 "manufacturer": "Studer Innotec",
 "manufacturer_slug": "studer-innotec",
 "model": "BSP battery status processor (via Xcom-485i)",
 "model_slug": "bsp",
 "short_model": "BSP",
 "aliases": [
  "BSP-500",
  "BSP-1200",
  "BSP500",
  "BSP1200",
  "Xcom-485i"
 ],
 "equipment_type": "Sensor (battery monitor for Studer systems)",
 "applies_to": "Studer BSP-500 and BSP-1200 battery status processors read through an Xcom-485i Modbus RTU gateway, system release R706.",
 "summary": "The BSP is Studer's shunt-based battery monitor for Xtender systems. An Xcom-485i on the Studer bus answers Modbus RTU for it. This map lists the BSP user infos (voltage, current, state of charge, power, Ah counters, temperature) as input registers and the BSP parameters as holding registers.",
 "transport": [
  "RTU"
 ],
 "defaults": {
  "unit_id": 61,
  "baud": null,
  "parity": "Even",
  "data_bits": 8,
  "stop_bits": 1,
  "tcp_port": null
 },
 "addressing": {
  "convention": "0-based",
  "note": "The appendix lists the register exactly as it goes in the request. The protocol spec's example reads info 3001 from register 2 with start address 0x0002 in the frame, and parameter 1107 from register 14 (0x000E)."
 },
 "default_word_order": "ABCD",
 "firmware": "Studer system release R706 (appendix V1.6.44); Xcom-485i protocol V1.1.3",
 "source": {
  "title": "Technical specification Studer Modbus RTU Appendix V1.6.44 (with Technical specification Studer Modbus RTU Protocol V1.1.3)",
  "doc_number": "Appendix V1.6.44 (R706); Protocol V1.1.3",
  "revision_date": "2025-09-03",
  "url": "https://studer-innotec.com/wp-content/uploads/2025/09/Manuel-xcom-485i-technical-specification.zip",
  "pages": "Appendix pp. 24-26 (BSP parameters pp. 24-25, BSP infos pp. 25-26); Protocol spec pp. 4-8 (bus settings, unit addressing), pp. 18-25 (examples, offsets, encoding). Both PDFs are inside the ZIP."
 },
 "notes": [
  "Info 7004 'Remaining autonomy' counts minutes to 0 % while discharging (between -60000 and 0) and reads NaN while charging.",
  "Info 7006 'Relative capacity' is deprecated and reads 100 % from BSP software 1.5.6 on. Info 7034 'ID type' reads 10241 (0x2801) for BSP500 and BSP1200.",
  "Every info and parameter is an IEEE 754 single-precision float in two registers, high word first. The protocol spec's example reads Xtender info 3001 as 0x41D3 0x3333 = 26.4 °C, and parameter 1107 as 0x4170 0x0000 = 15.0 A.",
  "Each request must read or write exactly 2 registers (one value); asking for more returns an exception. Infos use function 04, parameters function 03 to read and 16 to write.",
  "Parameter registers have three more views at fixed offsets: +2000 = minimum allowed value, +4000 = maximum allowed value (read only), +6000 = write to RAM only. Use the RAM-only offset for anything written repeatedly; flash is only guaranteed for about 1000 writes per parameter.",
  "Enumerated infos count 0, 1, 2 ...; enumerated parameters use one bit per option (1, 2, 4, 8), still sent as a float. Codes shown as '---' in the appendix are unused and left out of the value lists.",
  "Register names keep the Studer info/parameter number in braces, e.g. {3000}. The register is 2 x (number - base) for that device family.",
  "Parameters whose appendix format is MENU are menu headings, not values, and are left out. The appendix's per-row remarks column is not reproduced.",
  "The gateway's own input registers (pending messages at 0-4, device counts at 5-9, gateway identity at 10-14, on unit 1) and the system clock (holding registers 0-7 on unit 2) are described in the protocol spec but live at other unit IDs, so they are not in this register list.",
  "The protocol spec's first read example prints the value as 0x4170 in the PDU table but 0x41F0 in the serial-line frame; 0x4170 matches the stated 15.0 A."
 ],
 "registers": [
  {
   "table": "input_register",
   "address": 0,
   "documented": "0",
   "name": "Battery voltage {7000}",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "V",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "input_register",
   "address": 2,
   "documented": "2",
   "name": "Battery current {7001}",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "Adc",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "input_register",
   "address": 4,
   "documented": "4",
   "name": "State of Charge {7002}",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "input_register",
   "address": 6,
   "documented": "6",
   "name": "Power {7003}",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "W",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "input_register",
   "address": 8,
   "documented": "8",
   "name": "Remaining autonomy {7004}",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "minutes",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "input_register",
   "address": 10,
   "documented": "10",
   "name": "BSP Temperature {7005}",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "input_register",
   "address": 12,
   "documented": "12",
   "name": "Relative capacity {7006}",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "input_register",
   "address": 14,
   "documented": "14",
   "name": "Ah charged today {7007}",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "Ah",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "input_register",
   "address": 16,
   "documented": "16",
   "name": "Ah discharged today {7008}",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "Ah",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "input_register",
   "address": 18,
   "documented": "18",
   "name": "Ah charged yesterday {7009}",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "Ah",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "input_register",
   "address": 20,
   "documented": "20",
   "name": "Ah discharged yesterday {7010}",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "Ah",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "input_register",
   "address": 22,
   "documented": "22",
   "name": "Total Ah charged {7011}",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "kAh",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "input_register",
   "address": 24,
   "documented": "24",
   "name": "Total Ah discharged {7012}",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "kAh",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "input_register",
   "address": 26,
   "documented": "26",
   "name": "Total time {7013}",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "days",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "input_register",
   "address": 34,
   "documented": "34",
   "name": "Custom charge Ah counter {7017}",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "Ah",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "input_register",
   "address": 36,
   "documented": "36",
   "name": "Custom discharge Ah counter {7018}",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "Ah",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "input_register",
   "address": 38,
   "documented": "38",
   "name": "Custom counter duration {7019}",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "h",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "input_register",
   "address": 58,
   "documented": "58",
   "name": "Battery temperature {7029}",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "input_register",
   "address": 60,
   "documented": "60",
   "name": "Battery voltage (minute avg) {7030}",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "V",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "input_register",
   "address": 62,
   "documented": "62",
   "name": "Battery current (minute avg) {7031}",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "Adc",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "input_register",
   "address": 64,
   "documented": "64",
   "name": "State of Charge (minute avg) {7032}",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "input_register",
   "address": 66,
   "documented": "66",
   "name": "Battery temperature (minute avg) {7033}",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "input_register",
   "address": 68,
   "documented": "68",
   "name": "ID type {7034}",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "input_register",
   "address": 70,
   "documented": "70",
   "name": "ID batt voltage {7035}",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "V",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "input_register",
   "address": 72,
   "documented": "72",
   "name": "ID HW {7036}",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "input_register",
   "address": 74,
   "documented": "74",
   "name": "ID SOFT msb {7037}",
   "description": "Software version word, encoded as in the protocol spec's version section.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "input_register",
   "address": 76,
   "documented": "76",
   "name": "ID SOFT lsb {7038}",
   "description": "Software version word, encoded as in the protocol spec's version section.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "input_register",
   "address": 78,
   "documented": "78",
   "name": "Parameter number (in code) {7039}",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "input_register",
   "address": 80,
   "documented": "80",
   "name": "Info user number {7040}",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "input_register",
   "address": 82,
   "documented": "82",
   "name": "ID SID {7041}",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "input_register",
   "address": 94,
   "documented": "94",
   "name": "Manufacturer State of Charge {7047}",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "input_register",
   "address": 96,
   "documented": "96",
   "name": "ID FID msb {7048}",
   "description": "Half of the unit's unique FID number.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "input_register",
   "address": 98,
   "documented": "98",
   "name": "ID FID lsb {7049}",
   "description": "Half of the unit's unique FID number.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "input_register",
   "address": 118,
   "documented": "118",
   "name": "Local daily communication error counter (CAN) {7059}",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "input_register",
   "address": 120,
   "documented": "120",
   "name": "Number of parameters (in flash) {7060}",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 2,
   "documented": "2",
   "name": "Nominal capacity {6001}",
   "description": "Basic level. Range 20 to 20000, default 110.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "Ah",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 4,
   "documented": "4",
   "name": "Nominal discharge duration (C-rating) {6002}",
   "description": "Basic level. Range 1 to 100, default 20.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "h",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 6,
   "documented": "6",
   "name": "Reset of battery history {6003}",
   "description": "Expert level. Write 1.0 to trigger.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "W",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 8,
   "documented": "8",
   "name": "Restore default settings {6004}",
   "description": "Basic level. Write 1.0 to trigger.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "W",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 10,
   "documented": "10",
   "name": "Restore factory settings {6005}",
   "description": "Installer level. Write 1.0 to trigger.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "W",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 34,
   "documented": "34",
   "name": "Nominal shunt current {6017}",
   "description": "Basic level. Range 10 to 10000, default 500.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "A",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 36,
   "documented": "36",
   "name": "Nominal shunt voltage {6018}",
   "description": "Basic level. Range 10 to 200, default 50.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "mV",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 38,
   "documented": "38",
   "name": "Self-discharge rate {6019}",
   "description": "Expert level. Range 0 to 25, default 3.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "%/month",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 40,
   "documented": "40",
   "name": "Nominal temperature {6020}",
   "description": "Expert level. Range 0 to 40, default 20.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "°C",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 42,
   "documented": "42",
   "name": "Temperature coefficient {6021}",
   "description": "Expert level. Range 0 to 3, default 0.5.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "%cap/°C",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 44,
   "documented": "44",
   "name": "Charge efficiency factor {6022}",
   "description": "Expert level. Range 50 to 100, default 90.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "%",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 46,
   "documented": "46",
   "name": "Peukert's exponent {6023}",
   "description": "Expert level. Range 1 to 1.5, default 1.2.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 48,
   "documented": "48",
   "name": "End of charge voltage level {6024}",
   "description": "Expert level. Range 31.9 to 70.1, default 52.8.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "V",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 50,
   "documented": "50",
   "name": "End of charge current level {6025}",
   "description": "Expert level. Range 0 to 500, default 2.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "%cap",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 62,
   "documented": "62",
   "name": "Reset of user counters {6031}",
   "description": "Expert level. Write 1.0 to trigger.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "W",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 84,
   "documented": "84",
   "name": "Activate the end of charge synchronization {6042}",
   "description": "Expert level. Float 0.0 = no, 1.0 = yes.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "0": "No",
    "1": "Yes"
   },
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 88,
   "documented": "88",
   "name": "Activate the state of charge correction by the open circuit voltage {6044}",
   "description": "Expert level. Float 0.0 = no, 1.0 = yes.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "0": "No",
    "1": "Yes"
   },
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 96,
   "documented": "96",
   "name": "Temperature correction of the end of charge voltage {6048}",
   "description": "Expert level. Range -8 to 0, default 0.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "mV/°C/cell",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 98,
   "documented": "98",
   "name": "Use C20 Capacity as reference value {6049}",
   "description": "Expert level. Float 0.0 = no, 1.0 = yes.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "0": "No",
    "1": "Yes"
   },
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 110,
   "documented": "110",
   "name": "Manufacturer SOC for 0% displayed {6055}",
   "description": "Expert level. Range 0 to 60, default 30.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "%",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 112,
   "documented": "112",
   "name": "Manufacturer SOC for 100% displayed {6056}",
   "description": "Expert level. Range 80 to 100, default 100.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "%",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 114,
   "documented": "114",
   "name": "Voltage of the system {6057}",
   "description": "Basic level. Option code as a float; one option at a time.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "1": "Automatic",
    "2": "12V",
    "4": "24V",
    "8": "48V"
   },
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 116,
   "documented": "116",
   "name": "Battery charge current centralized regulation activated {6058}",
   "description": "Expert level. Float 0.0 = no, 1.0 = yes.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "0": "No",
    "1": "Yes"
   },
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 118,
   "documented": "118",
   "name": "Max battery charge current {6059}",
   "description": "Expert level. Range 0 to 10000, default 60.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "A",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 130,
   "documented": "130",
   "name": "Minimum duration before end of charge {6065}",
   "description": "Expert level. Range 5 to 300, default 5.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "min",
   "access": "RW",
   "values": null,
   "bits": null
  }
 ],
 "integration": {
  "summary": "Fit an Xcom-485i on the Studer communication bus and poll it as a Modbus RTU slave. Each Studer device answers at its own unit ID (offset set by DIP switches 1-2); read infos with function 04 and parameters with 03, always 2 registers at a time, and decode as big-endian float.",
  "minimum_registers": [
   {
    "table": "input_register",
    "address": 0,
    "why": "Battery voltage"
   },
   {
    "table": "input_register",
    "address": 2,
    "why": "Battery current"
   },
   {
    "table": "input_register",
    "address": 4,
    "why": "State of charge"
   },
   {
    "table": "input_register",
    "address": 6,
    "why": "Battery power"
   },
   {
    "table": "input_register",
    "address": 8,
    "why": "Remaining autonomy"
   },
   {
    "table": "input_register",
    "address": 58,
    "why": "Battery temperature"
   }
  ],
  "enable": "Install the Xcom-485i on the Studer bus. DIP switches 1-2 set the unit-ID offset (0, 32, 64 or 128) and switches 7-8 set the baud rate (9600, 19200, 38400 or 115200). Frames are 8 data bits, even parity, 1 stop bit.",
  "watchdog": null,
  "quirks": [
   "Unit 61 addresses the first BSP; multicast unit 60 reads the first such device and writes to all of them at once.",
   "Values are floats even for on/off and enumerated items: 1.0 = 0x3F800000."
  ],
  "setup": [
   "With DIP 1-2 off: unit 1 = Xcom-485i gateway, 2 = system, 10 = all Xtenders, 11-19 = single Xtenders, 20 = all VarioTracks, 21-35 = single VarioTracks, 40 = all VarioStrings, 41-55 = single VarioStrings, 60 = all BSP/Xcom-CAN BMS, 61 = the single BSP or Xcom-CAN BMS. Add the DIP offset to each.",
   "Single devices are numbered in the order shown on the RCC remote's device list.",
   "Allow up to 1 s for a reply and send one request at a time; the gateway is slower when the Studer bus is busy."
  ],
  "gotchas": [
   "Writing a parameter at its base register stores it in flash; cyclic writes should use base + 6000 (RAM only).",
   "Some parameters restart an internal timer or algorithm when changed while running.",
   "Parameter levels (Basic/Expert/Installer/QSP) are the RCC access levels printed in the appendix."
  ]
 },
 "page": "https://easymodbus.com/modbus-register-maps/studer-innotec/bsp",
 "address_note": "address = 0-based Modbus wire (PDU) address; documented = as printed in the source.",
 "note": "Re-typed from the manufacturer's public documentation (see source) and verified against it. Registers vary by firmware and options; verify against the live device before writing."
}