   "address": 192,
   "documented": "Bit192",
   "name": "Compressor over-current protection",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": {
    "0": "Normal",
    "1": "Fault"
   },
   "bits": null
  },
  {
   "table": "coil",
   "address": 193,
   "documented": "Bit193",
   "name": "Compressor power protection",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": {
    "0": "Normal",
    "1": "Fault"
   },
   "bits": null
  },
  {
   "table": "coil",
   "address": 194,
   "documented": "Bit194",
   "name": "Drive current detection circuit failure",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": {
    "0": "Normal",
    "1": "Fault"
   },
   "bits": null
  },
  {
   "table": "coil",
   "address": 195,
   "documented": "Bit195",
   "name": "Compressor out-of-step protection",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": {
    "0": "Normal",
    "1": "Fault"
   },
   "bits": null
  },
  {
   "table": "coil",
   "address": 196,
   "documented": "Bit196",
   "name": "Compressor stalling",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": {
    "0": "Normal",
    "1": "Fault"
   },
   "bits": null
  },
  {
   "table": "coil",
   "address": 198,
   "documented": "Bit198",
   "name": "Drive module high temperature protection",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": {
    "0": "Normal",
    "1": "Fault"
   },
   "bits": null
  },
  {
   "table": "coil",
   "address": 199,
   "documented": "Bit199",
   "name": "Drive module temperature sensor failure",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": {
    "0": "Normal",
    "1": "Fault"
   },
   "bits": null
  },
  {
   "table": "coil",
   "address": 205,
   "documented": "Bit205",
   "name": "Drive under-charge",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": {
    "0": "Charged",
    "1": "Under charge"
   },
   "bits": null
  },
  {
   "table": "coil",
   "address": 208,
   "documented": "Bit208",
   "name": "Drive storage chip failure",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": {
    "0": "Normal",
    "1": "Fault"
   },
   "bits": null
  },
  {
   "table": "coil",
   "address": 210,
   "documented": "Bit210",
   "name": "Drive charging circuit failure",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": {
    "0": "Normal",
    "1": "Fault"
   },
   "bits": null
  },
  {
   "table": "coil",
   "address": 211,
   "documented": "Bit211",
   "name": "Drive AC input voltage abnormal",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": {
    "0": "Normal",
    "1": "Fault"
   },
   "bits": null
  },
  {
   "table": "coil",
   "address": 212,
   "documented": "Bit212",
   "name": "Drive electric box temp sensor failure",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": {
    "0": "Normal",
    "1": "Fault"
   },
   "bits": null
  },
  {
   "table": "coil",
   "address": 213,
   "documented": "Bit213",
   "name": "Drive AC input zero-cross protection",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": {
    "0": "Normal",
    "1": "Fault"
   },
   "bits": null
  },
  {
   "table": "coil",
   "address": 214,
   "documented": "Bit214",
   "name": "Temperature drift protection",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": {
    "0": "Normal",
    "1": "Fault"
   },
   "bits": null
  },
  {
   "table": "coil",
   "address": 215,
   "documented": "Bit215",
   "name": "Current sensor connection protection",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": {
    "0": "Normal",
    "1": "Fault"
   },
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 2,
   "documented": "Word 2",
   "name": "Unit on/off",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "170": "0xAA: on",
    "85": "0x55: off"
   },
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 4,
   "documented": "Word 4",
   "name": "Ambient temperature",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 5,
   "documented": "Word 5",
   "name": "IDU address",
   "description": "1-16 with a central controller, 1-255 in PC address mode.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 17,
   "documented": "Word 17",
   "name": "Set mode",
   "description": "Heating is ignored on cooling-only units.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "1": "Cooling",
    "2": "Heating",
    "3": "Drying",
    "4": "Fan only",
    "5": "Auto"
   },
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 19,
   "documented": "Word 19",
   "name": "Set fan speed",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Auto",
    "1": "Speed 1",
    "2": "Speed 2",
    "3": "Speed 3",
    "4": "Speed 4",
    "5": "Speed 5",
    "6": "Turbo"
   },
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 20,
   "documented": "Word 20",
   "name": "Set temperature",
   "description": "16-30 °C; reads 12 in low-temp drying and 8 in absence mode.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "°C",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 22,
   "documented": "Word 22",
   "name": "Up/down swing",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Off",
    "1": "Swing 1-5",
    "2": "Position 1",
    "3": "Position 2",
    "4": "Position 3",
    "5": "Position 4",
    "6": "Position 5",
    "7": "Swing 3-5",
    "8": "Swing 2-5",
    "9": "Swing 2-4",
    "10": "Swing 1-4",
    "11": "Swing 1-3"
   },
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 23,
   "documented": "Word 23",
   "name": "Left/right swing",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Off (default after power-on)",
    "1": "Swing, same direction",
    "2": "Position 1",
    "3": "Position 2",
    "4": "Position 3",
    "5": "Position 4",
    "6": "Position 5",
    "12": "Positions 1-5",
    "13": "Swing, opposite direction"
   },
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 24,
   "documented": "Word 24",
   "name": "Fresh air valve",
   "description": "0-10; the manual lists 10 fresh-air modes but the meaning of 0 is cut short.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 25,
   "documented": "Word 25",
   "name": "Sleep mode",
   "description": "Ignored in fan or auto mode.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "0": "No sleep",
    "1": "Sleep 1",
    "2": "Sleep 2",
    "3": "Sleep 3"
   },
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 34,
   "documented": "Word 34",
   "name": "Clean function",
   "description": "0 = no clean function; 10-39 = contamination grade.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 35,
   "documented": "Word 35",
   "name": "Energy-saving lower limit, cooling",
   "description": "16-30 °C.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "°C",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 36,
   "documented": "Word 36",
   "name": "Energy-saving upper limit, heating",
   "description": "16-30 °C.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "°C",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 39,
   "documented": "Word 39",
   "name": "Ambient temperature sensor selection",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": {
    "1": "Return-air sensor",
    "2": "Wired controller sensor",
    "3": "Return air for cool/dry/fan, wired controller for heat/auto"
   },
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 49,
   "documented": "Word 49",
   "name": "Outdoor ambient temperature",
   "description": "-100 to 155 °C.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 77,
   "documented": "Word 77",
   "name": "DRED function",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": {
    "0": "No DRED",
    "1": "DRED1",
    "2": "DRED2",
    "3": "DRED3"
   },
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 82,
   "documented": "Word 82",
   "name": "Return-air temperature",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 83,
   "documented": "Word 83",
   "name": "Light-board ambient temperature",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null
  }
 ],
 "integration": {
  "summary": "Set the indoor unit to PC/Modbus address mode on the wired controller, then poll holding registers 0-83 with function 03 and coils 0-215 with function 01. Control by writing words 2, 17, 19 and 20 with function 16.",
  "minimum_registers": [
   {
    "table": "holding_register",
    "address": 2,
    "why": "Unit on/off (0xAA on, 0x55 off)"
   },
   {
    "table": "holding_register",
    "address": 4,
    "why": "Ambient temperature"
   },
   {
    "table": "holding_register",
    "address": 17,
    "why": "Mode"
   },
   {
    "table": "holding_register",
    "address": 19,
    "why": "Fan speed"
   },
   {
    "table": "holding_register",
    "address": 20,
    "why": "Setpoint"
   },
   {
    "table": "coil",
    "address": 151,
    "why": "Compressor running"
   },
   {
    "table": "coil",
    "address": 122,
    "why": "ODU communication failure"
   }
  ],
  "enable": "The Modbus interface is built into the indoor unit controller. Select the address mode and set the unit address on the wired controller (see the unit's service manual).",
  "watchdog": null,
  "quirks": [
   "Writes must use function 16 (registers) or 15 (coils); function 06/05 are not listed.",
   "On/off uses 0xAA (on) and 0x55 (off), not 1/0.",
   "The BMS and the unit's own controls act equally: the most recent command wins."
  ],
  "setup": [
   "RS-485 at 9600 baud, 8 data bits, no parity, 1 stop bit.",
   "Up to 255 indoor units per RS-485 port; use another port for more.",
   "Use twisted pair and keep it at least 15 cm from power cables."
  ],
  "gotchas": [
   "Exception 04 means the Modbus module can't reach the air conditioner, including right after power-up.",
   "Heating commands are ignored on cooling-only units (check coil 177)."
  ]
 },
 "page": "https://easymodbus.com/modbus-register-maps/sinclair/uni-split",
 "address_note": "address = 0-based Modbus wire (PDU) address; documented = as printed in the source.",
 "note": "Re-typed from the manufacturer's public documentation (see source) and verified against it. Registers vary by firmware and options; verify against the live device before writing."
}