 "manufacturer": "Stiebel Eltron",
 "manufacturer_slug": "stiebel-eltron",
 "model": "Heat pumps with WPM controller via ISG Modbus TCP/IP (WPMsystem, WPM 3, WPM 3i)",
 "model_slug": "isg-modbus-wpm-heat-pumps",
 "short_model": "ISG Modbus WPM",
 "aliases": [
  "ISG web Modbus TCP/IP",
  "ISG plus Modbus TCP/IP",
  "WPMsystem",
  "WPM 3",
  "WPM 3i"
 ],
 "equipment_type": "Heat pump (via ISG Modbus TCP gateway)",
 "applies_to": "Stiebel Eltron heat pumps run by a WPMsystem, WPM 3 or WPM 3i manager, reached through an ISG web (229336) or ISG plus (233493) with the Modbus TCP/IP software extension.",
 "summary": "Stiebel Eltron heat pumps are not polled directly: the Internet Service Gateway (ISG) with the paid Modbus TCP/IP extension acts as a Modbus TCP server for the WPM heat pump manager behind it. All data points are single 16-bit registers with a fixed scaling per data type. This map covers the WPM system values (input registers 501-608), the writable operating mode and setpoints (holding 1501-1521), status flags and output states (2501-2547), heat and energy counters per system and per heat pump (3501-3655), and the shared SG Ready registers (4001-4003, 5001-5002).",
 "transport": [
  "TCP"
 ],
 "defaults": {
  "unit_id": 1,
  "baud": null,
  "parity": null,
  "data_bits": null,
  "stop_bits": null,
  "tcp_port": 502
 },
 "addressing": {
  "convention": "1-based",
  "note": "The document states that ISG addressing is 1-based and gives the example that register 30501 is reached as address 501 with function code 04, so the wire address is the printed number minus one: outside temperature, printed 507, is requested at input register address 506. The document also warns that, depending on the configuration, an offset of 1 may have to be allowed for, so check outside temperature against the controller display first."
 },
 "default_word_order": null,
 "firmware": null,
 "source": {
  "title": "Software documentation - Software extension for Internet Service Gateway - Modbus TCP/IP",
  "doc_number": "A 321798-44755-9770",
  "revision_date": null,
  "url": "https://www.heizungsdiscount24.de/pdf/Stiebel-Eltron-Internet-Service-Gateway-ISG-Connect-Software-Dokumentation.pdf",
  "pages": "English section PDF pp. 25-40 (printed pp. 24-39): data types p. 26, addressing note p. 27, WPM tables pp. 27-35, SG Ready pp. 38-39. German original PDF pp. 3-18 cross-checked.",
  "unofficial": true
 },
 "notes": [
  "Stiebel Eltron does not host this software documentation publicly (its own download path for it returns 404). The linked copy is a retailer mirror: the multilingual Stiebel Eltron document unchanged, with one shop cover page added in front, so PDF page numbers are one higher than the printed page numbers.",
  "Data types from the document: type 2 = signed, value x 0.1 (temperatures, most pressures and flows); type 6 = unsigned 0-65535, x 1; type 7 = signed, value x 0.01; type 8 = unsigned 0-255, x 1. Write by sending the engineering value divided by the same factor (20.3 °C -> 203).",
  "Unavailable objects return 32768 (0x8000). Not every object exists on every controller; the WPMsystem / WPM 3 / WPM 3i columns are noted in descriptions where a register is not listed for all three.",
  "Energy counters are split into a kWh register (0-999) and an MWh register: total = MWh x 1000 + kWh. Day counters are single kWh registers.",
  "Registers 524-527 and 532 (cooling and external heat source temperatures) are printed with the unit K in both the German and English tables; they are kept as published.",
  "Left out: BUS-STATUS (2505) because it is typed as unsigned 0-65535 while its codes are negative (-1 to -4).",
  "SG Ready on/off (4001): the language tables of the same document disagree on the coding (German and Italian: 0 = off, 1 = on; English: 0 = on, 1 = off). No value labels are given here; test on site which code switches the function on.",
  "Holding register 1508 (fixed value operation) accepts 20-70 °C; writing 0x9000 turns the function off. The document says this works on WPMsystem, WPM 3 from software 39005 and WPM 3i from software 39106; older software can only activate and adjust it.",
  "Integral ventilation units (LWZ/LWA) use a different register set and are mapped separately (stiebel-eltron/isg-modbus-lwz-ventilation-units)."
 ],
 "registers": [
  {
   "table": "input_register",
   "address": 500,
   "documented": "501",
   "name": "Actual temperature FE7",
   "description": "Room temperature measured by an FE7 remote control.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "scale_factor_ref": null,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 501,
   "documented": "502",
   "name": "Set temperature FE7",
   "description": "Room setpoint at the FE7 remote control.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "scale_factor_ref": null,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 502,
   "documented": "503",
   "name": "Actual temperature FEK",
   "description": "Room temperature measured by an FEK remote control. Listed for WPM 3 and WPM 3i.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "scale_factor_ref": null,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 503,
   "documented": "504",
   "name": "Set temperature FEK",
   "description": "Room setpoint at the FEK remote control. Listed for WPM 3 and WPM 3i.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "scale_factor_ref": null,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 504,
   "documented": "505",
   "name": "Relative humidity",
   "description": "Room humidity from the FEK remote control. Listed for WPM 3 and WPM 3i.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "scale_factor_ref": null,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 505,
   "documented": "506",
   "name": "Dew point temperature",
   "description": "Room dew point from the FEK remote control. Listed for WPM 3 and WPM 3i.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "scale_factor_ref": null,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 506,
   "documented": "507",
   "name": "Outside temperature",
   "description": "Outdoor air temperature sensor.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "scale_factor_ref": null,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 507,
   "documented": "508",
   "name": "Actual temperature HK 1",
   "description": "Heating circuit 1 actual temperature.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "scale_factor_ref": null,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 508,
   "documented": "509",
   "name": "Set temperature HK 1 (WPM 3i)",
   "description": "Heating circuit 1 setpoint as reported by a WPM 3i. Listed for WPM 3i.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "scale_factor_ref": null,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 509,
   "documented": "510",
   "name": "Set temperature HK 1",
   "description": "Heating circuit 1 setpoint. Listed for WPMsystem and WPM 3.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "scale_factor_ref": null,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 510,
   "documented": "511",
   "name": "Actual temperature HK 2",
   "description": "Heating circuit 2 actual temperature.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "scale_factor_ref": null,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 511,
   "documented": "512",
   "name": "Set temperature HK 2",
   "description": "Heating circuit 2 setpoint.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "scale_factor_ref": null,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 512,
   "documented": "513",
   "name": "Actual flow temperature WP",
   "description": "Heat pump flow temperature, if a flow sensor (MFG) is fitted.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "scale_factor_ref": null,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 513,
   "documented": "514",
   "name": "Actual flow temperature NHZ",
   "description": "Flow temperature after the booster heater, if an MFG is fitted.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "scale_factor_ref": null,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 514,
   "documented": "515",
   "name": "Actual flow temperature",
   "description": "System flow temperature.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "scale_factor_ref": null,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 515,
   "documented": "516",
   "name": "Actual return temperature",
   "description": "System return temperature.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "scale_factor_ref": null,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 516,
   "documented": "517",
   "name": "Set fixed temperature",
   "description": "Setpoint used in fixed-value operation.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "scale_factor_ref": null,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 517,
   "documented": "518",
   "name": "Actual buffer temperature",
   "description": "Buffer cylinder temperature.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "scale_factor_ref": null,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 518,
   "documented": "519",
   "name": "Set buffer temperature",
   "description": "Buffer cylinder setpoint.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "scale_factor_ref": null,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 519,
   "documented": "520",
   "name": "Heating pressure",
   "description": "Heating water pressure, if a flow sensor (MFG) is fitted.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "scale_factor_ref": null,
   "units": "bar",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 520,
   "documented": "521",
   "name": "Flow rate",
   "description": "Heating water flow rate, if an MFG is fitted.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "scale_factor_ref": null,
   "units": "l/min",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 521,
   "documented": "522",
   "name": "Actual DHW temperature",
   "description": "Domestic hot water cylinder temperature.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "scale_factor_ref": null,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 522,
   "documented": "523",
   "name": "Set DHW temperature",
   "description": "Domestic hot water setpoint.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "scale_factor_ref": null,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 523,
   "documented": "524",
   "name": "Actual temperature fan cooling",
   "description": "Fan-convector cooling actual value (unit printed as K).",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "scale_factor_ref": null,
   "units": "K",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 524,
   "documented": "525",
   "name": "Set temperature fan cooling",
   "description": "Fan-convector cooling setpoint (unit printed as K).",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "scale_factor_ref": null,
   "units": "K",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 525,
   "documented": "526",
   "name": "Actual temperature area cooling",
   "description": "Surface cooling actual value (unit printed as K).",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "scale_factor_ref": null,
   "units": "K",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 526,
   "documented": "527",
   "name": "Set temperature area cooling",
   "description": "Surface cooling setpoint (unit printed as K).",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "scale_factor_ref": null,
   "units": "K",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 527,
   "documented": "528",
   "name": "Collector temperature",
   "description": "Solar thermal collector temperature. Listed for WPM 3.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "scale_factor_ref": null,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 528,
   "documented": "529",
   "name": "Cylinder temperature (solar)",
   "description": "Solar cylinder temperature. Listed for WPM 3.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "scale_factor_ref": null,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 529,
   "documented": "530",
   "name": "Runtime solar",
   "description": "Solar thermal operating hours. Listed for WPM 3.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "h",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 530,
   "documented": "531",
   "name": "Actual temperature external heat source",
   "description": "External (second) heat source actual temperature. Listed for WPMsystem and WPM 3.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "scale_factor_ref": null,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 531,
   "documented": "532",
   "name": "Set temperature external heat source",
   "description": "External heat source setpoint (unit printed as K). Listed for WPMsystem and WPM 3.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "scale_factor_ref": null,
   "units": "K",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 532,
   "documented": "533",
   "name": "Application limit HZG",
   "description": "Lower application limit for heating.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "scale_factor_ref": null,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 533,
   "documented": "534",
   "name": "Application limit WW",
   "description": "Lower application limit for DHW.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "scale_factor_ref": null,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 534,
   "documented": "535",
   "name": "Runtime external heat source",
   "description": "External heat source operating hours. Listed for WPMsystem and WPM 3.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "h",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 535,
   "documented": "536",
   "name": "Source temperature",
   "description": "Heat source (brine/air) temperature.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "scale_factor_ref": null,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 536,
   "documented": "537",
   "name": "Min source temperature",
   "description": "Minimum permitted source temperature.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "scale_factor_ref": null,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 537,
   "documented": "538",
   "name": "Source pressure",
   "description": "Heat source circuit pressure.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "scale_factor_ref": null,
   "units": "bar",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 538,
   "documented": "539",
   "name": "Hot gas temperature",
   "description": "Compressor discharge temperature. Listed for WPM 3i.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "scale_factor_ref": null,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 539,
   "documented": "540",
   "name": "High pressure",
   "description": "Refrigerant high pressure. Listed for WPM 3i.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "scale_factor_ref": null,
   "units": "bar",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 540,
   "documented": "541",
   "name": "Low pressure",
   "description": "Refrigerant low pressure. Listed for WPM 3i.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "scale_factor_ref": null,
   "units": "bar",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 541,
   "documented": "542",
   "name": "Return temperature HP 1",
   "description": "Heat pump 1 return temperature. Listed for WPMsystem and WPM 3.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "scale_factor_ref": null,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 542,
   "documented": "543",
   "name": "Flow temperature HP 1",
   "description": "Heat pump 1 flow temperature. Listed for WPMsystem and WPM 3.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "scale_factor_ref": null,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 543,
   "documented": "544",
   "name": "Hot gas temperature HP 1",
   "description": "Heat pump 1 compressor discharge temperature. Listed for WPMsystem and WPM 3.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "scale_factor_ref": null,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 544,
   "documented": "545",
   "name": "Low pressure HP 1",
   "description": "Heat pump 1 refrigerant low pressure. Listed for WPMsystem and WPM 3.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "scale_factor_ref": null,
   "units": "bar",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 545,
   "documented": "546",
   "name": "Mean pressure HP 1",
   "description": "Heat pump 1 refrigerant mean pressure. Listed for WPMsystem and WPM 3.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "scale_factor_ref": null,
   "units": "bar",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 546,
   "documented": "547",
   "name": "High pressure HP 1",
   "description": "Heat pump 1 refrigerant high pressure. Listed for WPMsystem and WPM 3.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "scale_factor_ref": null,
   "units": "bar",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 547,
   "documented": "548",
   "name": "WP water flow rate HP 1",
   "description": "Heat pump 1 water flow rate. Listed for WPMsystem and WPM 3.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "scale_factor_ref": null,
   "units": "l/min",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 548,
   "documented": "549",
   "name": "Return temperature HP 2",
   "description": "Heat pump 2 return temperature. Listed for WPMsystem and WPM 3.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "scale_factor_ref": null,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 549,
   "documented": "550",
   "name": "Flow temperature HP 2",
   "description": "Heat pump 2 flow temperature. Listed for WPMsystem and WPM 3.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "scale_factor_ref": null,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 550,
   "documented": "551",
   "name": "Hot gas temperature HP 2",
   "description": "Heat pump 2 compressor discharge temperature. Listed for WPMsystem and WPM 3.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "scale_factor_ref": null,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 551,
   "documented": "552",
   "name": "Low pressure HP 2",
   "description": "Heat pump 2 refrigerant low pressure. Listed for WPMsystem and WPM 3.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "scale_factor_ref": null,
   "units": "bar",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 552,
   "documented": "553",
   "name": "Mean pressure HP 2",
   "description": "Heat pump 2 refrigerant mean pressure. Listed for WPMsystem and WPM 3.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "scale_factor_ref": null,
   "units": "bar",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 553,
   "documented": "554",
   "name": "High pressure HP 2",
   "description": "Heat pump 2 refrigerant high pressure. Listed for WPMsystem and WPM 3.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "scale_factor_ref": null,
   "units": "bar",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 554,
   "documented": "555",
   "name": "WP water flow rate HP 2",
   "description": "Heat pump 2 water flow rate. Listed for WPMsystem and WPM 3.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "scale_factor_ref": null,
   "units": "l/min",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 555,
   "documented": "556",
   "name": "Return temperature HP 3",
   "description": "Heat pump 3 return temperature. Listed for WPMsystem and WPM 3.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "scale_factor_ref": null,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 556,
   "documented": "557",
   "name": "Flow temperature HP 3",
   "description": "Heat pump 3 flow temperature. Listed for WPMsystem and WPM 3.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "scale_factor_ref": null,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 557,
   "documented": "558",
   "name": "Hot gas temperature HP 3",
   "description": "Heat pump 3 compressor discharge temperature. Listed for WPMsystem and WPM 3.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "scale_factor_ref": null,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 558,
   "documented": "559",
   "name": "Low pressure HP 3",
   "description": "Heat pump 3 refrigerant low pressure. Listed for WPMsystem and WPM 3.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "scale_factor_ref": null,
   "units": "bar",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 559,
   "documented": "560",
   "name": "Mean pressure HP 3",
   "description": "Heat pump 3 refrigerant mean pressure. Listed for WPMsystem and WPM 3.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "scale_factor_ref": null,
   "units": "bar",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 560,
   "documented": "561",
   "name": "High pressure HP 3",
   "description": "Heat pump 3 refrigerant high pressure. Listed for WPMsystem and WPM 3.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "scale_factor_ref": null,
   "units": "bar",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 561,
   "documented": "562",
   "name": "WP water flow rate HP 3",
   "description": "Heat pump 3 water flow rate. Listed for WPMsystem and WPM 3.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "scale_factor_ref": null,
   "units": "l/min",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 562,
   "documented": "563",
   "name": "Return temperature HP 4",
   "description": "Heat pump 4 return temperature. Listed for WPMsystem and WPM 3.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "scale_factor_ref": null,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 563,
   "documented": "564",
   "name": "Flow temperature HP 4",
   "description": "Heat pump 4 flow temperature. Listed for WPMsystem and WPM 3.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "scale_factor_ref": null,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 564,
   "documented": "565",
   "name": "Hot gas temperature HP 4",
   "description": "Heat pump 4 compressor discharge temperature. Listed for WPMsystem and WPM 3.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "scale_factor_ref": null,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 565,
   "documented": "566",
   "name": "Low pressure HP 4",
   "description": "Heat pump 4 refrigerant low pressure. Listed for WPMsystem and WPM 3.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "scale_factor_ref": null,
   "units": "bar",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 566,
   "documented": "567",
   "name": "Mean pressure HP 4",
   "description": "Heat pump 4 refrigerant mean pressure. Listed for WPMsystem and WPM 3.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "scale_factor_ref": null,
   "units": "bar",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 567,
   "documented": "568",
   "name": "High pressure HP 4",
   "description": "Heat pump 4 refrigerant high pressure. Listed for WPMsystem and WPM 3.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "scale_factor_ref": null,
   "units": "bar",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 568,
   "documented": "569",
   "name": "WP water flow rate HP 4",
   "description": "Heat pump 4 water flow rate. Listed for WPMsystem and WPM 3.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "scale_factor_ref": null,
   "units": "l/min",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 569,
   "documented": "570",
   "name": "Return temperature HP 5",
   "description": "Heat pump 5 return temperature. Listed for WPMsystem and WPM 3.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "scale_factor_ref": null,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 570,
   "documented": "571",
   "name": "Flow temperature HP 5",
   "description": "Heat pump 5 flow temperature. Listed for WPMsystem and WPM 3.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "scale_factor_ref": null,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 571,
   "documented": "572",
   "name": "Hot gas temperature HP 5",
   "description": "Heat pump 5 compressor discharge temperature. Listed for WPMsystem and WPM 3.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "scale_factor_ref": null,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 572,
   "documented": "573",
   "name": "Low pressure HP 5",
   "description": "Heat pump 5 refrigerant low pressure. Listed for WPMsystem and WPM 3.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "scale_factor_ref": null,
   "units": "bar",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 573,
   "documented": "574",
   "name": "Mean pressure HP 5",
   "description": "Heat pump 5 refrigerant mean pressure. Listed for WPMsystem and WPM 3.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "scale_factor_ref": null,
   "units": "bar",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 574,
   "documented": "575",
   "name": "High pressure HP 5",
   "description": "Heat pump 5 refrigerant high pressure. Listed for WPMsystem and WPM 3.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "scale_factor_ref": null,
   "units": "bar",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 575,
   "documented": "576",
   "name": "WP water flow rate HP 5",
   "description": "Heat pump 5 water flow rate. Listed for WPMsystem and WPM 3.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "scale_factor_ref": null,
   "units": "l/min",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 576,
   "documented": "577",
   "name": "Return temperature HP 6",
   "description": "Heat pump 6 return temperature. Listed for WPMsystem and WPM 3.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "scale_factor_ref": null,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 577,
   "documented": "578",
   "name": "Flow temperature HP 6",
   "description": "Heat pump 6 flow temperature. Listed for WPMsystem and WPM 3.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "scale_factor_ref": null,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 578,
   "documented": "579",
   "name": "Hot gas temperature HP 6",
   "description": "Heat pump 6 compressor discharge temperature. Listed for WPMsystem and WPM 3.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "scale_factor_ref": null,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 579,
   "documented": "580",
   "name": "Low pressure HP 6",
   "description": "Heat pump 6 refrigerant low pressure. Listed for WPMsystem and WPM 3.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "scale_factor_ref": null,
   "units": "bar",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 580,
   "documented": "581",
   "name": "Mean pressure HP 6",
   "description": "Heat pump 6 refrigerant mean pressure. Listed for WPMsystem and WPM 3.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "scale_factor_ref": null,
   "units": "bar",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 581,
   "documented": "582",
   "name": "High pressure HP 6",
   "description": "Heat pump 6 refrigerant high pressure. Listed for WPMsystem and WPM 3.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "scale_factor_ref": null,
   "units": "bar",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 582,
   "documented": "583",
   "name": "WP water flow rate HP 6",
   "description": "Heat pump 6 water flow rate. Listed for WPMsystem and WPM 3.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "scale_factor_ref": null,
   "units": "l/min",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 583,
   "documented": "584",
   "name": "Room actual temperature HC 1",
   "description": "Room temperature for heating circuit 1. Listed for WPMsystem.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "scale_factor_ref": null,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 584,
   "documented": "585",
   "name": "Room set temperature HC 1",
   "description": "Room setpoint for heating circuit 1. Listed for WPMsystem.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "scale_factor_ref": null,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 585,
   "documented": "586",
   "name": "Relative humidity HC 1",
   "description": "Room humidity for heating circuit 1. Listed for WPMsystem.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "scale_factor_ref": null,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 586,
   "documented": "587",
   "name": "Dew point temperature HC 1",
   "description": "Room dew point for heating circuit 1. Listed for WPMsystem.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "scale_factor_ref": null,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 587,
   "documented": "588",
   "name": "Room actual temperature HC 2",
   "description": "Room temperature for heating circuit 2. Listed for WPMsystem.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "scale_factor_ref": null,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 588,
   "documented": "589",
   "name": "Room set temperature HC 2",
   "description": "Room setpoint for heating circuit 2. Listed for WPMsystem.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "scale_factor_ref": null,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 589,
   "documented": "590",
   "name": "Relative humidity HC 2",
   "description": "Room humidity for heating circuit 2. Listed for WPMsystem.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "scale_factor_ref": null,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 590,
   "documented": "591",
   "name": "Dew point temperature HC 2",
   "description": "Room dew point for heating circuit 2. Listed for WPMsystem.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "scale_factor_ref": null,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 591,
   "documented": "592",
   "name": "Room actual temperature HC 3",
   "description": "Room temperature for heating circuit 3. Listed for WPMsystem.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "scale_factor_ref": null,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 592,
   "documented": "593",
   "name": "Room set temperature HC 3",
   "description": "Room setpoint for heating circuit 3. Listed for WPMsystem.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "scale_factor_ref": null,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 593,
   "documented": "594",
   "name": "Relative humidity HC 3",
   "description": "Room humidity for heating circuit 3. Listed for WPMsystem.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "scale_factor_ref": null,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 594,
   "documented": "595",
   "name": "Dew point temperature HC 3",
   "description": "Room dew point for heating circuit 3. Listed for WPMsystem.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "scale_factor_ref": null,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 595,
   "documented": "596",
   "name": "Room actual temperature HC 4",
   "description": "Room temperature for heating circuit 4. Listed for WPMsystem.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "scale_factor_ref": null,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 596,
   "documented": "597",
   "name": "Room set temperature HC 4",
   "description": "Room setpoint for heating circuit 4. Listed for WPMsystem.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "scale_factor_ref": null,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 597,
   "documented": "598",
   "name": "Relative humidity HC 4",
   "description": "Room humidity for heating circuit 4. Listed for WPMsystem.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "scale_factor_ref": null,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 598,
   "documented": "599",
   "name": "Dew point temperature HC 4",
   "description": "Room dew point for heating circuit 4. Listed for WPMsystem.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "scale_factor_ref": null,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 599,
   "documented": "600",
   "name": "Room actual temperature HC 5",
   "description": "Room temperature for heating circuit 5. Listed for WPMsystem.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "scale_factor_ref": null,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 600,
   "documented": "601",
   "name": "Room set temperature HC 5",
   "description": "Room setpoint for heating circuit 5. Listed for WPMsystem.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "scale_factor_ref": null,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 601,
   "documented": "602",
   "name": "Relative humidity HC 5",
   "description": "Room humidity for heating circuit 5. Listed for WPMsystem.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "scale_factor_ref": null,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 602,
   "documented": "603",
   "name": "Dew point temperature HC 5",
   "description": "Room dew point for heating circuit 5. Listed for WPMsystem.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "scale_factor_ref": null,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 603,
   "documented": "604",
   "name": "Room set temperature cooling circuit 1",
   "description": "Room cooling setpoint for cooling circuit 1. Listed for WPMsystem.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "scale_factor_ref": null,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 604,
   "documented": "605",
   "name": "Room set temperature cooling circuit 2",
   "description": "Room cooling setpoint for cooling circuit 2. Listed for WPMsystem.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "scale_factor_ref": null,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 605,
   "documented": "606",
   "name": "Room set temperature cooling circuit 3",
   "description": "Room cooling setpoint for cooling circuit 3. Listed for WPMsystem.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "scale_factor_ref": null,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 606,
   "documented": "607",
   "name": "Room set temperature cooling circuit 4",
   "description": "Room cooling setpoint for cooling circuit 4. Listed for WPMsystem.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "scale_factor_ref": null,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 607,
   "documented": "608",
   "name": "Room set temperature cooling circuit 5",
   "description": "Room cooling setpoint for cooling circuit 5. Listed for WPMsystem.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "scale_factor_ref": null,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 2500,
   "documented": "2501",
   "name": "Operating status",
   "description": "Packed system status flags.",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "0": "HC 1 pump",
    "1": "HC 2 pump",
    "2": "Heat-up program",
    "3": "NHZ stages running",
    "4": "HP in heating mode",
    "5": "HP in DHW mode",
    "6": "Compressor running",
    "7": "Summer mode active",
    "8": "Cooling mode active",
    "9": "At least one IWS in defrost mode",
    "10": "Silent mode 1 active",
    "11": "Silent mode 2 active (HP off)"
   },
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 2501,
   "documented": "2502",
   "name": "Power-off (utility release)",
   "description": "Utility (EVU) release flag; German original EVU-FREIGABE.",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "0": "Power-off (EVU release)"
   },
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 2502,
   "documented": "2503",
   "name": "Operating status compressors",
   "description": "Packed compressor, buffer pump and booster heater flags.",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "0": "Compressor 1",
    "1": "Compressor 2",
    "2": "Compressor 3",
    "3": "Compressor 4",
    "4": "Compressor 5",
    "5": "Compressor 6",
    "6": "Buffer charging pump 1",
    "7": "Buffer charging pump 2",
    "8": "Buffer charging pump 3",
    "9": "Buffer charging pump 4",
    "10": "Buffer charging pump 5",
    "11": "Buffer charging pump 6",
    "12": "NHZ 1",
    "13": "NHZ 2"
   },
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 2503,
   "documented": "2504",
   "name": "Fault status",
   "description": "1 = system fault present; acknowledge only via SERVICEWELT.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": {
    "0": "No fault",
    "1": "Fault"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 2505,
   "documented": "2506",
   "name": "Defrost initiated",
   "description": "1 = defrost has been started.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": {
    "0": "Off",
    "1": "Initiated"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 2506,
   "documented": "2507",
   "name": "Active error",
   "description": "Number of the active fault.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 2507,
   "documented": "2508",
   "name": "Message number",
   "description": "Number of the active message.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 2508,
   "documented": "2509",
   "name": "Heating circuit pump 1 status",
   "description": "Output state reported by the WPM: 0 = off, 1 = on.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 2509,
   "documented": "2510",
   "name": "Heating circuit pump 2 status",
   "description": "Output state reported by the WPM: 0 = off, 1 = on.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 2510,
   "documented": "2511",
   "name": "Heating circuit pump 3 status",
   "description": "Output state reported by the WPM: 0 = off, 1 = on.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 2511,
   "documented": "2512",
   "name": "Buffer charging pump 1 status",
   "description": "Output state reported by the WPM: 0 = off, 1 = on.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 2512,
   "documented": "2513",
   "name": "Buffer charging pump 2 status",
   "description": "Output state reported by the WPM: 0 = off, 1 = on.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 2513,
   "documented": "2514",
   "name": "DHW charging pump status",
   "description": "Output state reported by the WPM: 0 = off, 1 = on.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 2514,
   "documented": "2515",
   "name": "Source pump status",
   "description": "Output state reported by the WPM: 0 = off, 1 = on.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 2515,
   "documented": "2516",
   "name": "Fault output status",
   "description": "Output state reported by the WPM: 0 = off, 1 = on.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 2516,
   "documented": "2517",
   "name": "DHW circulation pump status",
   "description": "Output state reported by the WPM: 0 = off, 1 = on.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 2517,
   "documented": "2518",
   "name": "WE 2 DHW status",
   "description": "Output state reported by the WPM: 0 = off, 1 = on.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 2518,
   "documented": "2519",
   "name": "WE 2 heating status",
   "description": "Output state reported by the WPM: 0 = off, 1 = on.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 2519,
   "documented": "2520",
   "name": "Cooling mode status",
   "description": "Output state reported by the WPM: 0 = off, 1 = on.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 2520,
   "documented": "2521",
   "name": "Mixer open HC 2 status",
   "description": "Output state reported by the WPM: 0 = off, 1 = on.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 2521,
   "documented": "2522",
   "name": "Mixer close HC 2 status",
   "description": "Output state reported by the WPM: 0 = off, 1 = on.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 2522,
   "documented": "2523",
   "name": "Mixer open HC 3 status",
   "description": "Output state reported by the WPM: 0 = off, 1 = on.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 2523,
   "documented": "2524",
   "name": "Mixer close HC 3 status",
   "description": "Output state reported by the WPM: 0 = off, 1 = on.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 2524,
   "documented": "2525",
   "name": "NHZ 1 status",
   "description": "Output state reported by the WPM: 0 = off, 1 = on.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 2525,
   "documented": "2526",
   "name": "NHZ 2 status",
   "description": "Output state reported by the WPM: 0 = off, 1 = on.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 2526,
   "documented": "2527",
   "name": "NHZ 1/2 status",
   "description": "Output state reported by the WPM: 0 = off, 1 = on.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 2527,
   "documented": "2528",
   "name": "Heating circuit pump 4 status",
   "description": "Output state reported by the WPE extension: 0 = off, 1 = on.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 2528,
   "documented": "2529",
   "name": "Heating circuit pump 5 status",
   "description": "Output state reported by the WPE extension: 0 = off, 1 = on.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 2529,
   "documented": "2530",
   "name": "Buffer charging pump 3 status",
   "description": "Output state reported by the WPE extension: 0 = off, 1 = on.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 2530,
   "documented": "2531",
   "name": "Buffer charging pump 4 status",
   "description": "Output state reported by the WPE extension: 0 = off, 1 = on.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 2531,
   "documented": "2532",
   "name": "Buffer charging pump 5 status",
   "description": "Output state reported by the WPE extension: 0 = off, 1 = on.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 2532,
   "documented": "2533",
   "name": "Buffer charging pump 6 status",
   "description": "Output state reported by the WPE extension: 0 = off, 1 = on.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 2533,
   "documented": "2534",
   "name": "Diff. controller pump 1 status",
   "description": "Output state reported by the WPE extension: 0 = off, 1 = on.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 2534,
   "documented": "2535",
   "name": "Diff. controller pump 2 status",
   "description": "Output state reported by the WPE extension: 0 = off, 1 = on.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 2535,
   "documented": "2536",
   "name": "Pool pump primary status",
   "description": "Output state reported by the WPE extension: 0 = off, 1 = on.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 2536,
   "documented": "2537",
   "name": "Pool pump secondary status",
   "description": "Output state reported by the WPE extension: 0 = off, 1 = on.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 2537,
   "documented": "2538",
   "name": "Mixer open HC 4 status",
   "description": "Output state reported by the WPE extension: 0 = off, 1 = on.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 2538,
   "documented": "2539",
   "name": "Mixer close HC 4 status",
   "description": "Output state reported by the WPE extension: 0 = off, 1 = on.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 2539,
   "documented": "2540",
   "name": "Mixer open HC 5 status",
   "description": "Output state reported by the WPE extension: 0 = off, 1 = on.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 2540,
   "documented": "2541",
   "name": "Mixer close HC 5 status",
   "description": "Output state reported by the WPE extension: 0 = off, 1 = on.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 2541,
   "documented": "2542",
   "name": "Compressor 1 status",
   "description": "Output state reported by the heat pump: 0 = off, 1 = on.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 2542,
   "documented": "2543",
   "name": "Compressor 2 status",
   "description": "Output state reported by the heat pump: 0 = off, 1 = on.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 2543,
   "documented": "2544",
   "name": "Compressor 3 status",
   "description": "Output state reported by the heat pump: 0 = off, 1 = on.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 2544,
   "documented": "2545",
   "name": "Compressor 4 status",
   "description": "Output state reported by the heat pump: 0 = off, 1 = on.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 2545,
   "documented": "2546",
   "name": "Compressor 5 status",
   "description": "Output state reported by the heat pump: 0 = off, 1 = on.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 2546,
   "documented": "2547",
   "name": "Compressor 6 status",
   "description": "Output state reported by the heat pump: 0 = off, 1 = on.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 3500,
   "documented": "3501",
   "name": "VD HEATING DAY kWh heat all HPs",
   "description": "Today heat output for heating by compressor, all heat pumps.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "kWh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 3501,
   "documented": "3502",
   "name": "VD HEATING TOTAL kWh heat all HPs",
   "description": "Total heat output for heating by compressor, all heat pumps, kWh part.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "kWh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 3502,
   "documented": "3503",
   "name": "VD HEATING TOTAL MWh heat all HPs",
   "description": "Total heat output for heating by compressor, all heat pumps, MWh part.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "MWh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 3503,
   "documented": "3504",
   "name": "VD DHW DAY kWh heat all HPs",
   "description": "Today heat output for DHW by compressor, all heat pumps.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "kWh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 3504,
   "documented": "3505",
   "name": "VD DHW TOTAL kWh heat all HPs",
   "description": "Total heat output for DHW by compressor, all heat pumps, kWh part.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "kWh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 3505,
   "documented": "3506",
   "name": "VD DHW TOTAL MWh heat all HPs",
   "description": "Total heat output for DHW by compressor, all heat pumps, MWh part.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "MWh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 3506,
   "documented": "3507",
   "name": "NHZ HEATING TOTAL kWh heat all HPs",
   "description": "Total heat output for heating by booster heater, all heat pumps, kWh part.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "kWh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 3507,
   "documented": "3508",
   "name": "NHZ HEATING TOTAL MWh heat all HPs",
   "description": "Total heat output for heating by booster heater, all heat pumps, MWh part.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "MWh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 3508,
   "documented": "3509",
   "name": "NHZ DHW TOTAL kWh heat all HPs",
   "description": "Total heat output for DHW by booster heater, all heat pumps, kWh part.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "kWh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 3509,
   "documented": "3510",
   "name": "NHZ DHW TOTAL MWh heat all HPs",
   "description": "Total heat output for DHW by booster heater, all heat pumps, MWh part.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "MWh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 3510,
   "documented": "3511",
   "name": "VD HEATING DAY kWh power consumption all HPs",
   "description": "Today electricity used for heating by compressor, all heat pumps.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "kWh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 3511,
   "documented": "3512",
   "name": "VD HEATING TOTAL kWh power consumption all HPs",
   "description": "Total electricity used for heating by compressor, all heat pumps, kWh part.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "kWh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 3512,
   "documented": "3513",
   "name": "VD HEATING TOTAL MWh power consumption all HPs",
   "description": "Total electricity used for heating by compressor, all heat pumps, MWh part.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "MWh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 3513,
   "documented": "3514",
   "name": "VD DHW DAY kWh power consumption all HPs",
   "description": "Today electricity used for DHW by compressor, all heat pumps.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "kWh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 3514,
   "documented": "3515",
   "name": "VD DHW TOTAL kWh power consumption all HPs",
   "description": "Total electricity used for DHW by compressor, all heat pumps, kWh part.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "kWh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 3515,
   "documented": "3516",
   "name": "VD DHW TOTAL MWh power consumption all HPs",
   "description": "Total electricity used for DHW by compressor, all heat pumps, MWh part.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "MWh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 3516,
   "documented": "3517",
   "name": "Runtime VD HEATING",
   "description": "Operating hours, compressor heating.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "h",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 3517,
   "documented": "3518",
   "name": "Runtime VD DHW",
   "description": "Operating hours, compressor DHW.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "h",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 3518,
   "documented": "3519",
   "name": "Runtime VD COOLING",
   "description": "Operating hours, compressor cooling.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "h",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 3519,
   "documented": "3520",
   "name": "Runtime NHZ 1",
   "description": "Operating hours, booster heater 1.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "h",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 3520,
   "documented": "3521",
   "name": "Runtime NHZ 2",
   "description": "Operating hours, booster heater 2.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "h",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 3521,
   "documented": "3522",
   "name": "Runtime NHZ 1/2",
   "description": "Operating hours, booster heater 1/2.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "h",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 3522,
   "documented": "3523",
   "name": "VD HEATING DAY kWh heat HP 1",
   "description": "Today heat output for heating by compressor, heat pump 1.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "kWh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 3523,
   "documented": "3524",
   "name": "VD HEATING TOTAL kWh heat HP 1",
   "description": "Total heat output for heating by compressor, heat pump 1, kWh part.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "kWh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 3524,
   "documented": "3525",
   "name": "VD HEATING TOTAL MWh heat HP 1",
   "description": "Total heat output for heating by compressor, heat pump 1, MWh part.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "MWh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 3525,
   "documented": "3526",
   "name": "VD DHW DAY kWh heat HP 1",
   "description": "Today heat output for DHW by compressor, heat pump 1.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "kWh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 3526,
   "documented": "3527",
   "name": "VD DHW TOTAL kWh heat HP 1",
   "description": "Total heat output for DHW by compressor, heat pump 1, kWh part.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "kWh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 3527,
   "documented": "3528",
   "name": "VD DHW TOTAL MWh heat HP 1",
   "description": "Total heat output for DHW by compressor, heat pump 1, MWh part.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "MWh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 3528,
   "documented": "3529",
   "name": "NHZ HEATING TOTAL kWh heat HP 1",
   "description": "Total heat output for heating by booster heater, heat pump 1, kWh part.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "kWh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 3529,
   "documented": "3530",
   "name": "NHZ HEATING TOTAL MWh heat HP 1",
   "description": "Total heat output for heating by booster heater, heat pump 1, MWh part.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "MWh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 3530,
   "documented": "3531",
   "name": "NHZ DHW TOTAL kWh heat HP 1",
   "description": "Total heat output for DHW by booster heater, heat pump 1, kWh part.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "kWh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 3531,
   "documented": "3532",
   "name": "NHZ DHW TOTAL MWh heat HP 1",
   "description": "Total heat output for DHW by booster heater, heat pump 1, MWh part.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "MWh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 3532,
   "documented": "3533",
   "name": "VD HEATING DAY kWh power consumption HP 1",
   "description": "Today electricity used for heating by compressor, heat pump 1.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "kWh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 3533,
   "documented": "3534",
   "name": "VD HEATING TOTAL kWh power consumption HP 1",
   "description": "Total electricity used for heating by compressor, heat pump 1, kWh part.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "kWh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 3534,
   "documented": "3535",
   "name": "VD HEATING TOTAL MWh power consumption HP 1",
   "description": "Total electricity used for heating by compressor, heat pump 1, MWh part.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "MWh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 3535,
   "documented": "3536",
   "name": "VD DHW DAY kWh power consumption HP 1",
   "description": "Today electricity used for DHW by compressor, heat pump 1.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "kWh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 3536,
   "documented": "3537",
   "name": "VD DHW TOTAL kWh power consumption HP 1",
   "description": "Total electricity used for DHW by compressor, heat pump 1, kWh part.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "kWh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 3537,
   "documented": "3538",
   "name": "VD DHW TOTAL MWh power consumption HP 1",
   "description": "Total electricity used for DHW by compressor, heat pump 1, MWh part.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "MWh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 3538,
   "documented": "3539",
   "name": "Runtime VD 1 HEATING HP 1",
   "description": "Operating hours, compressor 1 heating, heat pump 1.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "h",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 3539,
   "documented": "3540",
   "name": "Runtime VD 2 HEATING HP 1",
   "description": "Operating hours, compressor 2 heating, heat pump 1.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "h",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 3540,
   "documented": "3541",
   "name": "Runtime VD 1/2 HEATING HP 1",
   "description": "Operating hours, compressor 1/2 heating, heat pump 1.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "h",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 3541,
   "documented": "3542",
   "name": "Runtime VD 1 DHW HP 1",
   "description": "Operating hours, compressor 1 DHW, heat pump 1.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "h",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 3542,
   "documented": "3543",
   "name": "Runtime VD 2 DHW HP 1",
   "description": "Operating hours, compressor 2 DHW, heat pump 1.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "h",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 3543,
   "documented": "3544",
   "name": "Runtime VD 1/2 DHW HP 1",
   "description": "Operating hours, compressor 1/2 DHW, heat pump 1.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "h",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 3544,
   "documented": "3545",
   "name": "Runtime VD COOLING HP 1",
   "description": "Operating hours, compressor cooling, heat pump 1.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "h",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 3545,
   "documented": "3546",
   "name": "Runtime NHZ 1 (booster heater)",
   "description": "Operating hours of booster heater stage 1.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "h",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 3546,
   "documented": "3547",
   "name": "Runtime NHZ 2 (booster heater)",
   "description": "Operating hours of booster heater stage 2.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "h",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 3547,
   "documented": "3548",
   "name": "Runtime NHZ 1/2 (booster heater)",
   "description": "Operating hours of booster heater stage 1/2.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "h",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 3548,
   "documented": "3549",
   "name": "VD HEATING DAY kWh heat HP 2",
   "description": "Today heat output for heating by compressor, heat pump 2.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "kWh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 3549,
   "documented": "3550",
   "name": "VD HEATING TOTAL kWh heat HP 2",
   "description": "Total heat output for heating by compressor, heat pump 2, kWh part.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "kWh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 3550,
   "documented": "3551",
   "name": "VD HEATING TOTAL MWh heat HP 2",
   "description": "Total heat output for heating by compressor, heat pump 2, MWh part.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "MWh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 3551,
   "documented": "3552",
   "name": "VD DHW DAY kWh heat HP 2",
   "description": "Today heat output for DHW by compressor, heat pump 2.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "kWh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 3552,
   "documented": "3553",
   "name": "VD DHW TOTAL kWh heat HP 2",
   "description": "Total heat output for DHW by compressor, heat pump 2, kWh part.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "kWh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 3553,
   "documented": "3554",
   "name": "VD DHW TOTAL MWh heat HP 2",
   "description": "Total heat output for DHW by compressor, heat pump 2, MWh part.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "MWh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 3554,
   "documented": "3555",
   "name": "VD HEATING DAY kWh power consumption HP 2",
   "description": "Today electricity used for heating by compressor, heat pump 2.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "kWh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 3555,
   "documented": "3556",
   "name": "VD HEATING TOTAL kWh power consumption HP 2",
   "description": "Total electricity used for heating by compressor, heat pump 2, kWh part.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "kWh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 3556,
   "documented": "3557",
   "name": "VD HEATING TOTAL MWh power consumption HP 2",
   "description": "Total electricity used for heating by compressor, heat pump 2, MWh part.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "MWh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 3557,
   "documented": "3558",
   "name": "VD DHW DAY kWh power consumption HP 2",
   "description": "Today electricity used for DHW by compressor, heat pump 2.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "kWh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 3558,
   "documented": "3559",
   "name": "VD DHW TOTAL kWh power consumption HP 2",
   "description": "Total electricity used for DHW by compressor, heat pump 2, kWh part.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "kWh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 3559,
   "documented": "3560",
   "name": "VD DHW TOTAL MWh power consumption HP 2",
   "description": "Total electricity used for DHW by compressor, heat pump 2, MWh part.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "MWh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 3560,
   "documented": "3561",
   "name": "Runtime VD 1 HEATING HP 2",
   "description": "Operating hours, compressor 1 heating, heat pump 2.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "h",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 3561,
   "documented": "3562",
   "name": "Runtime VD 2 HEATING HP 2",
   "description": "Operating hours, compressor 2 heating, heat pump 2.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "h",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 3562,
   "documented": "3563",
   "name": "Runtime VD 1/2 HEATING HP 2",
   "description": "Operating hours, compressor 1/2 heating, heat pump 2.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "h",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 3563,
   "documented": "3564",
   "name": "Runtime VD 1 DHW HP 2",
   "description": "Operating hours, compressor 1 DHW, heat pump 2.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "h",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 3564,
   "documented": "3565",
   "name": "Runtime VD 2 DHW HP 2",
   "description": "Operating hours, compressor 2 DHW, heat pump 2.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "h",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 3565,
   "documented": "3566",
   "name": "Runtime VD 1/2 DHW HP 2",
   "description": "Operating hours, compressor 1/2 DHW, heat pump 2.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "h",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 3566,
   "documented": "3567",
   "name": "Runtime VD COOLING HP 2",
   "description": "Operating hours, compressor cooling, heat pump 2.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "h",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 3567,
   "documented": "3568",
   "name": "VD HEATING DAY kWh heat HP 3",
   "description": "Today heat output for heating by compressor, heat pump 3.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "kWh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 3568,
   "documented": "3569",
   "name": "VD HEATING TOTAL kWh heat HP 3",
   "description": "Total heat output for heating by compressor, heat pump 3, kWh part.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "kWh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 3569,
   "documented": "3570",
   "name": "VD HEATING TOTAL MWh heat HP 3",
   "description": "Total heat output for heating by compressor, heat pump 3, MWh part.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "MWh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 3570,
   "documented": "3571",
   "name": "VD DHW DAY kWh heat HP 3",
   "description": "Today heat output for DHW by compressor, heat pump 3.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "kWh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 3571,
   "documented": "3572",
   "name": "VD DHW TOTAL kWh heat HP 3",
   "description": "Total heat output for DHW by compressor, heat pump 3, kWh part.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "kWh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 3572,
   "documented": "3573",
   "name": "VD DHW TOTAL MWh heat HP 3",
   "description": "Total heat output for DHW by compressor, heat pump 3, MWh part.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "MWh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 3573,
   "documented": "3574",
   "name": "VD HEATING DAY kWh power consumption HP 3",
   "description": "Today electricity used for heating by compressor, heat pump 3.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "kWh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 3574,
   "documented": "3575",
   "name": "VD HEATING TOTAL kWh power consumption HP 3",
   "description": "Total electricity used for heating by compressor, heat pump 3, kWh part.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "kWh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 3575,
   "documented": "3576",
   "name": "VD HEATING TOTAL MWh power consumption HP 3",
   "description": "Total electricity used for heating by compressor, heat pump 3, MWh part.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "MWh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 3576,
   "documented": "3577",
   "name": "VD DHW DAY kWh power consumption HP 3",
   "description": "Today electricity used for DHW by compressor, heat pump 3.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "kWh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 3577,
   "documented": "3578",
   "name": "VD DHW TOTAL kWh power consumption HP 3",
   "description": "Total electricity used for DHW by compressor, heat pump 3, kWh part.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "kWh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 3578,
   "documented": "3579",
   "name": "VD DHW TOTAL MWh power consumption HP 3",
   "description": "Total electricity used for DHW by compressor, heat pump 3, MWh part.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "MWh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 3579,
   "documented": "3580",
   "name": "Runtime VD 1 HEATING HP 3",
   "description": "Operating hours, compressor 1 heating, heat pump 3.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "h",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 3580,
   "documented": "3581",
   "name": "Runtime VD 2 HEATING HP 3",
   "description": "Operating hours, compressor 2 heating, heat pump 3.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "h",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 3581,
   "documented": "3582",
   "name": "Runtime VD 1/2 HEATING HP 3",
   "description": "Operating hours, compressor 1/2 heating, heat pump 3.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "h",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 3582,
   "documented": "3583",
   "name": "Runtime VD 1 DHW HP 3",
   "description": "Operating hours, compressor 1 DHW, heat pump 3.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "h",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 3583,
   "documented": "3584",
   "name": "Runtime VD 2 DHW HP 3",
   "description": "Operating hours, compressor 2 DHW, heat pump 3.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "h",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 3584,
   "documented": "3585",
   "name": "Runtime VD 1/2 DHW HP 3",
   "description": "Operating hours, compressor 1/2 DHW, heat pump 3.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "h",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 3585,
   "documented": "3586",
   "name": "Runtime VD COOLING HP 3",
   "description": "Operating hours, compressor cooling, heat pump 3.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "h",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 3586,
   "documented": "3587",
   "name": "VD HEATING DAY kWh heat HP 4",
   "description": "Today heat output for heating by compressor, heat pump 4.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "kWh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 3587,
   "documented": "3588",
   "name": "VD HEATING TOTAL kWh heat HP 4",
   "description": "Total heat output for heating by compressor, heat pump 4, kWh part.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "kWh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 3588,
   "documented": "3589",
   "name": "VD HEATING TOTAL MWh heat HP 4",
   "description": "Total heat output for heating by compressor, heat pump 4, MWh part.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "MWh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 3589,
   "documented": "3590",
   "name": "VD DHW DAY kWh heat HP 4",
   "description": "Today heat output for DHW by compressor, heat pump 4.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "kWh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 3590,
   "documented": "3591",
   "name": "VD DHW TOTAL kWh heat HP 4",
   "description": "Total heat output for DHW by compressor, heat pump 4, kWh part.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "kWh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 3591,
   "documented": "3592",
   "name": "VD DHW TOTAL MWh heat HP 4",
   "description": "Total heat output for DHW by compressor, heat pump 4, MWh part.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "MWh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 3592,
   "documented": "3593",
   "name": "VD HEATING DAY kWh power consumption HP 4",
   "description": "Today electricity used for heating by compressor, heat pump 4.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "kWh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 3593,
   "documented": "3594",
   "name": "VD HEATING TOTAL kWh power consumption HP 4",
   "description": "Total electricity used for heating by compressor, heat pump 4, kWh part.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "kWh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 3594,
   "documented": "3595",
   "name": "VD HEATING TOTAL MWh power consumption HP 4",
   "description": "Total electricity used for heating by compressor, heat pump 4, MWh part.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "MWh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 3595,
   "documented": "3596",
   "name": "VD DHW DAY kWh power consumption HP 4",
   "description": "Today electricity used for DHW by compressor, heat pump 4.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "kWh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 3596,
   "documented": "3597",
   "name": "VD DHW TOTAL kWh power consumption HP 4",
   "description": "Total electricity used for DHW by compressor, heat pump 4, kWh part.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "kWh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 3597,
   "documented": "3598",
   "name": "VD DHW TOTAL MWh power consumption HP 4",
   "description": "Total electricity used for DHW by compressor, heat pump 4, MWh part.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "MWh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 3598,
   "documented": "3599",
   "name": "Runtime VD 1 HEATING HP 4",
   "description": "Operating hours, compressor 1 heating, heat pump 4.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "h",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 3599,
   "documented": "3600",
   "name": "Runtime VD 2 HEATING HP 4",
   "description": "Operating hours, compressor 2 heating, heat pump 4.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "h",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 3600,
   "documented": "3601",
   "name": "Runtime VD 1/2 HEATING HP 4",
   "description": "Operating hours, compressor 1/2 heating, heat pump 4.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "h",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 3601,
   "documented": "3602",
   "name": "Runtime VD 1 DHW HP 4",
   "description": "Operating hours, compressor 1 DHW, heat pump 4.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "h",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 3602,
   "documented": "3603",
   "name": "Runtime VD 2 DHW HP 4",
   "description": "Operating hours, compressor 2 DHW, heat pump 4.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "h",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 3603,
   "documented": "3604",
   "name": "Runtime VD 1/2 DHW HP 4",
   "description": "Operating hours, compressor 1/2 DHW, heat pump 4.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "h",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 3604,
   "documented": "3605",
   "name": "Runtime VD COOLING HP 4",
   "description": "Operating hours, compressor cooling, heat pump 4.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "h",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 3605,
   "documented": "3606",
   "name": "VD HEATING DAY kWh heat HP 5",
   "description": "Today heat output for heating by compressor, heat pump 5.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "kWh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 3606,
   "documented": "3607",
   "name": "VD HEATING TOTAL kWh heat HP 5",
   "description": "Total heat output for heating by compressor, heat pump 5, kWh part.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "kWh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 3607,
   "documented": "3608",
   "name": "VD HEATING TOTAL MWh heat HP 5",
   "description": "Total heat output for heating by compressor, heat pump 5, MWh part.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "MWh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 3608,
   "documented": "3609",
   "name": "VD DHW DAY kWh heat HP 5",
   "description": "Today heat output for DHW by compressor, heat pump 5.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "kWh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 3609,
   "documented": "3610",
   "name": "VD DHW TOTAL kWh heat HP 5",
   "description": "Total heat output for DHW by compressor, heat pump 5, kWh part.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "kWh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 3610,
   "documented": "3611",
   "name": "VD DHW TOTAL MWh heat HP 5",
   "description": "Total heat output for DHW by compressor, heat pump 5, MWh part.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "MWh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 3611,
   "documented": "3612",
   "name": "VD HEATING DAY kWh power consumption HP 5",
   "description": "Today electricity used for heating by compressor, heat pump 5.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "kWh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 3612,
   "documented": "3613",
   "name": "VD HEATING TOTAL kWh power consumption HP 5",
   "description": "Total electricity used for heating by compressor, heat pump 5, kWh part.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "kWh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 3613,
   "documented": "3614",
   "name": "VD HEATING TOTAL MWh power consumption HP 5",
   "description": "Total electricity used for heating by compressor, heat pump 5, MWh part.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "MWh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 3614,
   "documented": "3615",
   "name": "VD DHW DAY kWh power consumption HP 5",
   "description": "Today electricity used for DHW by compressor, heat pump 5.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "kWh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 3615,
   "documented": "3616",
   "name": "VD DHW TOTAL kWh power consumption HP 5",
   "description": "Total electricity used for DHW by compressor, heat pump 5, kWh part.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "kWh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 3616,
   "documented": "3617",
   "name": "VD DHW TOTAL MWh power consumption HP 5",
   "description": "Total electricity used for DHW by compressor, heat pump 5, MWh part.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "MWh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 3617,
   "documented": "3618",
   "name": "Runtime VD 1 HEATING HP 5",
   "description": "Operating hours, compressor 1 heating, heat pump 5.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "h",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 3618,
   "documented": "3619",
   "name": "Runtime VD 2 HEATING HP 5",
   "description": "Operating hours, compressor 2 heating, heat pump 5.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "h",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 3619,
   "documented": "3620",
   "name": "Runtime VD 1/2 HEATING HP 5",
   "description": "Operating hours, compressor 1/2 heating, heat pump 5.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "h",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 3620,
   "documented": "3621",
   "name": "Runtime VD 1 DHW HP 5",
   "description": "Operating hours, compressor 1 DHW, heat pump 5.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "h",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 3621,
   "documented": "3622",
   "name": "Runtime VD 2 DHW HP 5",
   "description": "Operating hours, compressor 2 DHW, heat pump 5.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "h",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 3622,
   "documented": "3623",
   "name": "Runtime VD 1/2 DHW HP 5",
   "description": "Operating hours, compressor 1/2 DHW, heat pump 5.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "h",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 3623,
   "documented": "3624",
   "name": "Runtime VD COOLING HP 5",
   "description": "Operating hours, compressor cooling, heat pump 5.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "h",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 3624,
   "documented": "3625",
   "name": "VD HEATING DAY kWh heat HP 6",
   "description": "Today heat output for heating by compressor, heat pump 6.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "kWh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 3625,
   "documented": "3626",
   "name": "VD HEATING TOTAL kWh heat HP 6",
   "description": "Total heat output for heating by compressor, heat pump 6, kWh part.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "kWh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 3626,
   "documented": "3627",
   "name": "VD HEATING TOTAL MWh heat HP 6",
   "description": "Total heat output for heating by compressor, heat pump 6, MWh part.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "MWh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 3627,
   "documented": "3628",
   "name": "VD DHW DAY kWh heat HP 6",
   "description": "Today heat output for DHW by compressor, heat pump 6.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "kWh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 3628,
   "documented": "3629",
   "name": "VD DHW TOTAL kWh heat HP 6",
   "description": "Total heat output for DHW by compressor, heat pump 6, kWh part.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "kWh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 3629,
   "documented": "3630",
   "name": "VD DHW TOTAL MWh heat HP 6",
   "description": "Total heat output for DHW by compressor, heat pump 6, MWh part.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "MWh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 3630,
   "documented": "3631",
   "name": "VD HEATING DAY kWh power consumption HP 6",
   "description": "Today electricity used for heating by compressor, heat pump 6.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "kWh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 3631,
   "documented": "3632",
   "name": "VD HEATING TOTAL kWh power consumption HP 6",
   "description": "Total electricity used for heating by compressor, heat pump 6, kWh part.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "kWh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 3632,
   "documented": "3633",
   "name": "VD HEATING TOTAL MWh power consumption HP 6",
   "description": "Total electricity used for heating by compressor, heat pump 6, MWh part.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "MWh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 3633,
   "documented": "3634",
   "name": "VD DHW DAY kWh power consumption HP 6",
   "description": "Today electricity used for DHW by compressor, heat pump 6.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "kWh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 3634,
   "documented": "3635",
   "name": "VD DHW TOTAL kWh power consumption HP 6",
   "description": "Total electricity used for DHW by compressor, heat pump 6, kWh part.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "kWh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 3635,
   "documented": "3636",
   "name": "VD DHW TOTAL MWh power consumption HP 6",
   "description": "Total electricity used for DHW by compressor, heat pump 6, MWh part.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "MWh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 3636,
   "documented": "3637",
   "name": "Runtime VD 1 HEATING HP 6",
   "description": "Operating hours, compressor 1 heating, heat pump 6.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "h",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 3637,
   "documented": "3638",
   "name": "Runtime VD 2 HEATING HP 6",
   "description": "Operating hours, compressor 2 heating, heat pump 6.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "h",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 3638,
   "documented": "3639",
   "name": "Runtime VD 1/2 HEATING HP 6",
   "description": "Operating hours, compressor 1/2 heating, heat pump 6.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "h",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 3639,
   "documented": "3640",
   "name": "Runtime VD 1 DHW HP 6",
   "description": "Operating hours, compressor 1 DHW, heat pump 6.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "h",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 3640,
   "documented": "3641",
   "name": "Runtime VD 2 DHW HP 6",
   "description": "Operating hours, compressor 2 DHW, heat pump 6.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "h",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 3641,
   "documented": "3642",
   "name": "Runtime VD 1/2 DHW HP 6",
   "description": "Operating hours, compressor 1/2 DHW, heat pump 6.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "h",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 3642,
   "documented": "3643",
   "name": "Runtime VD COOLING HP 6",
   "description": "Operating hours, compressor cooling, heat pump 6.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "h",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 3643,
   "documented": "3644",
   "name": "Runtime VD HEATING HP 1",
   "description": "Operating hours, compressor heating, heat pump 1.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "h",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 3644,
   "documented": "3645",
   "name": "Runtime VD DHW HP 1",
   "description": "Operating hours, compressor DHW, heat pump 1.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "h",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 3645,
   "documented": "3646",
   "name": "Runtime VD HEATING HP 2",
   "description": "Operating hours, compressor heating, heat pump 2.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "h",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 3646,
   "documented": "3647",
   "name": "Runtime VD DHW HP 2",
   "description": "Operating hours, compressor DHW, heat pump 2.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "h",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 3647,
   "documented": "3648",
   "name": "Runtime VD HEATING HP 3",
   "description": "Operating hours, compressor heating, heat pump 3.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "h",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 3648,
   "documented": "3649",
   "name": "Runtime VD DHW HP 3",
   "description": "Operating hours, compressor DHW, heat pump 3.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "h",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 3649,
   "documented": "3650",
   "name": "Runtime VD HEATING HP 4",
   "description": "Operating hours, compressor heating, heat pump 4.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "h",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 3650,
   "documented": "3651",
   "name": "Runtime VD DHW HP 4",
   "description": "Operating hours, compressor DHW, heat pump 4.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "h",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 3651,
   "documented": "3652",
   "name": "Runtime VD HEATING HP 5",
   "description": "Operating hours, compressor heating, heat pump 5.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "h",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 3652,
   "documented": "3653",
   "name": "Runtime VD DHW HP 5",
   "description": "Operating hours, compressor DHW, heat pump 5.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "h",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 3653,
   "documented": "3654",
   "name": "Runtime VD HEATING HP 6",
   "description": "Operating hours, compressor heating, heat pump 6.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "h",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 3654,
   "documented": "3655",
   "name": "Runtime VD DHW HP 6",
   "description": "Operating hours, compressor DHW, heat pump 6.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "h",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 5000,
   "documented": "5001",
   "name": "SG Ready operating state",
   "description": "Resulting SG Ready state 1-4.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": {
    "1": "State 1: heating must not start, frost protection only",
    "2": "State 2: normal automatic/programmed operation",
    "3": "State 3: accelerated mode with raised heating/DHW setpoints",
    "4": "State 4: immediate switch to maximum heating/DHW setpoints"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 5001,
   "documented": "5002",
   "name": "Controller identification",
   "description": "Type code of the connected controller.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": {
    "103": "LWZ 303/403 Integral/SOL, LWA 403, LWZ 304/404 Trend/FLEX, LWZ Smart, LWZ 604 Air, LWZ 5 S Plus/Trend/Smart, LWZ 8 S Trend",
    "104": "LWZ 304/404 SOL, LWZ 504, LWZ 5/8 CS Premium, VCR-I 8 CS Premium CN",
    "390": "WPM 3",
    "391": "WPM 3i",
    "449": "WPMsystem"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1500,
   "documented": "1501",
   "name": "Operating mode",
   "description": "Selects the controller operating mode.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Emergency operation",
    "1": "Standby mode",
    "2": "Programmed operation",
    "3": "Comfort mode",
    "4": "ECO mode",
    "5": "DHW mode"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1501,
   "documented": "1502",
   "name": "Comfort temperature HC 1",
   "description": "Comfort room setpoint, heating circuit 1.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "scale_factor_ref": null,
   "units": "°C",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1502,
   "documented": "1503",
   "name": "ECO temperature HC 1",
   "description": "ECO (setback) room setpoint, heating circuit 1.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "scale_factor_ref": null,
   "units": "°C",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1503,
   "documented": "1504",
   "name": "Heating curve rise HC 1",
   "description": "Heating curve slope, heating circuit 1.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1504,
   "documented": "1505",
   "name": "Comfort temperature HC 2",
   "description": "Comfort room setpoint, heating circuit 2.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "scale_factor_ref": null,
   "units": "°C",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1505,
   "documented": "1506",
   "name": "ECO temperature HC 2",
   "description": "ECO room setpoint, heating circuit 2.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "scale_factor_ref": null,
   "units": "°C",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1506,
   "documented": "1507",
   "name": "Heating curve rise HC 2",
   "description": "Heating curve slope, heating circuit 2.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1507,
   "documented": "1508",
   "name": "Fixed value operation",
   "description": "Fixed flow setpoint 20-70 °C; 0x9000 switches the function off.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "scale_factor_ref": null,
   "units": "°C",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1508,
   "documented": "1509",
   "name": "Dual mode temp HZG",
   "description": "Bivalence point for heating; observe application limits.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "scale_factor_ref": null,
   "units": "°C",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1509,
   "documented": "1510",
   "name": "Comfort temperature DHW",
   "description": "Comfort hot water setpoint.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "scale_factor_ref": null,
   "units": "°C",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1510,
   "documented": "1511",
   "name": "ECO temperature DHW",
   "description": "ECO hot water setpoint.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "scale_factor_ref": null,
   "units": "°C",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1511,
   "documented": "1512",
   "name": "DHW stages",
   "description": "Heat pump stages used for DHW; respect the number fitted.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1512,
   "documented": "1513",
   "name": "Dual mode temp WW",
   "description": "Bivalence point for DHW.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "scale_factor_ref": null,
   "units": "°C",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1513,
   "documented": "1514",
   "name": "Set flow temperature area cooling",
   "description": "Flow setpoint for surface cooling.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "scale_factor_ref": null,
   "units": "°C",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1514,
   "documented": "1515",
   "name": "Flow temp hysteresis area cooling",
   "description": "Flow temperature hysteresis for surface cooling.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "scale_factor_ref": null,
   "units": "K",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1515,
   "documented": "1516",
   "name": "Set room temperature area cooling",
   "description": "Room setpoint for surface cooling.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "scale_factor_ref": null,
   "units": "°C",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1516,
   "documented": "1517",
   "name": "Set flow temperature fan cooling",
   "description": "Flow setpoint for fan-convector cooling.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "scale_factor_ref": null,
   "units": "°C",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1517,
   "documented": "1518",
   "name": "Flow temp hysteresis fan cooling",
   "description": "Flow temperature hysteresis for fan cooling.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "scale_factor_ref": null,
   "units": "K",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1518,
   "documented": "1519",
   "name": "Set room temperature fan cooling",
   "description": "Room setpoint for fan cooling.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "scale_factor_ref": null,
   "units": "°C",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1519,
   "documented": "1520",
   "name": "Reset",
   "description": "Resets the fault list, a heat pump, or the whole system.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "1": "System reset (factory reset, all settings lost)",
    "2": "Fault list reset",
    "3": "Heat pump reset"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1520,
   "documented": "1521",
   "name": "Restart ISG",
   "description": "Restarts the ISG or emulates the service key.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Off",
    "1": "Restart",
    "2": "Service key"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 4000,
   "documented": "4001",
   "name": "Switch SG Ready on and off",
   "description": "Enables or disables SG Ready. Language tables disagree on which code means on; check on site.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 4001,
   "documented": "4002",
   "name": "SG Ready input 1",
   "description": "Virtual SG Ready contact written by the BMS.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Switched off",
    "1": "Switched on"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 4002,
   "documented": "4003",
   "name": "SG Ready input 2",
   "description": "Virtual SG Ready contact written by the BMS.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Switched off",
    "1": "Switched on"
   },
   "bits": null,
   "offset": 0
  }
 ],
 "integration": {
  "summary": "Connect a Modbus TCP master to the ISG on port 502, unit ID 1, and read input registers with FC 04 and holding registers with FC 03/06/16. Remember the 1-based numbering: wire address = printed number - 1. Read outside temperature (507), flow/return (515/516), DHW actual/set (522/523), status flags (2501) and fault status (2504); write the operating mode (1501) and comfort/ECO setpoints (1502-1511).",
  "minimum_registers": [
   {
    "table": "input_register",
    "address": 506,
    "why": "Outside temperature (check offset)"
   },
   {
    "table": "input_register",
    "address": 514,
    "why": "Actual flow temperature"
   },
   {
    "table": "input_register",
    "address": 521,
    "why": "Actual DHW temperature"
   },
   {
    "table": "input_register",
    "address": 2500,
    "why": "Operating status flags"
   },
   {
    "table": "input_register",
    "address": 2503,
    "why": "Fault status"
   },
   {
    "table": "holding_register",
    "address": 1500,
    "why": "Operating mode"
   },
   {
    "table": "holding_register",
    "address": 1501,
    "why": "Comfort temperature HC 1"
   },
   {
    "table": "holding_register",
    "address": 1509,
    "why": "Comfort DHW setpoint"
   },
   {
    "table": "input_register",
    "address": 3502,
    "why": "Total compressor heating heat, MWh part"
   }
  ],
  "enable": "The ISG web or ISG plus needs the Modbus TCP/IP software extension and, for the ISG web, the Basic service package. With a WPM connected, check for the extension in SERVICEWELT under DIAGNOSIS > SYSTEM > ISG; if Modbus TCP/IP is not listed, update the ISG firmware or contact Stiebel Eltron service.",
  "watchdog": null,
  "quirks": [
   "All values are single 16-bit registers; there are no 32-bit values in this map. Totals are spread over a kWh and an MWh register.",
   "Faults can only be acknowledged in SERVICEWELT, not over Modbus.",
   "The Modbus interface cannot be combined with other ISG software interfaces, except read-only use alongside the EMI energy management extension.",
   "Change either the operating mode or the setpoints of a mode over Modbus and leave the other fixed, so new setpoints take effect immediately."
  ],
  "setup": [
   "Default ISG address 192.168.0.126 when connected straight to a PC; behind a router it takes a DHCP address. Set the IP under the Profile tab in SERVICEWELT.",
   "Unit ID is fixed at 1; TCP port 502.",
   "Test with outside temperature against the controller display to confirm the 1-register offset."
  ],
  "gotchas": [
   "An ISG must not share a CAN bus with a DCo-aktiv GSM module; communication to the WPM can fail.",
   "1520 = 1 is a full factory reset of the system; all settings are lost."
  ]
 },
 "page": "https://easymodbus.com/modbus-register-maps/stiebel-eltron/isg-modbus-wpm-heat-pumps",
 "address_note": "address = 0-based Modbus wire (PDU) address; documented = as printed in the source.",
 "note": "Re-typed from the manufacturer's public documentation (see source) and verified against it. Registers vary by firmware and options; verify against the live device before writing."
}