 "manufacturer": "Studer Innotec",
 "manufacturer_slug": "studer-innotec",
 "model": "Xcom-CAN in BMS mode (lithium battery link, via Xcom-485i)",
 "model_slug": "xcom-can-bms",
 "short_model": "Xcom-CAN BMS",
 "aliases": [
  "Xcom-CAN",
  "Xcom-CAN BMS",
  "Xcom-485i"
 ],
 "equipment_type": "Battery inverter system (lithium battery BMS interface)",
 "applies_to": "Studer Xcom-CAN set to BMS mode (CAN link to a lithium battery BMS), read through an Xcom-485i Modbus RTU gateway, system release R706.",
 "summary": "In BMS mode the Studer Xcom-CAN links a lithium battery's BMS to the Xtender system and reports the battery's own values. An Xcom-485i on the Studer bus answers Modbus RTU for it. This map lists the Xcom-CAN BMS user infos (voltage, current, state of charge, BMS limits) as input registers and its parameters as holding registers.",
 "transport": [
  "RTU"
 ],
 "defaults": {
  "unit_id": 61,
  "baud": null,
  "parity": "Even",
  "data_bits": 8,
  "stop_bits": 1,
  "tcp_port": null
 },
 "addressing": {
  "convention": "0-based",
  "note": "The appendix lists the register exactly as it goes in the request. The protocol spec's example reads info 3001 from register 2 with start address 0x0002 in the frame, and parameter 1107 from register 14 (0x000E)."
 },
 "default_word_order": "ABCD",
 "firmware": "Studer system release R706 (appendix V1.6.44); Xcom-485i protocol V1.1.3",
 "source": {
  "title": "Technical specification Studer Modbus RTU Appendix V1.6.44 (with Technical specification Studer Modbus RTU Protocol V1.1.3)",
  "doc_number": "Appendix V1.6.44 (R706); Protocol V1.1.3",
  "revision_date": "2025-09-03",
  "url": "https://studer-innotec.com/wp-content/uploads/2025/09/Manuel-xcom-485i-technical-specification.zip",
  "pages": "Appendix pp. 26-29 (Xcom-CAN BMS parameters pp. 26-28, infos pp. 28-29); Protocol spec pp. 4-8 (bus settings, unit addressing), pp. 18-25 (examples, offsets, encoding). Both PDFs are inside the ZIP."
 },
 "notes": [
  "The Xcom-CAN BMS uses the same unit IDs (60/61) as the BSP; only one of the two can be in an installation.",
  "Every info and parameter is an IEEE 754 single-precision float in two registers, high word first. The protocol spec's example reads Xtender info 3001 as 0x41D3 0x3333 = 26.4 °C, and parameter 1107 as 0x4170 0x0000 = 15.0 A.",
  "Each request must read or write exactly 2 registers (one value); asking for more returns an exception. Infos use function 04, parameters function 03 to read and 16 to write.",
  "Parameter registers have three more views at fixed offsets: +2000 = minimum allowed value, +4000 = maximum allowed value (read only), +6000 = write to RAM only. Use the RAM-only offset for anything written repeatedly; flash is only guaranteed for about 1000 writes per parameter.",
  "Enumerated infos count 0, 1, 2 ...; enumerated parameters use one bit per option (1, 2, 4, 8), still sent as a float. Codes shown as '---' in the appendix are unused and left out of the value lists.",
  "Register names keep the Studer info/parameter number in braces, e.g. {3000}. The register is 2 x (number - base) for that device family.",
  "Parameters whose appendix format is MENU are menu headings, not values, and are left out. The appendix's per-row remarks column is not reproduced.",
  "The gateway's own input registers (pending messages at 0-4, device counts at 5-9, gateway identity at 10-14, on unit 1) and the system clock (holding registers 0-7 on unit 2) are described in the protocol spec but live at other unit IDs, so they are not in this register list.",
  "The protocol spec's first read example prints the value as 0x4170 in the PDU table but 0x41F0 in the serial-line frame; 0x4170 matches the stated 15.0 A."
 ],
 "registers": [
  {
   "table": "input_register",
   "address": 0,
   "documented": "0",
   "name": "Battery voltage {7000}",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "V",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "input_register",
   "address": 2,
   "documented": "2",
   "name": "Battery current {7001}",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "Adc",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "input_register",
   "address": 4,
   "documented": "4",
   "name": "State of Charge {7002}",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "input_register",
   "address": 6,
   "documented": "6",
   "name": "Power {7003}",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "W",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "input_register",
   "address": 14,
   "documented": "14",
   "name": "Ah charged today {7007}",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "Ah",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "input_register",
   "address": 16,
   "documented": "16",
   "name": "Ah discharged today {7008}",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "Ah",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "input_register",
   "address": 18,
   "documented": "18",
   "name": "Ah charged yesterday {7009}",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "Ah",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "input_register",
   "address": 20,
   "documented": "20",
   "name": "Ah discharged yesterday {7010}",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "Ah",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "input_register",
   "address": 44,
   "documented": "44",
   "name": "Minigrid State of Charge {7022}",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "input_register",
   "address": 58,
   "documented": "58",
   "name": "Battery temperature {7029}",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "input_register",
   "address": 60,
   "documented": "60",
   "name": "Battery voltage (minute avg) {7030}",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "V",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "input_register",
   "address": 62,
   "documented": "62",
   "name": "Battery current (minute avg) {7031}",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "Adc",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "input_register",
   "address": 64,
   "documented": "64",
   "name": "State of Charge (minute avg) {7032}",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "input_register",
   "address": 66,
   "documented": "66",
   "name": "Battery temperature (minute avg) {7033}",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "input_register",
   "address": 94,
   "documented": "94",
   "name": "Manufacturer State of Charge {7047}",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "input_register",
   "address": 106,
   "documented": "106",
   "name": "Battery Type {7053}",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "input_register",
   "address": 108,
   "documented": "108",
   "name": "BMS Version {7054}",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "input_register",
   "address": 110,
   "documented": "110",
   "name": "Nominal or remaining battery capacity (see battery documentation) {7055}",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "Ah",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "input_register",
   "address": 112,
   "documented": "112",
   "name": "Reserved Manufacturer ID {7056}",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "input_register",
   "address": 114,
   "documented": "114",
   "name": "State Of Health {7057}",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "input_register",
   "address": 116,
   "documented": "116",
   "name": "High resolution manufacturer State of Charge {7058}",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "input_register",
   "address": 118,
   "documented": "118",
   "name": "Local daily communication error counter (CAN) {7059}",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "input_register",
   "address": 122,
   "documented": "122",
   "name": "Charge voltage limit {7061}",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "V",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "input_register",
   "address": 124,
   "documented": "124",
   "name": "Discharge voltage limit {7062}",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "V",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "input_register",
   "address": 126,
   "documented": "126",
   "name": "Charge current limit {7063}",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "A",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "input_register",
   "address": 128,
   "documented": "128",
   "name": "Discharge current limit {7064}",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "A",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "input_register",
   "address": 130,
   "documented": "130",
   "name": "Recommended charge current {7065}",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "A",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "input_register",
   "address": 132,
   "documented": "132",
   "name": "Recommended discharge current {7066}",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "A",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "input_register",
   "address": 134,
   "documented": "134",
   "name": "Manufacturer name {7067}",
   "description": "Enumerated state, sent as a float (1.0 = code 1).",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": {
    "0": "OTHERS",
    "1": "BYD",
    "2": "PYLON",
    "3": "WECO"
   },
   "bits": null
  },
  {
   "table": "input_register",
   "address": 136,
   "documented": "136",
   "name": "State of Charge status {7068}",
   "description": "Enumerated state, sent as a float (1.0 = code 1).",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": {
    "0": "UNK. SOC",
    "1": "OVER GRID",
    "2": "AT GRID",
    "3": "UNDER GRID",
    "4": "UNDER ADA",
    "5": "AT BACKUP",
    "6": "UNDER BACK",
    "7": "END OF CH",
    "8": "OVER ENDC",
    "9": "FULL",
    "10": "NORMAL"
   },
   "bits": null
  },
  {
   "table": "input_register",
   "address": 138,
   "documented": "138",
   "name": "State of Charge for backup {7069}",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "input_register",
   "address": 140,
   "documented": "140",
   "name": "State of Charge for grid-feeding {7070}",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "input_register",
   "address": 142,
   "documented": "142",
   "name": "State of Charge for end of charge {7071}",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 8,
   "documented": "8",
   "name": "Restore default settings {6004}",
   "description": "Basic level. Write 1.0 to trigger.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "W",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 10,
   "documented": "10",
   "name": "Restore factory settings {6005}",
   "description": "Installer level. Write 1.0 to trigger.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "W",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 124,
   "documented": "124",
   "name": "SOC level for backup {6062}",
   "description": "Expert level. Range 0 to 100, default 30.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "%",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 126,
   "documented": "126",
   "name": "SOC level for grid feeding {6063}",
   "description": "Expert level. Range 0 to 100, default 98.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "%",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 128,
   "documented": "128",
   "name": "Use battery current limits instead of recommended values {6064}",
   "description": "Expert level. Float 0.0 = no, 1.0 = yes.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "0": "No",
    "1": "Yes"
   },
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 132,
   "documented": "132",
   "name": "Manufacturer SOC for 0% displayed {6066}",
   "description": "Expert level. Range 0 to 60, default 0.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "%",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 134,
   "documented": "134",
   "name": "Manufacturer SOC for 100% displayed {6067}",
   "description": "Expert level. Range 80 to 100, default 100.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "%",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 136,
   "documented": "136",
   "name": "Allow user to define the maximum charge current of the battery {6068}",
   "description": "Expert level. Float 0.0 = no, 1.0 = yes.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "0": "No",
    "1": "Yes"
   },
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 138,
   "documented": "138",
   "name": "Maximum charge current defined by user {6069}",
   "description": "Expert level. Range 0 to 10000, default 10.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "A",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 140,
   "documented": "140",
   "name": "SOC level under which battery discharge is stopped {6070}",
   "description": "Expert level. Range 0 to 100, default 15.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "%",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 142,
   "documented": "142",
   "name": "Use battery priority as energy source when SOC >= SOC for backup (not recommended in parallel) {6071}",
   "description": "Expert level. Float 0.0 = no, 1.0 = yes.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "0": "No",
    "1": "Yes"
   },
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 144,
   "documented": "144",
   "name": "Solar Inverter connected on AC-Out {6072}",
   "description": "Expert level. Float 0.0 = no, 1.0 = yes.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "0": "No",
    "1": "Yes"
   },
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 146,
   "documented": "146",
   "name": "Delta from user frequency to start derating of solar inverter {6073}",
   "description": "Expert level. Range 0 to 5, default 1.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "Hz",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 148,
   "documented": "148",
   "name": "Delta from user frequency to reach 100% derating of solar inverter {6074}",
   "description": "Expert level. Range 0 to 5, default 2.7.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "Hz",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 150,
   "documented": "150",
   "name": "SOC level for end of charge {6075}",
   "description": "Expert level. Range 80 to 100, default 100.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "%",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 152,
   "documented": "152",
   "name": "Allow user to define the maximum discharge current of the battery {6076}",
   "description": "Expert level. Float 0.0 = no, 1.0 = yes.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "0": "No",
    "1": "Yes"
   },
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 154,
   "documented": "154",
   "name": "Maximum discharge current defined by user {6077}",
   "description": "Expert level. Range 0 to 10000, default 10.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "A",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 156,
   "documented": "156",
   "name": "Charge current limit ratio {6078}",
   "description": "Expert level. Range 80 to 95, default 90.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "%",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 158,
   "documented": "158",
   "name": "Allow periodic full charging {6079}",
   "description": "Expert level. Float 0.0 = no, 1.0 = yes.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "0": "No",
    "1": "Yes"
   },
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 160,
   "documented": "160",
   "name": "Waiting time between two periodic full charges {6080}",
   "description": "Expert level. Range 1 to 1000, default 168.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "h",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 162,
   "documented": "162",
   "name": "Time fully charged before resetting periodical full charge {6081}",
   "description": "Expert level. Range 1 to 60, default 5.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "min",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 164,
   "documented": "164",
   "name": "Ki current regulation {6082}",
   "description": "Qualified service level. Range 1 to 100, default 15.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "%",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 172,
   "documented": "172",
   "name": "AC-Coupling priority {6086}",
   "description": "Expert level. Float 0.0 = no, 1.0 = yes.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "0": "No",
    "1": "Yes"
   },
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 174,
   "documented": "174",
   "name": "SOC level to start end of charge derating {6087}",
   "description": "Expert level. Range 80 to 100, default 90.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "%",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 176,
   "documented": "176",
   "name": "Charge current rate at end of charge {6088}",
   "description": "Expert level. Range 0 to 100, default 20.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "%",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 178,
   "documented": "178",
   "name": "Allow adaptative SOC for backup {6089}",
   "description": "Expert level. Float 0.0 = no, 1.0 = yes.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "0": "No",
    "1": "Yes"
   },
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 180,
   "documented": "180",
   "name": "Time before reseting adaptative SOC for Backup {6090}",
   "description": "Expert level. Range 1 to 60, default 5.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "min",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 182,
   "documented": "182",
   "name": "SOC in percent to reset adaptative SOC for Backup {6091}",
   "description": "Expert level. Range 80 to 100, default 99.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "%",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 184,
   "documented": "184",
   "name": "SOC in percent to increase adaptative SOC for Backup {6092}",
   "description": "Expert level. Range 20 to 100, default 98.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "%",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 186,
   "documented": "186",
   "name": "Discharge current limit ratio {6093}",
   "description": "Expert level. Range 80 to 95, default 95.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "%",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 188,
   "documented": "188",
   "name": "Enable minigrid {6094}",
   "description": "Installer level. Float 0.0 = no, 1.0 = yes.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "0": "No",
    "1": "Yes"
   },
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 190,
   "documented": "190",
   "name": "Enable minigrid as central {6095}",
   "description": "Installer level. Float 0.0 = no, 1.0 = yes.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "0": "No",
    "1": "Yes"
   },
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 194,
   "documented": "194",
   "name": "Frequency offset when minigrid energy is low {6097}",
   "description": "Installer level. Range -5 to 0, default -3.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "Hz",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 196,
   "documented": "196",
   "name": "Frequency offset when minigrid energy is full {6098}",
   "description": "Installer level. Range 0 to 5, default 3.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "Hz",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 198,
   "documented": "198",
   "name": "Forced activation of the minigrid genset {6099}",
   "description": "Installer level. Float 0.0 = no, 1.0 = yes.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "0": "No",
    "1": "Yes"
   },
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 200,
   "documented": "200",
   "name": "Delays for forcing activation of the minigrid genset {6100}",
   "description": "Installer level. Minutes after midnight as a float (0-1440).",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "min",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 202,
   "documented": "202",
   "name": "SoC to start forcing activation of the minigrid genset {6101}",
   "description": "Installer level. Range 0 to 100, default 20.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "%",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 204,
   "documented": "204",
   "name": "SoC to end forcing activation of the minigrid genset {6102}",
   "description": "Installer level. Range 0 to 100, default 50.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "%",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 208,
   "documented": "208",
   "name": "SOC in percent to reset periodical full charge {6104}",
   "description": "Expert level. Range 90 to 100, default 100.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "%",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 210,
   "documented": "210",
   "name": "Enable overcharge security with transfer {6105}",
   "description": "Installer level. Float 0.0 = no, 1.0 = yes.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "0": "No",
    "1": "Yes"
   },
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 212,
   "documented": "212",
   "name": "Use target voltage max. for limit {6106}",
   "description": "Installer level. Float 0.0 = no, 1.0 = yes.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "0": "No",
    "1": "Yes"
   },
   "bits": null
  }
 ],
 "integration": {
  "summary": "Fit an Xcom-485i on the Studer communication bus and poll it as a Modbus RTU slave. Each Studer device answers at its own unit ID (offset set by DIP switches 1-2); read infos with function 04 and parameters with 03, always 2 registers at a time, and decode as big-endian float.",
  "minimum_registers": [
   {
    "table": "input_register",
    "address": 0,
    "why": "Battery voltage"
   },
   {
    "table": "input_register",
    "address": 2,
    "why": "Battery current"
   },
   {
    "table": "input_register",
    "address": 4,
    "why": "State of charge"
   },
   {
    "table": "input_register",
    "address": 6,
    "why": "Battery power"
   },
   {
    "table": "input_register",
    "address": 122,
    "why": "BMS charge voltage limit"
   },
   {
    "table": "input_register",
    "address": 126,
    "why": "BMS charge current limit"
   }
  ],
  "enable": "Install the Xcom-485i on the Studer bus. DIP switches 1-2 set the unit-ID offset (0, 32, 64 or 128) and switches 7-8 set the baud rate (9600, 19200, 38400 or 115200). Frames are 8 data bits, even parity, 1 stop bit.",
  "watchdog": null,
  "quirks": [
   "Unit 61 addresses the first Xcom-CAN BMS; multicast unit 60 reads the first such device and writes to all of them at once.",
   "Values are floats even for on/off and enumerated items: 1.0 = 0x3F800000."
  ],
  "setup": [
   "With DIP 1-2 off: unit 1 = Xcom-485i gateway, 2 = system, 10 = all Xtenders, 11-19 = single Xtenders, 20 = all VarioTracks, 21-35 = single VarioTracks, 40 = all VarioStrings, 41-55 = single VarioStrings, 60 = all BSP/Xcom-CAN BMS, 61 = the single BSP or Xcom-CAN BMS. Add the DIP offset to each.",
   "Single devices are numbered in the order shown on the RCC remote's device list.",
   "Allow up to 1 s for a reply and send one request at a time; the gateway is slower when the Studer bus is busy."
  ],
  "gotchas": [
   "Writing a parameter at its base register stores it in flash; cyclic writes should use base + 6000 (RAM only).",
   "Some parameters restart an internal timer or algorithm when changed while running.",
   "Parameter levels (Basic/Expert/Installer/QSP) are the RCC access levels printed in the appendix."
  ]
 },
 "page": "https://easymodbus.com/modbus-register-maps/studer-innotec/xcom-can-bms",
 "address_note": "address = 0-based Modbus wire (PDU) address; documented = as printed in the source.",
 "note": "Re-typed from the manufacturer's public documentation (see source) and verified against it. Registers vary by firmware and options; verify against the live device before writing."
}