SmartGen Modbus register maps

Updated 25 October 2026

4 SmartGen models, 510 registers in all, each re-typed from SmartGen’s own free documentation and checked against it.

4 of 4 shown

SmartGen: default communication settings

Factory defaults as the manufacturer documents them. Change one setting at a time on site and write down what you changed. Word order applies to 32-bit values; the addressing column says how the manufacturer prints register numbers (every map on this site also gives the 0-based wire address).

ModelTransportUnit IDSerialWord orderDocumented addressingRegisters
HGM4010N / HGM4020NRTU19600 baud, 8N1CDAB0-based150
HGM6100N / HGM6100CAN SeriesRTU19600 baud, 8N116-bit only0-based145
HGM7100N SeriesRTUNot stated9600 baud, 8N116-bit only0-based81
HGM9510N / HGM9520N / HGM9530NRTU/TCP19600 baud, 8N1CDAB0-based134