 "manufacturer": "Smart Temp",
 "manufacturer_slug": "smart-temp",
 "model": "SMT-770 thermostat with EC-02 module (Modbus RTU)",
 "model_slug": "smt-770",
 "short_model": "SMT-770",
 "aliases": [
  "SMT-770 Chameleon",
  "EC-02",
  "SMT770"
 ],
 "equipment_type": "Thermostat",
 "applies_to": "SMT-770 thermostat (with or without a paired EC-02 module), communications addendum v4.6 for firmware 2.31.",
 "summary": "The Smart Temp SMT-770 is an Australian 24 V multifunction thermostat with an RS-485 Modbus RTU port; a paired EC-02 output module appears as the same device. This map covers relay coils, thermostat and fan modes, set temperatures, room temperature, network settings and the coil override.",
 "transport": [
  "RTU"
 ],
 "defaults": {
  "unit_id": 7,
  "baud": 9600,
  "parity": "None",
  "data_bits": 8,
  "stop_bits": 1,
  "tcp_port": null
 },
 "addressing": {
  "convention": "Modicon",
  "note": "Coils are printed 00001-00005 and holding registers 40002 upward (Modicon references); subtract 1 (coils) or 40001 (holding registers) for the wire address."
 },
 "default_word_order": null,
 "firmware": "2.31 (addendum v4.6)",
 "source": {
  "title": "SMT-770 / EC-02 Communications Addendum",
  "doc_number": "Version 4.6 (firmware 2.31, 1/03/12)",
  "revision_date": null,
  "url": "https://digitalassets.reecegroup.com.au/m/b5ba7cc34ddc69cd/original/Modbus-Smart-Temp-SMT-770-Chameleon-Multifunction-Thermostat.pdf",
  "unofficial": true,
  "pages": "protocol p. 1; address setting p. 3; coils p. 4; holding registers pp. 4-13"
 },
 "notes": [
  "This copy is hosted by the distributor Reece; it is the Smart Temp SMT-770 / EC-02 Communications Addendum, version 4.6.",
  "Set temperatures in Celsius mode are stored as (°C x 2) + 20, so value = raw x 0.5 - 10; in Fahrenheit mode the raw value is °F directly. The map shows the Celsius scaling; check 40029.",
  "Left out: 40310/40313/40316 room and outside-air temperatures, whose Celsius formula is printed two ways (subtract 20 or subtract 80); register 4021 (security PIN, address misprinted); the second 40318 row (heating set temperature, duplicate address); the TT temperature 40356, whose label says °F while its range is in °C; schedule registers 40513 upward.",
  "Many registers only act in particular DIP-switch modes (DIP 6/8 select manual, two-setpoint, commercial or residential programmable). Writing values that conflict with the DIP settings is ignored.",
  "Factory Modbus address is 7. The addendum warns that writing unlisted registers can corrupt the thermostat setup.",
  "The addendum prints 40318 twice (active set temperature, then heating set temperature after 40319). This map keeps the first, in-sequence 40318 as the active setpoint; confirm on site."
 ],
 "registers": [
  {
   "table": "coil",
   "address": 0,
   "documented": "00001",
   "name": "G1 relay",
   "description": "Writable from firmware 2.19; see coil override 40062.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Off",
    "1": "On"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 1,
   "documented": "00002",
   "name": "G2/Y2 relay",
   "description": "Writable from firmware 2.19; see coil override 40062.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Off",
    "1": "On"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 2,
   "documented": "00003",
   "name": "G3/W2/OB relay",
   "description": "Writable from firmware 2.19; see coil override 40062.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Off",
    "1": "On"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 3,
   "documented": "00004",
   "name": "Y1 relay",
   "description": "Writable from firmware 2.19; see coil override 40062.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Off",
    "1": "On"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 4,
   "documented": "00005",
   "name": "W1 relay",
   "description": "Writable from firmware 2.19; see coil override 40062.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Off",
    "1": "On"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1,
   "documented": "40002",
   "name": "Thermostat mode",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Off",
    "2": "Heat only",
    "3": "Cool only",
    "4": "Auto changeover",
    "5": "Emergency heat",
    "6": "Cool and dry (v2.3+)",
    "7": "Auto and dry (v2.3+)"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2,
   "documented": "40003",
   "name": "Fan mode",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Auto (cycles with heat/cool)",
    "1": "On"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 3,
   "documented": "40004",
   "name": "Program hold",
   "description": "Only in residential programmable mode (DIP 6 and 8 on).",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Off",
    "1": "Temporary hold",
    "2": "Permanent hold"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 4,
   "documented": "40005",
   "name": "Heat set temperature (hold)",
   "description": "Two-setpoint modes. °C = (raw - 20) / 2.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.5,
   "units": "°C",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": -10
  },
  {
   "table": "holding_register",
   "address": 5,
   "documented": "40006",
   "name": "Cool set temperature (hold)",
   "description": "Two-setpoint modes. °C = (raw - 20) / 2.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.5,
   "units": "°C",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": -10
  },
  {
   "table": "holding_register",
   "address": 9,
   "documented": "40010",
   "name": "Fan speed",
   "description": "Needs 3-speed fan DIP setting.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "1": "Low",
    "2": "Medium",
    "3": "High",
    "4": "Auto"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 10,
   "documented": "40011",
   "name": "Day cool set temperature",
   "description": "255 = off. °C = (raw - 20) / 2.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.5,
   "units": "°C",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": -10
  },
  {
   "table": "holding_register",
   "address": 11,
   "documented": "40012",
   "name": "Day heat set temperature",
   "description": "0 = off. °C = (raw - 20) / 2.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.5,
   "units": "°C",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": -10
  },
  {
   "table": "holding_register",
   "address": 12,
   "documented": "40013",
   "name": "Night cool set temperature",
   "description": "255 = off. °C = (raw - 20) / 2.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.5,
   "units": "°C",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": -10
  },
  {
   "table": "holding_register",
   "address": 13,
   "documented": "40014",
   "name": "Night heat set temperature",
   "description": "0 = off. °C = (raw - 20) / 2.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.5,
   "units": "°C",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": -10
  },
  {
   "table": "holding_register",
   "address": 14,
   "documented": "40015",
   "name": "Single set point (manual mode)",
   "description": "DIP 6 and 8 off. °C = (raw - 20) / 2.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.5,
   "units": "°C",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": -10
  },
  {
   "table": "holding_register",
   "address": 18,
   "documented": "40019",
   "name": "Current running program",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Manual mode",
    "1": "Program event 1",
    "2": "Program event 2",
    "3": "Program event 3",
    "4": "Program event 4",
    "5": "Start event",
    "6": "Stop event"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 19,
   "documented": "40020",
   "name": "Sentinel point",
   "description": "Identifies an SMT-770: 77 before firmware 2.17, 78 from 2.17.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 21,
   "documented": "40022",
   "name": "Modbus address",
   "description": "1-32; the network must follow a change.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 23,
   "documented": "40024",
   "name": "Temperature display mode",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Room and set temperature",
    "1": "Set temperature only"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 28,
   "documented": "40029",
   "name": "Display units",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "°F",
    "1": "°C"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 40,
   "documented": "40041",
   "name": "Permitted modes",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Auto (heat and cool)",
    "1": "Cool only",
    "2": "Heat only",
    "3": "Manual heat/cool (v2.19+)",
    "4": "Cool-dry / auto-dry (v2.3+)",
    "5": "Cool and dry (v2.3+)",
    "6": "Manual plus cool-dry (v2.3+)"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 53,
   "documented": "40054",
   "name": "Day/night mode",
   "description": "Two-setpoint manual mode only.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Night",
    "1": "Day"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 54,
   "documented": "40055",
   "name": "Firmware revision",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 56,
   "documented": "40057",
   "name": "Remote off status",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Mode selected by user",
    "1": "Held off remotely"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 57,
   "documented": "40058",
   "name": "Start/stop mode override",
   "description": "Commercial programmable mode only.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Normal schedule",
    "1": "Locked to start program",
    "2": "Locked to stop program"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 59,
   "documented": "40060",
   "name": "Baud rate",
   "description": "Changing it disconnects the unit from the current network.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "1": "4800",
    "2": "9600",
    "3": "19200"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 61,
   "documented": "40062",
   "name": "Coil override mode",
   "description": "Write 1 at least every 4 minutes to keep Modbus control of the relays (v2.2+).",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Thermostat controls relays",
    "1": "Modbus controls relays"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 67,
   "documented": "40068",
   "name": "Parity",
   "description": "Firmware 2.31+.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "None",
    "1": "Even",
    "2": "Odd"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 69,
   "documented": "40070",
   "name": "TT input status",
   "description": "Firmware 2.2+.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Open",
    "1": "Shorted"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 317,
   "documented": "40318",
   "name": "Active set temperature",
   "description": "Current active setpoint. °C = (raw - 20) / 2.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.5,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": -10
  },
  {
   "table": "holding_register",
   "address": 318,
   "documented": "40319",
   "name": "Active cooling set temperature",
   "description": "°C = (raw - 20) / 2.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.5,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": -10
  },
  {
   "table": "holding_register",
   "address": 346,
   "documented": "40347",
   "name": "Room minus set temperature",
   "description": "100 = equal; each count is 0.1 °C above (+) or below (-) the setpoint (v2.19+).",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 349,
   "documented": "40350",
   "name": "Raw room temperature",
   "description": "Fast-updating sensor value, (raw - 400) / 10 (v2.17+).",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": -40
  },
  {
   "table": "holding_register",
   "address": 353,
   "documented": "40354",
   "name": "Displayed room temperature",
   "description": "Value shown on the LCD, (raw - 400) / 10 (v2.17+).",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": -40
  }
 ],
 "integration": {
  "summary": "Read 40354 for the room temperature shown on the display and 40318 for the active setpoint; write mode (40002), fan (40003) and setpoints (40005/40006 or 40015 depending on DIP mode).",
  "minimum_registers": [
   {
    "table": "holding_register",
    "address": 353,
    "why": "Room temperature (0.1 °C)"
   },
   {
    "table": "holding_register",
    "address": 317,
    "why": "Active setpoint"
   },
   {
    "table": "holding_register",
    "address": 1,
    "why": "Thermostat mode"
   },
   {
    "table": "holding_register",
    "address": 2,
    "why": "Fan mode"
   },
   {
    "table": "holding_register",
    "address": 14,
    "why": "Single setpoint (manual mode)"
   },
   {
    "table": "coil",
    "address": 0,
    "why": "G1 fan relay"
   }
  ],
  "enable": "Set the thermostat address in the installer menu (item AD, default 7); 9600 8N1 by default. A paired EC-02 copies address and baud from the thermostat.",
  "watchdog": "Coil override (40062) falls back to thermostat control after about 5 minutes without Modbus or after a power loss; refresh it at least every 4 minutes.",
  "quirks": [
   "Celsius setpoints are (raw - 20) / 2.",
   "Registers 40350/40354 are (raw - 400) / 10."
  ],
  "setup": [
   "Only the last device on the bus gets the EOL resistor; with a paired EC-02, terminate at the EC-02, not the thermostat.",
   "Up to 32 thermostats per segment."
  ],
  "gotchas": [
   "Writes that conflict with the DIP-switch mode are silently ignored.",
   "Changing baud (40060) or parity (40068) over Modbus drops the device off the current network."
  ]
 },
 "page": "https://easymodbus.com/modbus-register-maps/smart-temp/smt-770",
 "address_note": "address = 0-based Modbus wire (PDU) address; documented = as printed in the source.",
 "note": "Re-typed from the manufacturer's public documentation (see source) and verified against it. Registers vary by firmware and options; verify against the live device before writing."
}