 "manufacturer": "Studer Innotec",
 "manufacturer_slug": "studer-innotec",
 "model": "VarioTrack MPPT solar charge controller (via Xcom-485i)",
 "model_slug": "variotrack",
 "short_model": "VarioTrack",
 "aliases": [
  "VT-40",
  "VT-65",
  "VT-80",
  "VT-HV",
  "VarioTrack VT-65",
  "Xcom-485i"
 ],
 "equipment_type": "Solar inverter (MPPT solar charge controller)",
 "applies_to": "Studer VarioTrack VT-40/65/80/HV MPPT chargers read through an Xcom-485i Modbus RTU gateway, system release R706.",
 "summary": "VarioTrack is Studer's MPPT solar charge controller for Xtender systems. An Xcom-485i on the Studer bus answers Modbus RTU for each VarioTrack. This map lists the VarioTrack user infos (battery, PV, production counters, state, errors, relays) as input registers and the VarioTrack parameters as holding registers.",
 "transport": [
  "RTU"
 ],
 "defaults": {
  "unit_id": 21,
  "baud": null,
  "parity": "Even",
  "data_bits": 8,
  "stop_bits": 1,
  "tcp_port": null
 },
 "addressing": {
  "convention": "0-based",
  "note": "The appendix lists the register exactly as it goes in the request. The protocol spec's example reads info 3001 from register 2 with start address 0x0002 in the frame, and parameter 1107 from register 14 (0x000E)."
 },
 "default_word_order": "ABCD",
 "firmware": "Studer system release R706 (appendix V1.6.44); Xcom-485i protocol V1.1.3",
 "source": {
  "title": "Technical specification Studer Modbus RTU Appendix V1.6.44 (with Technical specification Studer Modbus RTU Protocol V1.1.3)",
  "doc_number": "Appendix V1.6.44 (R706); Protocol V1.1.3",
  "revision_date": "2025-09-03",
  "url": "https://studer-innotec.com/wp-content/uploads/2025/09/Manuel-xcom-485i-technical-specification.zip",
  "pages": "Appendix pp. 29-45 (VarioTrack parameters pp. 29-41, VarioTrack infos pp. 41-45); Protocol spec pp. 4-8 (bus settings, unit addressing), pp. 18-25 (examples, offsets, encoding). Both PDFs are inside the ZIP."
 },
 "notes": [
  "Every info and parameter is an IEEE 754 single-precision float in two registers, high word first. The protocol spec's example reads Xtender info 3001 as 0x41D3 0x3333 = 26.4 °C, and parameter 1107 as 0x4170 0x0000 = 15.0 A.",
  "Each request must read or write exactly 2 registers (one value); asking for more returns an exception. Infos use function 04, parameters function 03 to read and 16 to write.",
  "Parameter registers have three more views at fixed offsets: +2000 = minimum allowed value, +4000 = maximum allowed value (read only), +6000 = write to RAM only. Use the RAM-only offset for anything written repeatedly; flash is only guaranteed for about 1000 writes per parameter.",
  "Enumerated infos count 0, 1, 2 ...; enumerated parameters use one bit per option (1, 2, 4, 8), still sent as a float. Codes shown as '---' in the appendix are unused and left out of the value lists.",
  "Register names keep the Studer info/parameter number in braces, e.g. {3000}. The register is 2 x (number - base) for that device family.",
  "Parameters whose appendix format is MENU are menu headings, not values, and are left out. The appendix's per-row remarks column is not reproduced.",
  "The gateway's own input registers (pending messages at 0-4, device counts at 5-9, gateway identity at 10-14, on unit 1) and the system clock (holding registers 0-7 on unit 2) are described in the protocol spec but live at other unit IDs, so they are not in this register list.",
  "The protocol spec's first read example prints the value as 0x4170 in the PDU table but 0x41F0 in the serial-line frame; 0x4170 matches the stated 15.0 A."
 ],
 "registers": [
  {
   "table": "input_register",
   "address": 0,
   "documented": "0",
   "name": "Battery voltage {11000}",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "V",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "input_register",
   "address": 2,
   "documented": "2",
   "name": "Battery current {11001}",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "A",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "input_register",
   "address": 4,
   "documented": "4",
   "name": "Voltage of the PV generator {11002}",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "V",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "input_register",
   "address": 6,
   "documented": "6",
   "name": "Current of the PV generator {11003}",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "A",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "input_register",
   "address": 8,
   "documented": "8",
   "name": "Power of the PV generator {11004}",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "kW",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "input_register",
   "address": 10,
   "documented": "10",
   "name": "Battery temperature {11005}",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "input_register",
   "address": 12,
   "documented": "12",
   "name": "Production in (Ah) for the current day {11006}",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "Ah",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "input_register",
   "address": 14,
   "documented": "14",
   "name": "Production in (kWh) for the current day {11007}",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "kWh",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "input_register",
   "address": 16,
   "documented": "16",
   "name": "Produced energy resettable counter {11008}",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "kWh",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "input_register",
   "address": 18,
   "documented": "18",
   "name": "Total produced energy {11009}",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "MWh",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "input_register",
   "address": 20,
   "documented": "20",
   "name": "Production in (Ah) for the previous day {11010}",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "Ah",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "input_register",
   "address": 22,
   "documented": "22",
   "name": "Production in (Wh) for the previous day {11011}",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "kWh",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "input_register",
   "address": 24,
   "documented": "24",
   "name": "Number of parameters (in code) {11012}",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "input_register",
   "address": 26,
   "documented": "26",
   "name": "Number of parameters (in flash) {11013}",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "input_register",
   "address": 28,
   "documented": "28",
   "name": "Number of infos users {11014}",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "input_register",
   "address": 30,
   "documented": "30",
   "name": "Model of VarioTrack {11015}",
   "description": "Enumerated state, sent as a float (1.0 = code 1).",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": {
    "0": "VT-80",
    "1": "VT-65",
    "2": "VT-40",
    "3": "VT-HV"
   },
   "bits": null
  },
  {
   "table": "input_register",
   "address": 32,
   "documented": "32",
   "name": "Operating mode {11016}",
   "description": "Enumerated state, sent as a float (1.0 = code 1).",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": {
    "0": "Night",
    "1": "StartUp",
    "3": "Charger",
    "5": "Security",
    "6": "OFF",
    "8": "Charge",
    "9": "Charge V",
    "10": "Charge I",
    "11": "Charge T",
    "12": "Ch. Ibsp"
   },
   "bits": null
  },
  {
   "table": "input_register",
   "address": 34,
   "documented": "34",
   "name": "Max PV voltage for the current day {11017}",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "V",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "input_register",
   "address": 36,
   "documented": "36",
   "name": "Max battery current of the current day {11018}",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "A",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "input_register",
   "address": 38,
   "documented": "38",
   "name": "Max power production for the current day {11019}",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "kW",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "input_register",
   "address": 40,
   "documented": "40",
   "name": "Max battery voltage for the current day {11020}",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "V",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "input_register",
   "address": 42,
   "documented": "42",
   "name": "Min battery voltage for the current day {11021}",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "V",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "input_register",
   "address": 50,
   "documented": "50",
   "name": "Number of irradiation hours for the current day {11025}",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "h",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "input_register",
   "address": 52,
   "documented": "52",
   "name": "Number of irradiation hours for the previous day {11026}",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "h",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "input_register",
   "address": 68,
   "documented": "68",
   "name": "Type of error {11034}",
   "description": "Enumerated state, sent as a float (1.0 = code 1).",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": {
    "0": "No Error",
    "1": "BatOverV",
    "2": "Earth",
    "3": "No Batt",
    "4": "OverTemp",
    "5": "BatOverV",
    "6": "PvOverV",
    "7": "Others",
    "12": "HardErr"
   },
   "bits": null
  },
  {
   "table": "input_register",
   "address": 74,
   "documented": "74",
   "name": "Number of days before next equalization {11037}",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "days",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "input_register",
   "address": 76,
   "documented": "76",
   "name": "Battery cycle phase {11038}",
   "description": "Enumerated state, sent as a float (1.0 = code 1).",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": {
    "0": "Bulk",
    "1": "Absorpt.",
    "2": "Equalize",
    "3": "Floating",
    "6": "R.float.",
    "7": "Per.abs."
   },
   "bits": null
  },
  {
   "table": "input_register",
   "address": 78,
   "documented": "78",
   "name": "Battery voltage (minute avg) {11039}",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "V",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "input_register",
   "address": 80,
   "documented": "80",
   "name": "Battery current (minute avg) {11040}",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "A",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "input_register",
   "address": 82,
   "documented": "82",
   "name": "PV voltage (minute avg) {11041}",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "V",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "input_register",
   "address": 86,
   "documented": "86",
   "name": "PV power (minute avg) {11043}",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "kW",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "input_register",
   "address": 88,
   "documented": "88",
   "name": "Battery temperature (minute avg) {11044}",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "input_register",
   "address": 90,
   "documented": "90",
   "name": "Electronic temperature 1 (minute avg) {11045}",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "input_register",
   "address": 92,
   "documented": "92",
   "name": "Electronic temperature 2 (minute avg) {11046}",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "input_register",
   "address": 94,
   "documented": "94",
   "name": "ID type {11047}",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "input_register",
   "address": 96,
   "documented": "96",
   "name": "ID batt voltage {11048}",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "V",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "input_register",
   "address": 98,
   "documented": "98",
   "name": "ID HW {11049}",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "input_register",
   "address": 100,
   "documented": "100",
   "name": "ID SOFT msb {11050}",
   "description": "Software version word, encoded as in the protocol spec's version section.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "input_register",
   "address": 102,
   "documented": "102",
   "name": "ID SOFT lsb {11051}",
   "description": "Software version word, encoded as in the protocol spec's version section.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "input_register",
   "address": 104,
   "documented": "104",
   "name": "ID SID {11052}",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "input_register",
   "address": 122,
   "documented": "122",
   "name": "State of auxiliary relay 1 {11061}",
   "description": "Enumerated state, sent as a float (1.0 = code 1).",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": {
    "0": "Opened",
    "1": "Closed"
   },
   "bits": null
  },
  {
   "table": "input_register",
   "address": 124,
   "documented": "124",
   "name": "State of auxiliary relay 2 {11062}",
   "description": "Enumerated state, sent as a float (1.0 = code 1).",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": {
    "0": "Opened",
    "1": "Closed"
   },
   "bits": null
  },
  {
   "table": "input_register",
   "address": 126,
   "documented": "126",
   "name": "Relay aux 1 mode {11063}",
   "description": "Enumerated state, sent as a float (1.0 = code 1).",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": {
    "1": "A",
    "2": "I",
    "3": "M",
    "4": "M",
    "5": "G"
   },
   "bits": null
  },
  {
   "table": "input_register",
   "address": 128,
   "documented": "128",
   "name": "Relay aux 2 mode {11064}",
   "description": "Enumerated state, sent as a float (1.0 = code 1).",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": {
    "1": "A",
    "2": "I",
    "3": "M",
    "4": "M",
    "5": "G"
   },
   "bits": null
  },
  {
   "table": "input_register",
   "address": 132,
   "documented": "132",
   "name": "Synchronisation state {11066}",
   "description": "Enumerated state, sent as a float (1.0 = code 1).",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": {
    "4": "XTslave",
    "5": "VTslave",
    "8": "VTmaster",
    "9": "Autonom.",
    "10": "VSslave",
    "11": "VSmaster"
   },
   "bits": null
  },
  {
   "table": "input_register",
   "address": 134,
   "documented": "134",
   "name": "ID FID msb {11067}",
   "description": "Half of the unit's unique FID number.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "input_register",
   "address": 136,
   "documented": "136",
   "name": "ID FID lsb {11068}",
   "description": "Half of the unit's unique FID number.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "input_register",
   "address": 138,
   "documented": "138",
   "name": "State of the VarioTrack {11069}",
   "description": "Enumerated state, sent as a float (1.0 = code 1).",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": {
    "0": "Off",
    "1": "On"
   },
   "bits": null
  },
  {
   "table": "input_register",
   "address": 152,
   "documented": "152",
   "name": "Local daily communication error counter (CAN) {11076}",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "input_register",
   "address": 154,
   "documented": "154",
   "name": "State of auxiliary relay 3 {11077}",
   "description": "Enumerated state, sent as a float (1.0 = code 1).",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": {
    "0": "Opened",
    "1": "Closed"
   },
   "bits": null
  },
  {
   "table": "input_register",
   "address": 156,
   "documented": "156",
   "name": "State of auxiliary relay 4 {11078}",
   "description": "Enumerated state, sent as a float (1.0 = code 1).",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": {
    "0": "Opened",
    "1": "Closed"
   },
   "bits": null
  },
  {
   "table": "input_register",
   "address": 158,
   "documented": "158",
   "name": "Relay aux 3 mode {11079}",
   "description": "Enumerated state, sent as a float (1.0 = code 1).",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": {
    "1": "A",
    "2": "I",
    "3": "M",
    "4": "M",
    "5": "G"
   },
   "bits": null
  },
  {
   "table": "input_register",
   "address": 160,
   "documented": "160",
   "name": "Relay aux 4 mode {11080}",
   "description": "Enumerated state, sent as a float (1.0 = code 1).",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": {
    "1": "A",
    "2": "I",
    "3": "M",
    "4": "M",
    "5": "G"
   },
   "bits": null
  },
  {
   "table": "input_register",
   "address": 164,
   "documented": "164",
   "name": "Remote entry state {11082}",
   "description": "Enumerated state, sent as a float (1.0 = code 1).",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": {
    "0": "RM EN 0",
    "1": "RM EN 1"
   },
   "bits": null
  },
  {
   "table": "input_register",
   "address": 176,
   "documented": "176",
   "name": "Relay voltage measure {11088}",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "V",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 2,
   "documented": "2",
   "name": "Voltage of the system {10001}",
   "description": "Basic level. Option code as a float; one option at a time.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "1": "Automatic",
    "2": "12V",
    "4": "24V",
    "8": "48V"
   },
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 4,
   "documented": "4",
   "name": "Battery charge current {10002}",
   "description": "Expert level. Range 0 to 80, default 80.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "Adc",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 10,
   "documented": "10",
   "name": "Floating voltage {10005}",
   "description": "Basic level. Range 37.9 to 68.2, default 54.4.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "Vdc",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 12,
   "documented": "12",
   "name": "Force phase of floating {10006}",
   "description": "Expert level. Write 1.0 to trigger.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "W",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 16,
   "documented": "16",
   "name": "Absorption phase allowed {10008}",
   "description": "Expert level. Float 0.0 = no, 1.0 = yes.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "0": "No",
    "1": "Yes"
   },
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 18,
   "documented": "18",
   "name": "Absorption voltage {10009}",
   "description": "Basic level. Range 37.9 to 68.2, default 57.6.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "Vdc",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 20,
   "documented": "20",
   "name": "Force absorption phase {10010}",
   "description": "Expert level. Write 1.0 to trigger.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "W",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 22,
   "documented": "22",
   "name": "Absorption duration {10011}",
   "description": "Expert level. Range 5 to 510, default 120.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "min",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 24,
   "documented": "24",
   "name": "End of absorption triggered by the current {10012}",
   "description": "Expert level. Float 0.0 = no, 1.0 = yes.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "0": "No",
    "1": "Yes"
   },
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 26,
   "documented": "26",
   "name": "Current threshold to end absorption phase {10013}",
   "description": "Expert level. Range 2 to 80, default 10.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "Adc",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 34,
   "documented": "34",
   "name": "Equalization allowed {10017}",
   "description": "Basic level. Float 0.0 = no, 1.0 = yes.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "0": "No",
    "1": "Yes"
   },
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 36,
   "documented": "36",
   "name": "Force equalization {10018}",
   "description": "Expert level. Write 1.0 to trigger.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "W",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 38,
   "documented": "38",
   "name": "Equalization before absorption phase {10019}",
   "description": "Expert level. Float 0.0 = no, 1.0 = yes.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "0": "No",
    "1": "Yes"
   },
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 40,
   "documented": "40",
   "name": "Equalization current {10020}",
   "description": "Expert level. Range 2 to 80, default 80.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "Adc",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 42,
   "documented": "42",
   "name": "Equalization voltage {10021}",
   "description": "Basic level. Range 52.1 to 68.2, default 62.4.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "Vdc",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 44,
   "documented": "44",
   "name": "Equalization duration {10022}",
   "description": "Expert level. Range 5 to 510, default 30.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "min",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 50,
   "documented": "50",
   "name": "Days between equalizations {10025}",
   "description": "Expert level. Range 1 to 365, default 26.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "days",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 52,
   "documented": "52",
   "name": "End of equalization triggered by the current {10026}",
   "description": "Expert level. Float 0.0 = no, 1.0 = yes.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "0": "No",
    "1": "Yes"
   },
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 54,
   "documented": "54",
   "name": "Current threshold to end equalization phase {10027}",
   "description": "Expert level. Range 4 to 30, default 10.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "Adc",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 58,
   "documented": "58",
   "name": "Force a new cycle {10029}",
   "description": "Expert level. Write 1.0 to trigger.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "W",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 60,
   "documented": "60",
   "name": "Voltage level 1 to start a new cycle {10030}",
   "description": "Expert level. Range 37.9 to 68.2, default 48.8.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "Vdc",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 62,
   "documented": "62",
   "name": "Time period under voltage level 1 to start a new cycle {10031}",
   "description": "Expert level. Range 0 to 240, default 30.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "min",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 64,
   "documented": "64",
   "name": "Voltage level 2 to start a new cycle {10032}",
   "description": "Expert level. Range 37.9 to 68.2, default 47.2.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "Vdc",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 66,
   "documented": "66",
   "name": "Time period under voltage level 2 to start a new cycle {10033}",
   "description": "Expert level. Range 0 to 240, default 2.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "min",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 68,
   "documented": "68",
   "name": "Cycling restricted {10034}",
   "description": "Expert level. Float 0.0 = no, 1.0 = yes.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "0": "No",
    "1": "Yes"
   },
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 70,
   "documented": "70",
   "name": "Minimal delay between cycles {10035}",
   "description": "Expert level. Range 0 to 540, default 1.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "hours",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 72,
   "documented": "72",
   "name": "Temperature compensation {10036}",
   "description": "Expert level. Range -8 to 0, default -3.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "mV/°C/cell",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 74,
   "documented": "74",
   "name": "Synchronisation battery cycle with Xtender {10037}",
   "description": "Basic level. Float 0.0 = no, 1.0 = yes.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "0": "No",
    "1": "Yes"
   },
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 78,
   "documented": "78",
   "name": "ON of the VarioTrack {10039}",
   "description": "Expert level. Write 1.0 to trigger.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "W",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 80,
   "documented": "80",
   "name": "OFF of the VarioTrack {10040}",
   "description": "Expert level. Write 1.0 to trigger.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "W",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 86,
   "documented": "86",
   "name": "Reset daily solar production meters {10043}",
   "description": "Expert level. Write 1.0 to trigger.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "W",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 88,
   "documented": "88",
   "name": "Reset daily min-max {10044}",
   "description": "Expert level. Write 1.0 to trigger.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "W",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 102,
   "documented": "102",
   "name": "Reset of all VarioTrack {10051}",
   "description": "Expert level. Write 1.0 to trigger.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "W",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 104,
   "documented": "104",
   "name": "Equalization with fixed interval {10052}",
   "description": "Expert level. Float 0.0 = no, 1.0 = yes.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "0": "No",
    "1": "Yes"
   },
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 106,
   "documented": "106",
   "name": "Open circuit ratio -> MPP {10053}",
   "description": "Expert level. Range 1 to 99, default 80.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "%",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 108,
   "documented": "108",
   "name": "Block manual programming (dip-switch) {10054}",
   "description": "Expert level. Float 0.0 = no, 1.0 = yes.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "0": "No",
    "1": "Yes"
   },
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 112,
   "documented": "112",
   "name": "Restore default settings {10056}",
   "description": "Basic level. Write 1.0 to trigger.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "W",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 114,
   "documented": "114",
   "name": "Restore factory settings {10057}",
   "description": "Installer level. Write 1.0 to trigger.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "W",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 116,
   "documented": "116",
   "name": "Parameters saved in flash memory {10058}",
   "description": "Installer level. Float 0.0 = no, 1.0 = yes.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "0": "No",
    "1": "Yes"
   },
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 120,
   "documented": "120",
   "name": "Check Earthing {10060}",
   "description": "Expert level. Option code as a float; one option at a time.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "1": "No control",
    "2": "Neg bat pole earth",
    "4": "Pos bat pole earth",
    "8": "Floating battery"
   },
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 150,
   "documented": "150",
   "name": "Type of MPP tracking {10075}",
   "description": "Expert level. Option code as a float; one option at a time.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "1": "P&O",
    "2": "OC ratio",
    "4": "Upv fixed"
   },
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 170,
   "documented": "170",
   "name": "Battery overvoltage level {10085}",
   "description": "Expert level. Range 37.9 to 68.2, default 68.2.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "Vdc",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 172,
   "documented": "172",
   "name": "Restart voltage level after a battery overvoltage {10086}",
   "description": "Expert level. Range 37.9 to 68.2, default 64.8.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "Vdc",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 174,
   "documented": "174",
   "name": "Disabling of the display button {10087}",
   "description": "Installer level. Float 0.0 = no, 1.0 = yes.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "0": "No",
    "1": "Yes"
   },
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 178,
   "documented": "178",
   "name": "Operating mode (AUX 1) {10089}",
   "description": "Expert level. Option code as a float; one option at a time.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "1": "Automatic",
    "2": "Reversed automatic",
    "4": "Manual ON",
    "8": "Manual OFF"
   },
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 180,
   "documented": "180",
   "name": "Combination of the events for the auxiliary contact (AUX 1) {10090}",
   "description": "Expert level. Option code as a float; one option at a time.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Any (Function OR)",
    "1": "All (Function AND)"
   },
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 182,
   "documented": "182",
   "name": "VarioTrack is OFF (AUX 1) {10091}",
   "description": "Expert level. Float 0.0 = no, 1.0 = yes.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "0": "No",
    "1": "Yes"
   },
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 186,
   "documented": "186",
   "name": "Activated in night mode (AUX 1) {10093}",
   "description": "Expert level. Float 0.0 = no, 1.0 = yes.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "0": "No",
    "1": "Yes"
   },
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 188,
   "documented": "188",
   "name": "Delay of activation after entering night mode (AUX 1) {10094}",
   "description": "Expert level. Range 0 to 1440, default 1.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "min",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 190,
   "documented": "190",
   "name": "Activation time for the auxiliary relay in night mode (AUX 1) {10095}",
   "description": "Expert level. Range 0 to 1440, default 1.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "min",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 194,
   "documented": "194",
   "name": "Battery undervoltage (AUX 1) {10097}",
   "description": "Expert level. Float 0.0 = no, 1.0 = yes.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "0": "No",
    "1": "Yes"
   },
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 196,
   "documented": "196",
   "name": "Battery overvoltage (AUX 1) {10098}",
   "description": "Expert level. Float 0.0 = no, 1.0 = yes.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "0": "No",
    "1": "Yes"
   },
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 198,
   "documented": "198",
   "name": "Earth fault (AUX 1) {10099}",
   "description": "Expert level. Float 0.0 = no, 1.0 = yes.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "0": "No",
    "1": "Yes"
   },
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 200,
   "documented": "200",
   "name": "PV error (48h without charge) (AUX 1) {10100}",
   "description": "Expert level. Float 0.0 = no, 1.0 = yes.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "0": "No",
    "1": "Yes"
   },
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 204,
   "documented": "204",
   "name": "Overtemperature (AUX 1) {10102}",
   "description": "Expert level. Float 0.0 = no, 1.0 = yes.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "0": "No",
    "1": "Yes"
   },
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 206,
   "documented": "206",
   "name": "PV voltage fixed -> MPP {10103}",
   "description": "Expert level. Range 0 to 165, default 70.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "Vdc",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 208,
   "documented": "208",
   "name": "Bulk charge phase (AUX 1) {10104}",
   "description": "Expert level. Float 0.0 = no, 1.0 = yes.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "0": "No",
    "1": "Yes"
   },
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 210,
   "documented": "210",
   "name": "Absorption phase (AUX 1) {10105}",
   "description": "Expert level. Float 0.0 = no, 1.0 = yes.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "0": "No",
    "1": "Yes"
   },
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 212,
   "documented": "212",
   "name": "Equalization phase (AUX 1) {10106}",
   "description": "Expert level. Float 0.0 = no, 1.0 = yes.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "0": "No",
    "1": "Yes"
   },
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 214,
   "documented": "214",
   "name": "Floating (AUX 1) {10107}",
   "description": "Expert level. Float 0.0 = no, 1.0 = yes.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "0": "No",
    "1": "Yes"
   },
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 216,
   "documented": "216",
   "name": "Reduced floating (AUX 1) {10108}",
   "description": "Expert level. Float 0.0 = no, 1.0 = yes.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "0": "No",
    "1": "Yes"
   },
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 218,
   "documented": "218",
   "name": "Periodic absorption (AUX 1) {10109}",
   "description": "Expert level. Float 0.0 = no, 1.0 = yes.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "0": "No",
    "1": "Yes"
   },
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 222,
   "documented": "222",
   "name": "Battery voltage 1 activate (AUX 1) {10111}",
   "description": "Expert level. Float 0.0 = no, 1.0 = yes.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "0": "No",
    "1": "Yes"
   },
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 224,
   "documented": "224",
   "name": "Battery voltage 1 (AUX 1) {10112}",
   "description": "Expert level. Range 36 to 72, default 46.8.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "Vdc",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 226,
   "documented": "226",
   "name": "Delay 1 (AUX 1) {10113}",
   "description": "Expert level. Range 0 to 60, default 1.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "min",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 228,
   "documented": "228",
   "name": "Battery voltage 2 activate (AUX 1) {10114}",
   "description": "Expert level. Float 0.0 = no, 1.0 = yes.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "0": "No",
    "1": "Yes"
   },
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 230,
   "documented": "230",
   "name": "Battery voltage 2 (AUX 1) {10115}",
   "description": "Expert level. Range 36 to 72, default 47.8.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "Vdc",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 232,
   "documented": "232",
   "name": "Delay 2 (AUX 1) {10116}",
   "description": "Expert level. Range 0 to 60, default 10.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "min",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 234,
   "documented": "234",
   "name": "Battery voltage 3 activate (AUX 1) {10117}",
   "description": "Expert level. Float 0.0 = no, 1.0 = yes.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "0": "No",
    "1": "Yes"
   },
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 236,
   "documented": "236",
   "name": "Battery voltage 3 (AUX 1) {10118}",
   "description": "Expert level. Range 36 to 72, default 48.5.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "Vdc",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 238,
   "documented": "238",
   "name": "Delay 3 (AUX 1) {10119}",
   "description": "Expert level. Range 0 to 60, default 60.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "min",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 240,
   "documented": "240",
   "name": "Battery voltage to deactivate (AUX 1) {10120}",
   "description": "Expert level. Range 36 to 72, default 54.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "Vdc",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 242,
   "documented": "242",
   "name": "Delay to deactivate (AUX 1) {10121}",
   "description": "Expert level. Range 0 to 480, default 60.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "min",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 244,
   "documented": "244",
   "name": "Deactivate if battery in floating phase (AUX 1) {10122}",
   "description": "Expert level. Float 0.0 = no, 1.0 = yes.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "0": "No",
    "1": "Yes"
   },
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 248,
   "documented": "248",
   "name": "Contact activated with the temperature of battery (AUX 1) {10124}",
   "description": "Expert level. Float 0.0 = no, 1.0 = yes.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "0": "No",
    "1": "Yes"
   },
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 250,
   "documented": "250",
   "name": "Contact activated over (AUX 1) {10125}",
   "description": "Expert level. Range -10 to 50, default 3.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "°C",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 252,
   "documented": "252",
   "name": "Contact deactivated below (AUX 1) {10126}",
   "description": "Expert level. Range -10 to 50, default 5.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "°C",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 254,
   "documented": "254",
   "name": "Only activated if the battery is not in bulk phase (AUX 1) {10127}",
   "description": "Expert level. Float 0.0 = no, 1.0 = yes.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "0": "No",
    "1": "Yes"
   },
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 258,
   "documented": "258",
   "name": "Contact activated with the SOC 1 of battery (AUX 1) {10129}",
   "description": "Expert level. Float 0.0 = no, 1.0 = yes.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "0": "No",
    "1": "Yes"
   },
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 260,
   "documented": "260",
   "name": "Contact activated below SOC 1 (AUX 1) {10130}",
   "description": "Expert level. Range 0 to 100, default 50.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "% SOC",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 262,
   "documented": "262",
   "name": "Delay 1 (AUX 1) {10131}",
   "description": "Expert level. Range 0 to 99, default 12.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "hours",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 264,
   "documented": "264",
   "name": "Contact activated with the SOC 2 of battery (AUX 1) {10132}",
   "description": "Expert level. Float 0.0 = no, 1.0 = yes.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "0": "No",
    "1": "Yes"
   },
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 266,
   "documented": "266",
   "name": "Contact activated below SOC 2 (AUX 1) {10133}",
   "description": "Expert level. Range 0 to 100, default 30.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "%",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 268,
   "documented": "268",
   "name": "Delay 2 (AUX 1) {10134}",
   "description": "Expert level. Range 0 to 99, default 0.2.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "hours",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 270,
   "documented": "270",
   "name": "Contact activated with the SOC 3 of battery (AUX 1) {10135}",
   "description": "Expert level. Float 0.0 = no, 1.0 = yes.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "0": "No",
    "1": "Yes"
   },
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 272,
   "documented": "272",
   "name": "Contact activated below SOC 3 (AUX 1) {10136}",
   "description": "Expert level. Range 0 to 100, default 20.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "%",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 274,
   "documented": "274",
   "name": "Delay 3 (AUX 1) {10137}",
   "description": "Expert level. Range 0 to 99, default 0.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "hours",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 276,
   "documented": "276",
   "name": "Contact deactivated over SOC (AUX 1) {10138}",
   "description": "Expert level. Range 0 to 100, default 90.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "% SOC",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 278,
   "documented": "278",
   "name": "Delay to deactivate (AUX 1) {10139}",
   "description": "Expert level. Range 0 to 10, default 0.2.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "hours",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 280,
   "documented": "280",
   "name": "Deactivate if battery in floating phase (AUX 1) {10140}",
   "description": "Expert level. Float 0.0 = no, 1.0 = yes.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "0": "No",
    "1": "Yes"
   },
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 282,
   "documented": "282",
   "name": "Reset all settings (AUX 1) {10141}",
   "description": "Expert level. Write 1.0 to trigger.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "W",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 286,
   "documented": "286",
   "name": "Operating mode (AUX 2) {10143}",
   "description": "Expert level. Option code as a float; one option at a time.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "1": "Automatic",
    "2": "Reversed automatic",
    "4": "Manual ON",
    "8": "Manual OFF"
   },
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 288,
   "documented": "288",
   "name": "Combination of the events for the auxiliary contact (AUX 2) {10144}",
   "description": "Expert level. Option code as a float; one option at a time.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Any (Function OR)",
    "1": "All (Function AND)"
   },
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 290,
   "documented": "290",
   "name": "VarioTrack is OFF (AUX 2) {10145}",
   "description": "Expert level. Float 0.0 = no, 1.0 = yes.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "0": "No",
    "1": "Yes"
   },
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 294,
   "documented": "294",
   "name": "Activated in night mode (AUX 2) {10147}",
   "description": "Expert level. Float 0.0 = no, 1.0 = yes.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "0": "No",
    "1": "Yes"
   },
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 296,
   "documented": "296",
   "name": "Delay of activation after entering night mode (AUX 2) {10148}",
   "description": "Expert level. Range 0 to 1440, default 1.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "min",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 298,
   "documented": "298",
   "name": "Activation time for the auxiliary relay in night mode (AUX 2) {10149}",
   "description": "Expert level. Range 0 to 1440, default 1.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "min",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 302,
   "documented": "302",
   "name": "Battery undervoltage (AUX 2) {10151}",
   "description": "Expert level. Float 0.0 = no, 1.0 = yes.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "0": "No",
    "1": "Yes"
   },
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 304,
   "documented": "304",
   "name": "Battery overvoltage (AUX 2) {10152}",
   "description": "Expert level. Float 0.0 = no, 1.0 = yes.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "0": "No",
    "1": "Yes"
   },
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 306,
   "documented": "306",
   "name": "Earth fault (AUX 2) {10153}",
   "description": "Expert level. Float 0.0 = no, 1.0 = yes.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "0": "No",
    "1": "Yes"
   },
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 308,
   "documented": "308",
   "name": "PV error (48h without charge) (AUX 2) {10154}",
   "description": "Expert level. Float 0.0 = no, 1.0 = yes.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "0": "No",
    "1": "Yes"
   },
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 312,
   "documented": "312",
   "name": "Overtemperature (AUX 2) {10156}",
   "description": "Expert level. Float 0.0 = no, 1.0 = yes.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "0": "No",
    "1": "Yes"
   },
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 316,
   "documented": "316",
   "name": "Bulk charge phase (AUX 2) {10158}",
   "description": "Expert level. Float 0.0 = no, 1.0 = yes.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "0": "No",
    "1": "Yes"
   },
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 318,
   "documented": "318",
   "name": "Absorption phase (AUX 2) {10159}",
   "description": "Expert level. Float 0.0 = no, 1.0 = yes.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "0": "No",
    "1": "Yes"
   },
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 320,
   "documented": "320",
   "name": "Equalization phase (AUX 2) {10160}",
   "description": "Expert level. Float 0.0 = no, 1.0 = yes.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "0": "No",
    "1": "Yes"
   },
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 322,
   "documented": "322",
   "name": "Floating (AUX 2) {10161}",
   "description": "Expert level. Float 0.0 = no, 1.0 = yes.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "0": "No",
    "1": "Yes"
   },
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 324,
   "documented": "324",
   "name": "Reduced floating (AUX 2) {10162}",
   "description": "Expert level. Float 0.0 = no, 1.0 = yes.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "0": "No",
    "1": "Yes"
   },
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 326,
   "documented": "326",
   "name": "Periodic absorption (AUX 2) {10163}",
   "description": "Expert level. Float 0.0 = no, 1.0 = yes.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "0": "No",
    "1": "Yes"
   },
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 330,
   "documented": "330",
   "name": "Battery voltage 1 activate (AUX 2) {10165}",
   "description": "Expert level. Float 0.0 = no, 1.0 = yes.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "0": "No",
    "1": "Yes"
   },
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 332,
   "documented": "332",
   "name": "Battery voltage 1 (AUX 2) {10166}",
   "description": "Expert level. Range 36 to 72, default 46.8.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "Vdc",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 334,
   "documented": "334",
   "name": "Delay 1 (AUX 2) {10167}",
   "description": "Expert level. Range 0 to 60, default 1.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "min",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 336,
   "documented": "336",
   "name": "Battery voltage 2 activate (AUX 2) {10168}",
   "description": "Expert level. Float 0.0 = no, 1.0 = yes.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "0": "No",
    "1": "Yes"
   },
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 338,
   "documented": "338",
   "name": "Battery voltage 2 (AUX 2) {10169}",
   "description": "Expert level. Range 36 to 72, default 47.8.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "Vdc",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 340,
   "documented": "340",
   "name": "Delay 2 (AUX 2) {10170}",
   "description": "Expert level. Range 0 to 60, default 10.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "min",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 342,
   "documented": "342",
   "name": "Battery voltage 3 activate (AUX 2) {10171}",
   "description": "Expert level. Float 0.0 = no, 1.0 = yes.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "0": "No",
    "1": "Yes"
   },
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 344,
   "documented": "344",
   "name": "Battery voltage 3 (AUX 2) {10172}",
   "description": "Expert level. Range 36 to 72, default 48.5.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "Vdc",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 346,
   "documented": "346",
   "name": "Delay 3 (AUX 2) {10173}",
   "description": "Expert level. Range 0 to 60, default 60.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "min",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 348,
   "documented": "348",
   "name": "Battery voltage to deactivate (AUX 2) {10174}",
   "description": "Expert level. Range 36 to 72, default 54.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "Vdc",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 350,
   "documented": "350",
   "name": "Delay to deactivate (AUX 2) {10175}",
   "description": "Expert level. Range 0 to 480, default 60.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "min",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 352,
   "documented": "352",
   "name": "Deactivate if battery in floating phase (AUX 2) {10176}",
   "description": "Expert level. Float 0.0 = no, 1.0 = yes.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "0": "No",
    "1": "Yes"
   },
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 356,
   "documented": "356",
   "name": "Contact activated with the temperature of battery (AUX 2) {10178}",
   "description": "Expert level. Float 0.0 = no, 1.0 = yes.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "0": "No",
    "1": "Yes"
   },
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 358,
   "documented": "358",
   "name": "Contact activated over (AUX 2) {10179}",
   "description": "Expert level. Range -10 to 50, default 3.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "°C",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 360,
   "documented": "360",
   "name": "Contact deactivated below (AUX 2) {10180}",
   "description": "Expert level. Range -10 to 50, default 5.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "°C",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 362,
   "documented": "362",
   "name": "Only activated if the battery is not in bulk phase (AUX 2) {10181}",
   "description": "Expert level. Float 0.0 = no, 1.0 = yes.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "0": "No",
    "1": "Yes"
   },
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 366,
   "documented": "366",
   "name": "Contact activated with the SOC 1 of battery (AUX 2) {10183}",
   "description": "Expert level. Float 0.0 = no, 1.0 = yes.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "0": "No",
    "1": "Yes"
   },
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 368,
   "documented": "368",
   "name": "Contact activated below SOC 1 (AUX 2) {10184}",
   "description": "Expert level. Range 0 to 100, default 50.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "% SOC",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 370,
   "documented": "370",
   "name": "Delay 1 (AUX 2) {10185}",
   "description": "Expert level. Range 0 to 99, default 12.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "hours",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 372,
   "documented": "372",
   "name": "Contact activated with the SOC 2 of battery (AUX 2) {10186}",
   "description": "Expert level. Float 0.0 = no, 1.0 = yes.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "0": "No",
    "1": "Yes"
   },
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 374,
   "documented": "374",
   "name": "Contact activated below SOC 2 (AUX 2) {10187}",
   "description": "Expert level. Range 0 to 100, default 30.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "%",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 376,
   "documented": "376",
   "name": "Delay 2 (AUX 2) {10188}",
   "description": "Expert level. Range 0 to 99, default 0.2.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "hours",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 378,
   "documented": "378",
   "name": "Contact activated with the SOC 3 of battery (AUX 2) {10189}",
   "description": "Expert level. Float 0.0 = no, 1.0 = yes.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "0": "No",
    "1": "Yes"
   },
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 380,
   "documented": "380",
   "name": "Contact activated below SOC 3 (AUX 2) {10190}",
   "description": "Expert level. Range 0 to 100, default 20.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "%",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 382,
   "documented": "382",
   "name": "Delay 3 (AUX 2) {10191}",
   "description": "Expert level. Range 0 to 99, default 0.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "hours",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 384,
   "documented": "384",
   "name": "Contact deactivated over SOC (AUX 2) {10192}",
   "description": "Expert level. Range 0 to 100, default 90.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "% SOC",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 386,
   "documented": "386",
   "name": "Delay to deactivate (AUX 2) {10193}",
   "description": "Expert level. Range 0 to 10, default 0.2.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "hours",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 388,
   "documented": "388",
   "name": "Deactivate if battery in floating phase (AUX 2) {10194}",
   "description": "Expert level. Float 0.0 = no, 1.0 = yes.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "0": "No",
    "1": "Yes"
   },
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 390,
   "documented": "390",
   "name": "Reset all settings (AUX 2) {10195}",
   "description": "Expert level. Write 1.0 to trigger.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "W",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 396,
   "documented": "396",
   "name": "VarioTrack is ON (AUX 1) {10198}",
   "description": "Expert level. Float 0.0 = no, 1.0 = yes.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "0": "No",
    "1": "Yes"
   },
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 398,
   "documented": "398",
   "name": "VarioTrack is ON (AUX 2) {10199}",
   "description": "Expert level. Float 0.0 = no, 1.0 = yes.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "0": "No",
    "1": "Yes"
   },
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 400,
   "documented": "400",
   "name": "Reset PV energy meter {10200}",
   "description": "Expert level. Write 1.0 to trigger.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "W",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 402,
   "documented": "402",
   "name": "Reset total produced PV energy meter {10201}",
   "description": "Qualified service level. Write 1.0 to trigger.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "W",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 406,
   "documented": "406",
   "name": "Operating mode (AUX 3) {10203}",
   "description": "Expert level. Option code as a float; one option at a time.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "1": "Automatic",
    "2": "Reversed automatic",
    "4": "Manual ON",
    "8": "Manual OFF"
   },
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 408,
   "documented": "408",
   "name": "Combination of the events for the auxiliary contact (AUX 3) {10204}",
   "description": "Expert level. Option code as a float; one option at a time.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Any (Function OR)",
    "1": "All (Function AND)"
   },
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 412,
   "documented": "412",
   "name": "Activated in night mode (AUX 3) {10206}",
   "description": "Expert level. Float 0.0 = no, 1.0 = yes.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "0": "No",
    "1": "Yes"
   },
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 414,
   "documented": "414",
   "name": "Delay of activation after entering night mode (AUX 3) {10207}",
   "description": "Expert level. Range 0 to 1440, default 1.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "min",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 416,
   "documented": "416",
   "name": "Activation time for the auxiliary relay in night mode (AUX 3) {10208}",
   "description": "Expert level. Range 0 to 1440, default 1.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "min",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 420,
   "documented": "420",
   "name": "VarioTrack is ON (AUX 3) {10210}",
   "description": "Expert level. Float 0.0 = no, 1.0 = yes.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "0": "No",
    "1": "Yes"
   },
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 422,
   "documented": "422",
   "name": "VarioTrack is OFF (AUX 3) {10211}",
   "description": "Expert level. Float 0.0 = no, 1.0 = yes.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "0": "No",
    "1": "Yes"
   },
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 424,
   "documented": "424",
   "name": "Battery undervoltage (AUX 3) {10212}",
   "description": "Expert level. Float 0.0 = no, 1.0 = yes.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "0": "No",
    "1": "Yes"
   },
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 426,
   "documented": "426",
   "name": "Battery overvoltage (AUX 3) {10213}",
   "description": "Expert level. Float 0.0 = no, 1.0 = yes.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "0": "No",
    "1": "Yes"
   },
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 428,
   "documented": "428",
   "name": "Earth fault (AUX 3) {10214}",
   "description": "Expert level. Float 0.0 = no, 1.0 = yes.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "0": "No",
    "1": "Yes"
   },
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 430,
   "documented": "430",
   "name": "PV error (48h without charge) (AUX 3) {10215}",
   "description": "Expert level. Float 0.0 = no, 1.0 = yes.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "0": "No",
    "1": "Yes"
   },
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 432,
   "documented": "432",
   "name": "Overtemperature (AUX 3) {10216}",
   "description": "Expert level. Float 0.0 = no, 1.0 = yes.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "0": "No",
    "1": "Yes"
   },
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 434,
   "documented": "434",
   "name": "Bulk charge phase (AUX 3) {10217}",
   "description": "Expert level. Float 0.0 = no, 1.0 = yes.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "0": "No",
    "1": "Yes"
   },
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 436,
   "documented": "436",
   "name": "Absorption phase (AUX 3) {10218}",
   "description": "Expert level. Float 0.0 = no, 1.0 = yes.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "0": "No",
    "1": "Yes"
   },
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 438,
   "documented": "438",
   "name": "Equalization phase (AUX 3) {10219}",
   "description": "Expert level. Float 0.0 = no, 1.0 = yes.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "0": "No",
    "1": "Yes"
   },
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 440,
   "documented": "440",
   "name": "Floating (AUX 3) {10220}",
   "description": "Expert level. Float 0.0 = no, 1.0 = yes.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "0": "No",
    "1": "Yes"
   },
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 442,
   "documented": "442",
   "name": "Reduced floating (AUX 3) {10221}",
   "description": "Expert level. Float 0.0 = no, 1.0 = yes.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "0": "No",
    "1": "Yes"
   },
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 444,
   "documented": "444",
   "name": "Periodic absorption (AUX 3) {10222}",
   "description": "Expert level. Float 0.0 = no, 1.0 = yes.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "0": "No",
    "1": "Yes"
   },
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 448,
   "documented": "448",
   "name": "Battery voltage 1 activate (AUX 3) {10224}",
   "description": "Expert level. Float 0.0 = no, 1.0 = yes.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "0": "No",
    "1": "Yes"
   },
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 450,
   "documented": "450",
   "name": "Battery voltage 1 (AUX 3) {10225}",
   "description": "Expert level. Range 36 to 72, default 46.8.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "Vdc",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 452,
   "documented": "452",
   "name": "Delay 1 (AUX 3) {10226}",
   "description": "Expert level. Range 0 to 60, default 1.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "min",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 454,
   "documented": "454",
   "name": "Battery voltage 2 activate (AUX 3) {10227}",
   "description": "Expert level. Float 0.0 = no, 1.0 = yes.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "0": "No",
    "1": "Yes"
   },
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 456,
   "documented": "456",
   "name": "Battery voltage 2 (AUX 3) {10228}",
   "description": "Expert level. Range 36 to 72, default 47.8.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "Vdc",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 458,
   "documented": "458",
   "name": "Delay 2 (AUX 3) {10229}",
   "description": "Expert level. Range 0 to 60, default 10.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "min",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 460,
   "documented": "460",
   "name": "Battery voltage 3 activate (AUX 3) {10230}",
   "description": "Expert level. Float 0.0 = no, 1.0 = yes.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "0": "No",
    "1": "Yes"
   },
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 462,
   "documented": "462",
   "name": "Battery voltage 3 (AUX 3) {10231}",
   "description": "Expert level. Range 36 to 72, default 48.5.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "Vdc",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 464,
   "documented": "464",
   "name": "Delay 3 (AUX 3) {10232}",
   "description": "Expert level. Range 0 to 60, default 60.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "min",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 466,
   "documented": "466",
   "name": "Battery voltage to deactivate (AUX 3) {10233}",
   "description": "Expert level. Range 36 to 72, default 54.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "Vdc",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 468,
   "documented": "468",
   "name": "Delay to deactivate (AUX 3) {10234}",
   "description": "Expert level. Range 0 to 480, default 60.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "min",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 470,
   "documented": "470",
   "name": "Deactivate if battery in floating phase (AUX 3) {10235}",
   "description": "Expert level. Float 0.0 = no, 1.0 = yes.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "0": "No",
    "1": "Yes"
   },
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 474,
   "documented": "474",
   "name": "Contact activated with the temperature of battery (AUX 3) {10237}",
   "description": "Expert level. Float 0.0 = no, 1.0 = yes.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "0": "No",
    "1": "Yes"
   },
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 476,
   "documented": "476",
   "name": "Contact activated over (AUX 3) {10238}",
   "description": "Expert level. Range -10 to 50, default 3.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "°C",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 478,
   "documented": "478",
   "name": "Contact deactivated below (AUX 3) {10239}",
   "description": "Expert level. Range -10 to 50, default 5.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "°C",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 480,
   "documented": "480",
   "name": "Only activated if the battery is not in bulk phase (AUX 3) {10240}",
   "description": "Expert level. Float 0.0 = no, 1.0 = yes.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "0": "No",
    "1": "Yes"
   },
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 484,
   "documented": "484",
   "name": "Contact activated with the SOC 1 of battery (AUX 3) {10242}",
   "description": "Expert level. Float 0.0 = no, 1.0 = yes.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "0": "No",
    "1": "Yes"
   },
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 486,
   "documented": "486",
   "name": "Contact activated below SOC 1 (AUX 3) {10243}",
   "description": "Expert level. Range 0 to 100, default 50.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "% SOC",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 488,
   "documented": "488",
   "name": "Delay 1 (AUX 3) {10244}",
   "description": "Expert level. Range 0 to 99, default 12.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "hours",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 490,
   "documented": "490",
   "name": "Contact activated with the SOC 2 of battery (AUX 3) {10245}",
   "description": "Expert level. Float 0.0 = no, 1.0 = yes.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "0": "No",
    "1": "Yes"
   },
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 492,
   "documented": "492",
   "name": "Contact activated below SOC 2 (AUX 3) {10246}",
   "description": "Expert level. Range 0 to 100, default 30.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "%",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 494,
   "documented": "494",
   "name": "Delay 2 (AUX 3) {10247}",
   "description": "Expert level. Range 0 to 99, default 0.2.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "hours",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 496,
   "documented": "496",
   "name": "Contact activated with the SOC 3 of battery (AUX 3) {10248}",
   "description": "Expert level. Float 0.0 = no, 1.0 = yes.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "0": "No",
    "1": "Yes"
   },
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 498,
   "documented": "498",
   "name": "Contact activated below SOC 3 (AUX 3) {10249}",
   "description": "Expert level. Range 0 to 100, default 20.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "%",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 500,
   "documented": "500",
   "name": "Delay 3 (AUX 3) {10250}",
   "description": "Expert level. Range 0 to 99, default 0.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "hours",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 502,
   "documented": "502",
   "name": "Contact deactivated over SOC (AUX 3) {10251}",
   "description": "Expert level. Range 0 to 100, default 90.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "% SOC",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 504,
   "documented": "504",
   "name": "Delay to deactivate (AUX 3) {10252}",
   "description": "Expert level. Range 0 to 10, default 0.2.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "hours",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 506,
   "documented": "506",
   "name": "Deactivate if battery in floating phase (AUX 3) {10253}",
   "description": "Expert level. Float 0.0 = no, 1.0 = yes.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "0": "No",
    "1": "Yes"
   },
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 508,
   "documented": "508",
   "name": "Reset all settings (AUX 3) {10254}",
   "description": "Expert level. Write 1.0 to trigger.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "W",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 512,
   "documented": "512",
   "name": "Operating mode (AUX 4) {10256}",
   "description": "Expert level. Option code as a float; one option at a time.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "1": "Automatic",
    "2": "Reversed automatic",
    "4": "Manual ON",
    "8": "Manual OFF"
   },
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 514,
   "documented": "514",
   "name": "Combination of the events for the auxiliary contact (AUX 4) {10257}",
   "description": "Expert level. Option code as a float; one option at a time.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Any (Function OR)",
    "1": "All (Function AND)"
   },
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 518,
   "documented": "518",
   "name": "Activated in night mode (AUX 4) {10259}",
   "description": "Expert level. Float 0.0 = no, 1.0 = yes.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "0": "No",
    "1": "Yes"
   },
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 520,
   "documented": "520",
   "name": "Delay of activation after entering night mode (AUX 4) {10260}",
   "description": "Expert level. Range 0 to 1440, default 1.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "min",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 522,
   "documented": "522",
   "name": "Activation time for the auxiliary relay in night mode (AUX 4) {10261}",
   "description": "Expert level. Range 0 to 1440, default 1.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "min",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 526,
   "documented": "526",
   "name": "VarioTrack is ON (AUX 4) {10263}",
   "description": "Expert level. Float 0.0 = no, 1.0 = yes.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "0": "No",
    "1": "Yes"
   },
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 528,
   "documented": "528",
   "name": "VarioTrack is OFF (AUX 4) {10264}",
   "description": "Expert level. Float 0.0 = no, 1.0 = yes.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "0": "No",
    "1": "Yes"
   },
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 530,
   "documented": "530",
   "name": "Battery undervoltage (AUX 4) {10265}",
   "description": "Expert level. Float 0.0 = no, 1.0 = yes.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "0": "No",
    "1": "Yes"
   },
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 532,
   "documented": "532",
   "name": "Battery overvoltage (AUX 4) {10266}",
   "description": "Expert level. Float 0.0 = no, 1.0 = yes.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "0": "No",
    "1": "Yes"
   },
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 534,
   "documented": "534",
   "name": "Earth fault (AUX 4) {10267}",
   "description": "Expert level. Float 0.0 = no, 1.0 = yes.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "0": "No",
    "1": "Yes"
   },
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 536,
   "documented": "536",
   "name": "PV error (48h without charge) (AUX 4) {10268}",
   "description": "Expert level. Float 0.0 = no, 1.0 = yes.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "0": "No",
    "1": "Yes"
   },
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 538,
   "documented": "538",
   "name": "Overtemperature (AUX 4) {10269}",
   "description": "Expert level. Float 0.0 = no, 1.0 = yes.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "0": "No",
    "1": "Yes"
   },
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 540,
   "documented": "540",
   "name": "Bulk charge phase (AUX 4) {10270}",
   "description": "Expert level. Float 0.0 = no, 1.0 = yes.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "0": "No",
    "1": "Yes"
   },
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 542,
   "documented": "542",
   "name": "Absorption phase (AUX 4) {10271}",
   "description": "Expert level. Float 0.0 = no, 1.0 = yes.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "0": "No",
    "1": "Yes"
   },
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 544,
   "documented": "544",
   "name": "Equalization phase (AUX 4) {10272}",
   "description": "Expert level. Float 0.0 = no, 1.0 = yes.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "0": "No",
    "1": "Yes"
   },
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 546,
   "documented": "546",
   "name": "Floating (AUX 4) {10273}",
   "description": "Expert level. Float 0.0 = no, 1.0 = yes.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "0": "No",
    "1": "Yes"
   },
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 548,
   "documented": "548",
   "name": "Reduced floating (AUX 4) {10274}",
   "description": "Expert level. Float 0.0 = no, 1.0 = yes.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "0": "No",
    "1": "Yes"
   },
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 550,
   "documented": "550",
   "name": "Periodic absorption (AUX 4) {10275}",
   "description": "Expert level. Float 0.0 = no, 1.0 = yes.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "0": "No",
    "1": "Yes"
   },
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 554,
   "documented": "554",
   "name": "Battery voltage 1 activate (AUX 4) {10277}",
   "description": "Expert level. Float 0.0 = no, 1.0 = yes.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "0": "No",
    "1": "Yes"
   },
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 556,
   "documented": "556",
   "name": "Battery voltage 1 (AUX 4) {10278}",
   "description": "Expert level. Range 36 to 72, default 46.8.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "Vdc",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 558,
   "documented": "558",
   "name": "Delay 1 (AUX 4) {10279}",
   "description": "Expert level. Range 0 to 60, default 1.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "min",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 560,
   "documented": "560",
   "name": "Battery voltage 2 activate (AUX 4) {10280}",
   "description": "Expert level. Float 0.0 = no, 1.0 = yes.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "0": "No",
    "1": "Yes"
   },
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 562,
   "documented": "562",
   "name": "Battery voltage 2 (AUX 4) {10281}",
   "description": "Expert level. Range 36 to 72, default 47.8.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "Vdc",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 564,
   "documented": "564",
   "name": "Delay 2 (AUX 4) {10282}",
   "description": "Expert level. Range 0 to 60, default 10.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "min",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 566,
   "documented": "566",
   "name": "Battery voltage 3 activate (AUX 4) {10283}",
   "description": "Expert level. Float 0.0 = no, 1.0 = yes.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "0": "No",
    "1": "Yes"
   },
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 568,
   "documented": "568",
   "name": "Battery voltage 3 (AUX 4) {10284}",
   "description": "Expert level. Range 36 to 72, default 48.5.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "Vdc",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 570,
   "documented": "570",
   "name": "Delay 3 (AUX 4) {10285}",
   "description": "Expert level. Range 0 to 60, default 60.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "min",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 572,
   "documented": "572",
   "name": "Battery voltage to deactivate (AUX 4) {10286}",
   "description": "Expert level. Range 36 to 72, default 54.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "Vdc",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 574,
   "documented": "574",
   "name": "Delay to deactivate (AUX 4) {10287}",
   "description": "Expert level. Range 0 to 480, default 60.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "min",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 576,
   "documented": "576",
   "name": "Deactivate if battery in floating phase (AUX 4) {10288}",
   "description": "Expert level. Float 0.0 = no, 1.0 = yes.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "0": "No",
    "1": "Yes"
   },
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 580,
   "documented": "580",
   "name": "Contact activated with the temperature of battery (AUX 4) {10290}",
   "description": "Expert level. Float 0.0 = no, 1.0 = yes.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "0": "No",
    "1": "Yes"
   },
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 582,
   "documented": "582",
   "name": "Contact activated over (AUX 4) {10291}",
   "description": "Expert level. Range -10 to 50, default 3.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "°C",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 584,
   "documented": "584",
   "name": "Contact deactivated below (AUX 4) {10292}",
   "description": "Expert level. Range -10 to 50, default 5.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "°C",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 586,
   "documented": "586",
   "name": "Only activated if the battery is not in bulk phase (AUX 4) {10293}",
   "description": "Expert level. Float 0.0 = no, 1.0 = yes.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "0": "No",
    "1": "Yes"
   },
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 590,
   "documented": "590",
   "name": "Contact activated with the SOC 1 of battery (AUX 4) {10295}",
   "description": "Expert level. Float 0.0 = no, 1.0 = yes.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "0": "No",
    "1": "Yes"
   },
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 592,
   "documented": "592",
   "name": "Contact activated below SOC 1 (AUX 4) {10296}",
   "description": "Expert level. Range 0 to 100, default 50.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "% SOC",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 594,
   "documented": "594",
   "name": "Delay 1 (AUX 4) {10297}",
   "description": "Expert level. Range 0 to 99, default 12.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "hours",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 596,
   "documented": "596",
   "name": "Contact activated with the SOC 2 of battery (AUX 4) {10298}",
   "description": "Expert level. Float 0.0 = no, 1.0 = yes.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "0": "No",
    "1": "Yes"
   },
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 598,
   "documented": "598",
   "name": "Contact activated below SOC 2 (AUX 4) {10299}",
   "description": "Expert level. Range 0 to 100, default 30.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "%",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 600,
   "documented": "600",
   "name": "Delay 2 (AUX 4) {10300}",
   "description": "Expert level. Range 0 to 99, default 0.2.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "hours",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 602,
   "documented": "602",
   "name": "Contact activated with the SOC 3 of battery (AUX 4) {10301}",
   "description": "Expert level. Float 0.0 = no, 1.0 = yes.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "0": "No",
    "1": "Yes"
   },
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 604,
   "documented": "604",
   "name": "Contact activated below SOC 3 (AUX 4) {10302}",
   "description": "Expert level. Range 0 to 100, default 20.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "%",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 606,
   "documented": "606",
   "name": "Delay 3 (AUX 4) {10303}",
   "description": "Expert level. Range 0 to 99, default 0.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "hours",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 608,
   "documented": "608",
   "name": "Contact deactivated over SOC (AUX 4) {10304}",
   "description": "Expert level. Range 0 to 100, default 90.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "% SOC",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 610,
   "documented": "610",
   "name": "Delay to deactivate (AUX 4) {10305}",
   "description": "Expert level. Range 0 to 10, default 0.2.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "hours",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 612,
   "documented": "612",
   "name": "Deactivate if battery in floating phase (AUX 4) {10306}",
   "description": "Expert level. Float 0.0 = no, 1.0 = yes.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "0": "No",
    "1": "Yes"
   },
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 614,
   "documented": "614",
   "name": "Reset all settings (AUX 4) {10307}",
   "description": "Expert level. Write 1.0 to trigger.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "W",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 616,
   "documented": "616",
   "name": "Remote entry (AUX 1) {10308}",
   "description": "Expert level. Float 0.0 = no, 1.0 = yes.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "0": "No",
    "1": "Yes"
   },
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 618,
   "documented": "618",
   "name": "Remote entry (AUX 2) {10309}",
   "description": "Expert level. Float 0.0 = no, 1.0 = yes.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "0": "No",
    "1": "Yes"
   },
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 620,
   "documented": "620",
   "name": "Remote entry (AUX 3) {10310}",
   "description": "Expert level. Float 0.0 = no, 1.0 = yes.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "0": "No",
    "1": "Yes"
   },
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 622,
   "documented": "622",
   "name": "Remote entry (AUX 4) {10311}",
   "description": "Expert level. Float 0.0 = no, 1.0 = yes.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "0": "No",
    "1": "Yes"
   },
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 626,
   "documented": "626",
   "name": "Remote entry active {10313}",
   "description": "Expert level. Option code as a float; one option at a time.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "1": "Closed",
    "2": "Open",
    "4": "Edge"
   },
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 628,
   "documented": "628",
   "name": "ON/OFF command {10314}",
   "description": "Expert level. Float 0.0 = no, 1.0 = yes.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "0": "No",
    "1": "Yes"
   },
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 630,
   "documented": "630",
   "name": "Activated by AUX1 state {10315}",
   "description": "Expert level. Float 0.0 = no, 1.0 = yes.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "0": "No",
    "1": "Yes"
   },
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 632,
   "documented": "632",
   "name": "Start equalization {10316}",
   "description": "Expert level. Float 0.0 = no, 1.0 = yes.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "0": "No",
    "1": "Yes"
   },
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 634,
   "documented": "634",
   "name": "Send a message when remote entry changes state {10317}",
   "description": "Expert level. Float 0.0 = no, 1.0 = yes.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "0": "No",
    "1": "Yes"
   },
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 638,
   "documented": "638",
   "name": "Contact activated with fixed time schedule (AUX 1) {10319}",
   "description": "Expert level. Float 0.0 = no, 1.0 = yes.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "0": "No",
    "1": "Yes"
   },
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 640,
   "documented": "640",
   "name": "Start hour (AUX 1) {10320}",
   "description": "Expert level. Minutes after midnight as a float (0-1440).",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "min",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 642,
   "documented": "642",
   "name": "End hour (AUX 1) {10321}",
   "description": "Expert level. Minutes after midnight as a float (0-1440).",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "min",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 646,
   "documented": "646",
   "name": "Contact activated with fixed time schedule (AUX 2) {10323}",
   "description": "Expert level. Float 0.0 = no, 1.0 = yes.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "0": "No",
    "1": "Yes"
   },
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 648,
   "documented": "648",
   "name": "Start hour (AUX 2) {10324}",
   "description": "Expert level. Minutes after midnight as a float (0-1440).",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "min",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 650,
   "documented": "650",
   "name": "End hour (AUX 2) {10325}",
   "description": "Expert level. Minutes after midnight as a float (0-1440).",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "min",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 654,
   "documented": "654",
   "name": "Contact activated with fixed time schedule (AUX 3) {10327}",
   "description": "Expert level. Float 0.0 = no, 1.0 = yes.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "0": "No",
    "1": "Yes"
   },
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 656,
   "documented": "656",
   "name": "Start hour (AUX 3) {10328}",
   "description": "Expert level. Minutes after midnight as a float (0-1440).",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "min",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 658,
   "documented": "658",
   "name": "End hour (AUX 3) {10329}",
   "description": "Expert level. Minutes after midnight as a float (0-1440).",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "min",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 662,
   "documented": "662",
   "name": "Contact activated with fixed time schedule (AUX 4) {10331}",
   "description": "Expert level. Float 0.0 = no, 1.0 = yes.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "0": "No",
    "1": "Yes"
   },
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 664,
   "documented": "664",
   "name": "Start hour (AUX 4) {10332}",
   "description": "Expert level. Minutes after midnight as a float (0-1440).",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "min",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 666,
   "documented": "666",
   "name": "End hour (AUX 4) {10333}",
   "description": "Expert level. Minutes after midnight as a float (0-1440).",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "min",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 668,
   "documented": "668",
   "name": "Battery undervoltage {10334}",
   "description": "Expert level. Range 34 to 68.2, default 40.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "Vdc",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 670,
   "documented": "670",
   "name": "Partial shading check {10335}",
   "description": "Qualified service level. Float 0.0 = no, 1.0 = yes.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "0": "No",
    "1": "Yes"
   },
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 672,
   "documented": "672",
   "name": "Time between checks {10336}",
   "description": "Qualified service level. Range 1 to 30, default 5.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "min",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 684,
   "documented": "684",
   "name": "VarioTrack watchdog enabled (SCOM) {10342}",
   "description": "Installer level. Float 0.0 = no, 1.0 = yes.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "0": "No",
    "1": "Yes"
   },
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 686,
   "documented": "686",
   "name": "VarioTrack watchdog delay (SCOM) {10343}",
   "description": "Installer level. Range 10 to 300, default 60.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "sec",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 700,
   "documented": "700",
   "name": "Offset of PV voltage to start power derating {10350}",
   "description": "Installer level. Range -50 to -5, default -30.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "Vdc",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 702,
   "documented": "702",
   "name": "Battery current at PV max {10351}",
   "description": "Installer level. Range 0 to 80, default 5.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "Adc",
   "access": "RW",
   "values": null,
   "bits": null
  }
 ],
 "integration": {
  "summary": "Fit an Xcom-485i on the Studer communication bus and poll it as a Modbus RTU slave. Each Studer device answers at its own unit ID (offset set by DIP switches 1-2); read infos with function 04 and parameters with 03, always 2 registers at a time, and decode as big-endian float.",
  "minimum_registers": [
   {
    "table": "input_register",
    "address": 0,
    "why": "Battery voltage"
   },
   {
    "table": "input_register",
    "address": 2,
    "why": "Battery current"
   },
   {
    "table": "input_register",
    "address": 4,
    "why": "PV voltage"
   },
   {
    "table": "input_register",
    "address": 8,
    "why": "PV power"
   },
   {
    "table": "input_register",
    "address": 14,
    "why": "Energy produced today"
   },
   {
    "table": "input_register",
    "address": 18,
    "why": "Total produced energy"
   },
   {
    "table": "input_register",
    "address": 32,
    "why": "Operating mode"
   },
   {
    "table": "input_register",
    "address": 68,
    "why": "Type of error"
   }
  ],
  "enable": "Install the Xcom-485i on the Studer bus. DIP switches 1-2 set the unit-ID offset (0, 32, 64 or 128) and switches 7-8 set the baud rate (9600, 19200, 38400 or 115200). Frames are 8 data bits, even parity, 1 stop bit.",
  "watchdog": null,
  "quirks": [
   "Unit 21 addresses the first VarioTrack; multicast unit 20 reads the first such device and writes to all of them at once.",
   "Values are floats even for on/off and enumerated items: 1.0 = 0x3F800000."
  ],
  "setup": [
   "With DIP 1-2 off: unit 1 = Xcom-485i gateway, 2 = system, 10 = all Xtenders, 11-19 = single Xtenders, 20 = all VarioTracks, 21-35 = single VarioTracks, 40 = all VarioStrings, 41-55 = single VarioStrings, 60 = all BSP/Xcom-CAN BMS, 61 = the single BSP or Xcom-CAN BMS. Add the DIP offset to each.",
   "Single devices are numbered in the order shown on the RCC remote's device list.",
   "Allow up to 1 s for a reply and send one request at a time; the gateway is slower when the Studer bus is busy."
  ],
  "gotchas": [
   "Writing a parameter at its base register stores it in flash; cyclic writes should use base + 6000 (RAM only).",
   "Some parameters restart an internal timer or algorithm when changed while running.",
   "Parameter levels (Basic/Expert/Installer/QSP) are the RCC access levels printed in the appendix."
  ]
 },
 "page": "https://easymodbus.com/modbus-register-maps/studer-innotec/variotrack",
 "address_note": "address = 0-based Modbus wire (PDU) address; documented = as printed in the source.",
 "note": "Re-typed from the manufacturer's public documentation (see source) and verified against it. Registers vary by firmware and options; verify against the live device before writing."
}