 "manufacturer": "Stiebel Eltron",
 "manufacturer_slug": "stiebel-eltron",
 "model": "Integral ventilation units LWZ / LWA via ISG Modbus TCP/IP",
 "model_slug": "isg-modbus-lwz-ventilation-units",
 "short_model": "ISG Modbus LWZ",
 "aliases": [
  "LWZ 303 Integral",
  "LWZ 403 SOL",
  "LWA 403",
  "LWZ 304 Trend",
  "LWZ 404 Trend",
  "LWZ 304 SOL",
  "LWZ 404 SOL",
  "LWZ 504",
  "LWZ Smart",
  "LWZ 604 Air",
  "LWZ 5 S Plus",
  "LWZ 5 S Trend",
  "LWZ 8 S Trend",
  "LWZ 5 S Smart",
  "LWZ 5 CS Premium",
  "LWZ 8 CS Premium"
 ],
 "equipment_type": "Heat pump (integral ventilation unit, via ISG Modbus TCP gateway)",
 "applies_to": "Stiebel Eltron LWZ / LWA integral ventilation and heat pump units reached through an ISG web or ISG plus with the Modbus TCP/IP software extension.",
 "summary": "Stiebel Eltron's LWZ integral units combine ventilation with heat recovery, an exhaust-air heat pump and DHW. Over Modbus they are reached through the Internet Service Gateway (ISG) with the Modbus TCP/IP extension, which serves single 16-bit registers with fixed scaling per data type. The map covers system values (input registers 1-33), operating mode, heating/DHW/cooling setpoints and fan stages (holding 1001-1027), status flags (2001-2005), heat, energy and runtime counters (3001-3032) and the shared SG Ready registers.",
 "transport": [
  "TCP"
 ],
 "defaults": {
  "unit_id": 1,
  "baud": null,
  "parity": null,
  "data_bits": null,
  "stop_bits": null,
  "tcp_port": 502
 },
 "addressing": {
  "convention": "1-based",
  "note": "The document states that ISG addressing is 1-based (its example: register 30501 is reached as address 501 with function code 04), so subtract one from the printed register number: outside temperature, printed 7, is requested at input register address 6. The document also warns that, depending on the configuration, an offset of 1 may have to be allowed for; confirm with outside temperature against the unit display."
 },
 "default_word_order": null,
 "firmware": null,
 "source": {
  "title": "Software documentation - Software extension for Internet Service Gateway - Modbus TCP/IP",
  "doc_number": "A 321798-44755-9770",
  "revision_date": null,
  "url": "https://www.heizungsdiscount24.de/pdf/Stiebel-Eltron-Internet-Service-Gateway-ISG-Connect-Software-Dokumentation.pdf",
  "pages": "English section PDF pp. 35-39 (printed pp. 34-38): ventilation tables pp. 35-38, SG Ready and controller ID pp. 38-39; data types p. 26. German original PDF pp. 13-17 cross-checked.",
  "unofficial": true
 },
 "notes": [
  "Stiebel Eltron does not host this software documentation publicly (its own download path returns 404). The linked copy is a retailer mirror of the unchanged Stiebel Eltron document with one shop cover page added in front.",
  "Data types: type 2 = signed, value x 0.1; type 6 = unsigned, x 1; type 7 = signed, value x 0.01; type 8 = unsigned 0-255, x 1. Unavailable objects return 32768 (0x8000).",
  "For LWZ units the controller reports -60 for a missing or open sensor lead and -50 for a shorted sensor lead.",
  "Energy totals are split into a kWh register (0-999) and an MWh register: total = MWh x 1000 + kWh.",
  "Rows marked '(x)' in the table apply only to the listed sub-models (LWZ 504, units with cooling, units with solar, LWZ 304/404/504/Trend); this is noted in the descriptions. Registers 18 and 19 (supply air fan) are listed for LWZ only, not LWA.",
  "Left out: extract air temperature (23) and extract air dew point (24), because they are typed as signed x 0.1 values but given a 0-65535 range; BUS-STATUS (2003), typed unsigned but coded with negative values.",
  "Holding registers 1016-1027 sit on a continuation page without a repeated table header in the English section; their values were checked against the German table.",
  "SG Ready on/off (4001): the language tables of the same document disagree on the coding (German and Italian: 0 = off, 1 = on; English: 0 = on, 1 = off). No value labels are given here; test on site which code switches the function on.",
  "WPM-managed heat pumps use another register set: see stiebel-eltron/isg-modbus-wpm-heat-pumps."
 ],
 "registers": [
  {
   "table": "input_register",
   "address": 0,
   "documented": "1",
   "name": "Actual room T HC1",
   "description": "Room temperature, heating circuit 1 (remote control value).",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "scale_factor_ref": null,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 1,
   "documented": "2",
   "name": "Set room temperature HC1",
   "description": "Room setpoint, heating circuit 1.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "scale_factor_ref": null,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 2,
   "documented": "3",
   "name": "Relative humidity HC1",
   "description": "Room humidity, heating circuit 1 (remote control value).",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "scale_factor_ref": null,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 3,
   "documented": "4",
   "name": "Actual room T HC2",
   "description": "Room temperature, heating circuit 2 (remote control value).",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "scale_factor_ref": null,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 4,
   "documented": "5",
   "name": "Set room temperature HC2",
   "description": "Room setpoint, heating circuit 2.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "scale_factor_ref": null,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 5,
   "documented": "6",
   "name": "Relative humidity HC2",
   "description": "Room humidity, heating circuit 2 (remote control value).",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "scale_factor_ref": null,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 6,
   "documented": "7",
   "name": "Outside temperature",
   "description": "Outdoor air temperature.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "scale_factor_ref": null,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 7,
   "documented": "8",
   "name": "Actual value HC1",
   "description": "Heating circuit 1 actual temperature.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "scale_factor_ref": null,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 8,
   "documented": "9",
   "name": "Set value HC1",
   "description": "Heating circuit 1 setpoint.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "scale_factor_ref": null,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 9,
   "documented": "10",
   "name": "Actual value HC2",
   "description": "Heating circuit 2 actual temperature.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "scale_factor_ref": null,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 10,
   "documented": "11",
   "name": "Set value HC2",
   "description": "Heating circuit 2 setpoint.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "scale_factor_ref": null,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 11,
   "documented": "12",
   "name": "Flow temperature",
   "description": "Heating flow temperature.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "scale_factor_ref": null,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 12,
   "documented": "13",
   "name": "Return temperature",
   "description": "Heating return temperature.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "scale_factor_ref": null,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 13,
   "documented": "14",
   "name": "Pressure heating circuit",
   "description": "Heating circuit pressure; LWZ 304/404/504/Trend only.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "scale_factor_ref": null,
   "units": "bar",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 14,
   "documented": "15",
   "name": "Flow rate",
   "description": "Heating water flow rate; LWZ 304/404/504/Trend only.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "scale_factor_ref": null,
   "units": "l/min",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 15,
   "documented": "16",
   "name": "Actual DHW temperature",
   "description": "Hot water cylinder temperature.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "scale_factor_ref": null,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 16,
   "documented": "17",
   "name": "DHW set temperature",
   "description": "Hot water setpoint.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "scale_factor_ref": null,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 17,
   "documented": "18",
   "name": "Ventilation air actual fan speed",
   "description": "Supply (ventilation) air fan speed.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "Hz",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 18,
   "documented": "19",
   "name": "Ventilation air set flow rate",
   "description": "Supply air flow setpoint.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "m³/h",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 19,
   "documented": "20",
   "name": "Extract air actual fan speed",
   "description": "Extract air fan speed.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "Hz",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 20,
   "documented": "21",
   "name": "Extract air set flow rate",
   "description": "Extract air flow setpoint.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "m³/h",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 21,
   "documented": "22",
   "name": "Extract air humidity",
   "description": "Extract air relative humidity; LWZ 304/404/504/Trend only.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 24,
   "documented": "25",
   "name": "Dew point temp. HC1",
   "description": "Dew point, heating circuit 1; units with cooling only.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "scale_factor_ref": null,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 25,
   "documented": "26",
   "name": "Dew point temp. HC2",
   "description": "Dew point, heating circuit 2; units with cooling only.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "scale_factor_ref": null,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 26,
   "documented": "27",
   "name": "Collector temperature",
   "description": "Solar collector temperature; units with solar only.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "scale_factor_ref": null,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 27,
   "documented": "28",
   "name": "Hot gas temperature",
   "description": "Compressor discharge temperature.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "scale_factor_ref": null,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 28,
   "documented": "29",
   "name": "High pressure",
   "description": "Refrigerant high pressure.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "scale_factor_ref": null,
   "units": "bar",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 29,
   "documented": "30",
   "name": "Low pressure",
   "description": "Refrigerant low pressure.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "scale_factor_ref": null,
   "units": "bar",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 30,
   "documented": "31",
   "name": "Compressor starts",
   "description": "Number of compressor starts.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 31,
   "documented": "32",
   "name": "Compressor speed",
   "description": "Compressor speed; LWZ 504 only.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "scale_factor_ref": null,
   "units": "Hz",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 32,
   "documented": "33",
   "name": "Mixed water amount",
   "description": "Available mixed hot water volume; LWZ 504 only.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "l",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 2000,
   "documented": "2001",
   "name": "Operating status",
   "description": "Packed status flags of the unit.",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "0": "Switching program enabled",
    "1": "Compressor",
    "2": "Heating",
    "3": "Cooling",
    "4": "DHW",
    "5": "Electric reheating",
    "6": "Service",
    "7": "Power-off (utility block)",
    "8": "Filter",
    "9": "Ventilation",
    "10": "Heating circuit pump",
    "11": "Evaporator defrost",
    "12": "Filter extract air",
    "13": "Filter ventilation air",
    "14": "Heat-up program"
   },
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 2001,
   "documented": "2002",
   "name": "Fault status",
   "description": "1 = system fault; acknowledge only via SERVICEWELT.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": {
    "0": "No fault",
    "1": "Fault"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 2003,
   "documented": "2004",
   "name": "Defrost initiated",
   "description": "1 = defrost signal active.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": {
    "0": "Off",
    "1": "Initiated"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 2004,
   "documented": "2005",
   "name": "Operating status-2",
   "description": "Further packed status flags.",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "0": "Summer mode active",
    "1": "Oven/fireplace mode active"
   },
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 3000,
   "documented": "3001",
   "name": "Heat meter htg day",
   "description": "Heat delivered for heating today.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "kWh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 3001,
   "documented": "3002",
   "name": "Heat meter htg total kWh",
   "description": "Total heat for heating, kWh part (0-999).",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "kWh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 3002,
   "documented": "3003",
   "name": "Heat meter htg total MWh",
   "description": "Total heat for heating, MWh part.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "MWh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 3003,
   "documented": "3004",
   "name": "Heat meter DHW day",
   "description": "Heat delivered for DHW today.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "kWh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 3004,
   "documented": "3005",
   "name": "Heat meter DHW total kWh",
   "description": "Total heat for DHW, kWh part.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "kWh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 3005,
   "documented": "3006",
   "name": "Heat meter DHW total MWh",
   "description": "Total heat for DHW, MWh part.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "MWh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 3006,
   "documented": "3007",
   "name": "Heat M boost htg total kWh",
   "description": "Heat from the electric booster for heating, kWh part.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "kWh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 3007,
   "documented": "3008",
   "name": "Heat M boost htg total MWh",
   "description": "Heat from the electric booster for heating, MWh part.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "MWh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 3008,
   "documented": "3009",
   "name": "Heat M boost DHW total kWh",
   "description": "Heat from the electric booster for DHW, kWh part.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "kWh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 3009,
   "documented": "3010",
   "name": "Heat M boost DHW total MWh",
   "description": "Heat from the electric booster for DHW, MWh part.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "MWh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 3010,
   "documented": "3011",
   "name": "Heat M recovery day",
   "description": "Heat recovered by the heat exchanger today.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "kWh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 3011,
   "documented": "3012",
   "name": "Heat M recovery total kWh",
   "description": "Total recovered heat, kWh part.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "kWh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 3012,
   "documented": "3013",
   "name": "Heat M recovery total MWh",
   "description": "Total recovered heat, MWh part.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "MWh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 3013,
   "documented": "3014",
   "name": "HM solar htg day",
   "description": "Solar heat for heating today; solar units only.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "kWh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 3014,
   "documented": "3015",
   "name": "HM solar htg total kWh",
   "description": "Solar heat for heating, kWh part; solar units only.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "kWh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 3015,
   "documented": "3016",
   "name": "HM solar htg total MWh",
   "description": "Solar heat for heating, MWh part; solar units only.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "MWh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 3016,
   "documented": "3017",
   "name": "HM solar DHW day",
   "description": "Solar heat for DHW today; solar units only.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "kWh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 3017,
   "documented": "3018",
   "name": "HM solar DHW total kWh",
   "description": "Solar heat for DHW, kWh part; solar units only.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "kWh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 3018,
   "documented": "3019",
   "name": "HM solar DHW total MWh",
   "description": "Solar heat for DHW, MWh part; solar units only.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "MWh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 3019,
   "documented": "3020",
   "name": "HM cooling total kWh",
   "description": "Cooling energy, kWh part; units with cooling only.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "kWh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 3020,
   "documented": "3021",
   "name": "HM cooling total MWh",
   "description": "Cooling energy, MWh part; units with cooling only.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "MWh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 3021,
   "documented": "3022",
   "name": "Pwr con htg day",
   "description": "Electricity used for heating today.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "kWh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 3022,
   "documented": "3023",
   "name": "Pwr con htg total kWh",
   "description": "Electricity used for heating, kWh part.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "kWh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 3023,
   "documented": "3024",
   "name": "Pwr con htg total MWh",
   "description": "Electricity used for heating, MWh part.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "MWh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 3024,
   "documented": "3025",
   "name": "Pwr con DHW day",
   "description": "Electricity used for DHW today.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "kWh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 3025,
   "documented": "3026",
   "name": "Pwr con DHW total kWh",
   "description": "Electricity used for DHW, kWh part.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "kWh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 3026,
   "documented": "3027",
   "name": "Pwr con DHW total MWh",
   "description": "Electricity used for DHW, MWh part.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "MWh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 3027,
   "documented": "3028",
   "name": "Compressor heating hours",
   "description": "Compressor operating hours in heating.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "h",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 3028,
   "documented": "3029",
   "name": "Compressor cooling hours",
   "description": "Compressor operating hours in cooling; units with cooling only.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "h",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 3029,
   "documented": "3030",
   "name": "Compressor DHW hours",
   "description": "Compressor operating hours in DHW mode.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "h",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 3030,
   "documented": "3031",
   "name": "Elec booster heating hours",
   "description": "Electric booster operating hours for heating.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "h",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 3031,
   "documented": "3032",
   "name": "Elec booster DHW hours",
   "description": "Electric booster operating hours for DHW.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "h",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 5000,
   "documented": "5001",
   "name": "SG Ready operating state",
   "description": "Resulting SG Ready state 1-4.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": {
    "1": "State 1: heating must not start, frost protection only",
    "2": "State 2: normal automatic/programmed operation",
    "3": "State 3: accelerated mode with raised heating/DHW setpoints",
    "4": "State 4: immediate switch to maximum heating/DHW setpoints"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 5001,
   "documented": "5002",
   "name": "Controller identification",
   "description": "Type code of the connected controller.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": {
    "103": "LWZ 303/403 Integral/SOL, LWA 403, LWZ 304/404 Trend/FLEX, LWZ Smart, LWZ 604 Air, LWZ 5 S Plus/Trend/Smart, LWZ 8 S Trend",
    "104": "LWZ 304/404 SOL, LWZ 504, LWZ 5/8 CS Premium, VCR-I 8 CS Premium CN",
    "390": "WPM 3",
    "391": "WPM 3i",
    "449": "WPMsystem"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1000,
   "documented": "1001",
   "name": "Operating mode",
   "description": "Selects the unit operating mode.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Emergency operation",
    "1": "Standby",
    "3": "Day mode",
    "4": "Setback mode",
    "5": "DHW",
    "11": "Automatic",
    "14": "Manual mode"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1001,
   "documented": "1002",
   "name": "Room temperature day HC1",
   "description": "Day (comfort) room heating setpoint, heating circuit 1.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "scale_factor_ref": null,
   "units": "°C",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1002,
   "documented": "1003",
   "name": "Room temp. night HC1",
   "description": "Night (setback) room heating setpoint, heating circuit 1.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "scale_factor_ref": null,
   "units": "°C",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1003,
   "documented": "1004",
   "name": "Manual set HC1",
   "description": "Heating circuit 1 setpoint in manual mode.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "scale_factor_ref": null,
   "units": "°C",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1004,
   "documented": "1005",
   "name": "Room temperature day HC2",
   "description": "Day room heating setpoint, heating circuit 2.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "scale_factor_ref": null,
   "units": "°C",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1005,
   "documented": "1006",
   "name": "Room temp. night HC2",
   "description": "Night room heating setpoint, heating circuit 2.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "scale_factor_ref": null,
   "units": "°C",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1006,
   "documented": "1007",
   "name": "Manual set HC2",
   "description": "Heating circuit 2 setpoint in manual mode.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "scale_factor_ref": null,
   "units": "°C",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1007,
   "documented": "1008",
   "name": "Gradient HC1",
   "description": "Heating curve slope, heating circuit 1.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1008,
   "documented": "1009",
   "name": "Low end HC1",
   "description": "Heating curve base point, heating circuit 1.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "scale_factor_ref": null,
   "units": "°C",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1009,
   "documented": "1010",
   "name": "Gradient HC2",
   "description": "Heating curve slope, heating circuit 2.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1010,
   "documented": "1011",
   "name": "Low end HC2",
   "description": "Heating curve base point, heating circuit 2.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "scale_factor_ref": null,
   "units": "°C",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1011,
   "documented": "1012",
   "name": "DHW set day",
   "description": "Day hot water setpoint.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "scale_factor_ref": null,
   "units": "°C",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1012,
   "documented": "1013",
   "name": "DHW set night",
   "description": "Night hot water setpoint.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "scale_factor_ref": null,
   "units": "°C",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1013,
   "documented": "1014",
   "name": "DHW set manual",
   "description": "Hot water setpoint in manual mode.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "scale_factor_ref": null,
   "units": "°C",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1014,
   "documented": "1015",
   "name": "MWM set day",
   "description": "Mixed water volume setpoint, day; LWZ 504 only.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "l",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1015,
   "documented": "1016",
   "name": "MWM set night",
   "description": "Mixed water volume setpoint, night; LWZ 504 only.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "l",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1016,
   "documented": "1017",
   "name": "MWM set manual",
   "description": "Mixed water volume setpoint, manual mode; LWZ 504 only.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "l",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1017,
   "documented": "1018",
   "name": "Day stage",
   "description": "Ventilation fan stage in day mode (0-3).",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1018,
   "documented": "1019",
   "name": "Night stage",
   "description": "Ventilation fan stage in night mode (0-3).",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1019,
   "documented": "1020",
   "name": "Party stage",
   "description": "Ventilation fan stage in party mode (0-3).",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1020,
   "documented": "1021",
   "name": "Manual stage",
   "description": "Ventilation fan stage in manual mode (0-3).",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1021,
   "documented": "1022",
   "name": "Room temperature day HC1 cooling",
   "description": "Day room cooling setpoint, HC 1; units with cooling only.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "scale_factor_ref": null,
   "units": "°C",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1022,
   "documented": "1023",
   "name": "Room temp. night HC1 cooling",
   "description": "Night room cooling setpoint, HC 1; units with cooling only.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "scale_factor_ref": null,
   "units": "°C",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1023,
   "documented": "1024",
   "name": "Room temperature day HC2 cooling",
   "description": "Day room cooling setpoint, HC 2; units with cooling only.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "scale_factor_ref": null,
   "units": "°C",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1024,
   "documented": "1025",
   "name": "Room temp. night HC2 cooling",
   "description": "Night room cooling setpoint, HC 2; units with cooling only.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "scale_factor_ref": null,
   "units": "°C",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1025,
   "documented": "1026",
   "name": "Reset",
   "description": "Reset command; LWZ 504 only.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Off",
    "1": "On"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1026,
   "documented": "1027",
   "name": "Restart ISG",
   "description": "ISG restart command; codes as published.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Off",
    "1": "Reset",
    "2": "Menu"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 4000,
   "documented": "4001",
   "name": "Switch SG Ready on and off",
   "description": "Enables or disables SG Ready. Language tables disagree on which code means on; check on site.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 4001,
   "documented": "4002",
   "name": "SG Ready input 1",
   "description": "Virtual SG Ready contact written by the BMS.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Switched off",
    "1": "Switched on"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 4002,
   "documented": "4003",
   "name": "SG Ready input 2",
   "description": "Virtual SG Ready contact written by the BMS.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Switched off",
    "1": "Switched on"
   },
   "bits": null,
   "offset": 0
  }
 ],
 "integration": {
  "summary": "Poll the ISG on TCP port 502, unit ID 1. Read input registers (FC 04) for temperatures, fan speeds, status flags 2001 and fault status 2002; write holding registers (FC 06/16) for operating mode 1001, room/DHW setpoints and the ventilation stages 1018-1021. Subtract 1 from every printed register number.",
  "minimum_registers": [
   {
    "table": "input_register",
    "address": 6,
    "why": "Outside temperature (offset check)"
   },
   {
    "table": "input_register",
    "address": 15,
    "why": "Actual DHW temperature"
   },
   {
    "table": "input_register",
    "address": 0,
    "why": "Actual room temperature HC1"
   },
   {
    "table": "input_register",
    "address": 2000,
    "why": "Operating status flags"
   },
   {
    "table": "input_register",
    "address": 2001,
    "why": "Fault status"
   },
   {
    "table": "holding_register",
    "address": 1000,
    "why": "Operating mode"
   },
   {
    "table": "holding_register",
    "address": 1001,
    "why": "Day room setpoint HC1"
   },
   {
    "table": "holding_register",
    "address": 1017,
    "why": "Ventilation day stage"
   }
  ],
  "enable": "The ISG web or ISG plus needs the Modbus TCP/IP software extension and, for the ISG web, the Basic service package. With an integral ventilation unit connected, check for it in SERVICEWELT under DIAGNOSIS > BUS SUBSCRIBER > ISG; if Modbus TCP/IP is not listed, update the ISG firmware or contact Stiebel Eltron service.",
  "watchdog": null,
  "quirks": [
   "All points are 16-bit; totals use paired kWh/MWh registers.",
   "Operating mode codes are not contiguous: 11 = automatic, 14 = manual.",
   "Faults cannot be acknowledged over Modbus, only in SERVICEWELT.",
   "The Modbus interface cannot run alongside other ISG software interfaces (read-only use with EMI excepted)."
  ],
  "setup": [
   "Default ISG IP 192.168.0.126 on a direct PC link; DHCP behind a router. Change it on the Profile tab in SERVICEWELT.",
   "Unit ID fixed at 1, port 502."
  ],
  "gotchas": [
   "Do not run the ISG on the same CAN bus as a DCo-aktiv GSM module."
  ]
 },
 "page": "https://easymodbus.com/modbus-register-maps/stiebel-eltron/isg-modbus-lwz-ventilation-units",
 "address_note": "address = 0-based Modbus wire (PDU) address; documented = as printed in the source.",
 "note": "Re-typed from the manufacturer's public documentation (see source) and verified against it. Registers vary by firmware and options; verify against the live device before writing."
}