 "manufacturer": "Swegon",
 "manufacturer_slug": "swegon",
 "model": "REACT Parasol Zenith with Belimo actuator (Modbus RTU)",
 "model_slug": "react-parasol-zenith",
 "short_model": "REACT Parasol Zenith",
 "aliases": [
  "Parasol Zenith REACT",
  "REACT damper actuator"
 ],
 "equipment_type": "Actuator / valve (comfort module air damper)",
 "applies_to": "Swegon REACT Parasol Zenith comfort modules fitted with the Belimo Modbus actuator; Swegon Modbus settings sheet dated 2022-08-10.",
 "summary": "The REACT version of the Parasol Zenith comfort module uses a Belimo actuator with a Modbus RTU interface. Over the bus a BMS can set the damper or flow setpoint, force open/close/min/max, run adaption or test, and read position, relative and absolute airflow, sensor input, service flags and the bus-watchdog settings.",
 "transport": [
  "RTU"
 ],
 "defaults": {
  "unit_id": null,
  "baud": 19200,
  "parity": "Even",
  "data_bits": 8,
  "stop_bits": 1,
  "tcp_port": null
 },
 "addressing": {
  "convention": "0-based",
  "note": "Every table gives both a register number (No.) and the protocol Address, with Address = No. - 1 (No. 1 = address 0). The Address column is used here; the 'documented' field shows both."
 },
 "default_word_order": "CDAB",
 "firmware": null,
 "source": {
  "title": "REACT Parasol Zenith - Modbus settings / Modbus-installningar (Belimo actuator)",
  "doc_number": null,
  "revision_date": "2022-08-10",
  "url": "https://www.swegon.com/siteassets/_products-documents-archive/room-management-systems/_en/react_parasol_zenith-modbus-m.pdf",
  "pages": "p. 1-2 communication settings and register overview, pp. 3-5 register descriptions"
 },
 "notes": [
  "The two 32-bit flow values are split as LowWord (lower 16 bits) at the first register and HighWord at the next, so they are CDAB; scale 0.001 in the unit chosen in No. 118.",
  "Registers No. 10, 112, 115 and 116 are unused (dash) and not listed.",
  "Absolute position (No. 6) is in degrees or mm depending on the actuator type.",
  "Default communication setting 14: 19200 baud, 8 data bits, even parity, 1 stop bit, 0 ms delay; also selectable 9600-115200 baud and 8N2, 8N1, 8E1, 8O1.",
  "Bus termination (No. 100) is read-only in the register overview but marked R/W in the description table, which also says it is set with the configuration tools; it is listed here as read-only.",
  "The Swedish column on page 5 places the LW/HW labels one row higher than the English text; the English description (No. 113 = lower 16 bits, No. 114 = upper 16 bits) and the overview table are followed here."
 ],
 "registers": [
  {
   "table": "holding_register",
   "address": 0,
   "documented": "No. 1 / Address 0",
   "name": "Setpoint",
   "description": "Actuator setpoint between Min (No. 106) and Max (No. 107).",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "%",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1,
   "documented": "No. 2 / Address 1",
   "name": "Override Control",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "None",
    "1": "Open",
    "2": "Close",
    "3": "Min",
    "4": "Mid",
    "5": "Max"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2,
   "documented": "No. 3 / Address 2",
   "name": "Command",
   "description": "Returns to 0 after the command; Reset clears service info.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "None",
    "1": "Adaption",
    "2": "Test",
    "3": "Sync",
    "4": "Reset"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 3,
   "documented": "No. 4 / Address 3",
   "name": "Actuator Type",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Actuator not connected",
    "1": "Air / Water",
    "2": "VAV / EPIV",
    "3": "Fire",
    "4": "Energy Valve",
    "5": "6-way EPIV"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 4,
   "documented": "No. 5 / Address 4",
   "name": "Relative Position",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 5,
   "documented": "No. 6 / Address 5",
   "name": "Absolute Position",
   "description": "Degrees for rotary, mm for linear actuators.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 6,
   "documented": "No. 7 / Address 6",
   "name": "Relative volumetric flow",
   "description": "Percent of Vnom.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 7,
   "documented": "No. 8 / Address 7",
   "name": "Absolute volumetric flow",
   "description": "0 to Vnom; the unit column reads 'm³/h Pa'.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "m³/h",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8,
   "documented": "No. 9 / Address 8",
   "name": "Sensor 1 Value",
   "description": "mV if sensor type is Active, 0/1 if Switch.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 10,
   "documented": "No. 11 / Address 10",
   "name": "Absolute volumetric flow (unit selected)",
   "description": "Flow in the unit chosen in No. 118; low word at No. 11.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 0.001,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 12,
   "documented": "No. 13 / Address 12",
   "name": "Setpoint Analog",
   "description": "Setpoint when the actuator follows the analog signal.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 99,
   "documented": "No. 100 / Address 99",
   "name": "Bus Termination",
   "description": "Shows whether the 120 ohm terminator is on; set it with the configuration tools.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Inactive",
    "1": "Active (120 ohm)"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 100,
   "documented": "No. 101 / Address 100",
   "name": "Series Number 1st part",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 101,
   "documented": "No. 102 / Address 101",
   "name": "Series Number 2nd part",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 102,
   "documented": "No. 103 / Address 102",
   "name": "Series Number 4th part",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 103,
   "documented": "No. 104 / Address 103",
   "name": "Firmware Version",
   "description": "e.g. 302 = version 3.02.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 104,
   "documented": "No. 105 / Address 104",
   "name": "Malfunction and Service Information",
   "description": "Bit-coded; more than one bit can be set.",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "1": "Mechanical travel increased",
    "2": "Actuator cannot move",
    "8": "Internal activity",
    "9": "Gear disengaged",
    "10": "Bus watchdog triggered"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 105,
   "documented": "No. 106 / Address 105",
   "name": "Vmin",
   "description": "Must be at most Vmax.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "%",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 106,
   "documented": "No. 107 / Address 106",
   "name": "Vmax",
   "description": "Must be at least Vmin and above 20 %.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "%",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 107,
   "documented": "No. 108 / Address 107",
   "name": "Sensor 1 Type",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "None",
    "1": "Active / Hybrid",
    "4": "Switch"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 108,
   "documented": "No. 109 / Address 108",
   "name": "Bus Fail Position",
   "description": "Position taken when the bus watchdog expires.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "None / last setpoint",
    "1": "Fast close",
    "2": "Fast open",
    "3": "Mid position"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 109,
   "documented": "No. 110 / Address 109",
   "name": "Timeout for Bus Watchdog",
   "description": "0 = watchdog off, max 3600 s.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "s",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 110,
   "documented": "No. 111 / Address 110",
   "name": "Nominal volumetric flow",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "m³/h",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 112,
   "documented": "No. 113 / Address 112",
   "name": "Nominal volumetric flow (unit selected)",
   "description": "Vnom in the unit chosen in No. 118; low word at No. 113.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 0.001,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 116,
   "documented": "No. 117 / Address 116",
   "name": "Control Mode",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Position control",
    "1": "Flow control"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 117,
   "documented": "No. 118 / Address 117",
   "name": "Unit Selection Flow",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "m³/s",
    "1": "m³/h",
    "2": "l/s",
    "3": "l/min",
    "4": "l/h",
    "5": "gpm",
    "6": "cfm"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 118,
   "documented": "No. 119 / Address 118",
   "name": "Setpoint Source",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Analog (0-10 V on wire 3)",
    "1": "Bus (Modbus No. 1)"
   },
   "bits": null,
   "offset": 0
  }
 ],
 "integration": {
  "summary": "Write the setpoint in 0.01 % to address 0 (with Setpoint Source = Bus) and read relative position (address 4) and relative or absolute flow (addresses 6-7). Use Override Control (address 1) to force open/close and the bus watchdog (addresses 108-109) for a safe position on comms loss.",
  "minimum_registers": [
   {
    "table": "holding_register",
    "address": 0,
    "why": "Setpoint %"
   },
   {
    "table": "holding_register",
    "address": 1,
    "why": "Override control"
   },
   {
    "table": "holding_register",
    "address": 4,
    "why": "Relative position"
   },
   {
    "table": "holding_register",
    "address": 6,
    "why": "Relative flow"
   },
   {
    "table": "holding_register",
    "address": 7,
    "why": "Absolute flow m³/h"
   },
   {
    "table": "holding_register",
    "address": 104,
    "why": "Malfunction flags"
   },
   {
    "table": "holding_register",
    "address": 118,
    "why": "Setpoint source"
   }
  ],
  "enable": "Setpoint Source (address 118) must be Bus for Modbus setpoints. Bus termination is set with the actuator configuration tools.",
  "watchdog": "Bus Fail Position (address 108) and Timeout for Bus Watchdog (address 109, 0-3600 s; 0 = off). If neither setpoint nor override is rewritten within the timeout, the actuator goes to the fail position and sets bit 10 in address 104.",
  "quirks": [
   "Register numbers in the sheet start at 1; send Address = No. - 1.",
   "32-bit flows are low word first."
  ],
  "setup": [
   "External 120 ohm termination at the line ends; No. 100 shows whether the built-in terminator is active.",
   "Max 32 nodes without a repeater."
  ],
  "gotchas": [
   "Vmax must stay above 20 % and at or above Vmin."
  ]
 },
 "page": "https://easymodbus.com/modbus-register-maps/swegon/react-parasol-zenith",
 "address_note": "address = 0-based Modbus wire (PDU) address; documented = as printed in the source.",
 "note": "Re-typed from the manufacturer's public documentation (see source) and verified against it. Registers vary by firmware and options; verify against the live device before writing."
}