 "manufacturer": "TECO-Westinghouse",
 "manufacturer_slug": "teco-westinghouse",
 "model": "A510 inverter (Modbus RTU/ASCII)",
 "model_slug": "a510",
 "short_model": "A510",
 "aliases": [
  "TECO A510",
  "A510s"
 ],
 "equipment_type": "Variable frequency drive",
 "applies_to": "TECO-Westinghouse A510 inverters using the built-in RS-485 port (CN6), per communication addendum DOCUMENT-TECO-A510-AC001 Ver01 (2015-04).",
 "summary": "The A510 is TECO-Westinghouse's general-purpose vector inverter with a built-in RS-485 port speaking Modbus RTU or ASCII. Commands, frequency, torque and speed limit are written to 2501H-2504H; status, fault and warning codes and monitors are read from 2520H-252FH. Each parameter nn-mm has its own register, with the group in the high byte and the number in the low byte.",
 "transport": [
  "RTU",
  "ASCII"
 ],
 "defaults": {
  "unit_id": null,
  "baud": null,
  "parity": null,
  "data_bits": null,
  "stop_bits": null,
  "tcp_port": null
 },
 "addressing": {
  "convention": "hex 0-based",
  "note": "Register numbers are hex and sent unchanged (2520H is sent as 25 20; the 03H example reads 01 23). Parameters map group to the high byte and number to the low byte (11-44 = 0B2CH), except 12-00 which is 32-bit at 2510H (high word) / 2511H (low word)."
 },
 "default_word_order": null,
 "firmware": null,
 "source": {
  "title": "A510 Communication Addendum Modbus RTU/ASCII",
  "doc_number": "DOCUMENT-TECO-A510-AC001 Ver01",
  "revision_date": "2015-04",
  "url": "https://tecowestinghouse.com/PDF/A510_comm_addendum.pdf",
  "pages": "pp. 1-1 to 1-4 (connection, frames, exceptions), p. 1-5 (command data), pp. 1-6 to 1-8 (monitor data), parameter registers from p. 1-13"
 },
 "notes": [
  "Frequency registers are 0.01 Hz, but the addendum says resolution becomes 0.1 Hz when the motor's maximum output frequency is above 300 Hz.",
  "The addendum does not name the drive parameters for node address, baud rate, parity or run/frequency source; set those per the A510 manual.",
  "2521H (faults) and 2528H (warnings) are code tables, mapped as enums; empty table cells are omitted.",
  "Left out: 2505H and 252AH AO1 command/readback (raw scale not stated), 2506H AO2 command, 2507H DO and 2529H digital output state (no bit list).",
  "Parameter 12-00 is 32-bit (2510H high word, 2511H low word) and is not listed."
 ],
 "registers": [
  {
   "table": "holding_register",
   "address": 9473,
   "documented": "2501H",
   "name": "Operation signal",
   "description": "Run, direction, fault, reset, comm inputs S1-S8, inverter/torque mode.",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": {
    "0": "Run (0 stop)",
    "1": "Reverse (0 forward)",
    "2": "External fault",
    "3": "Fault reset",
    "6": "Comm input S1",
    "7": "Comm input S2",
    "8": "Comm input S3",
    "9": "Comm input S4",
    "10": "Comm input S5",
    "11": "Comm input S6",
    "12": "Comm input S7",
    "13": "Comm input S8",
    "14": "Inverter mode",
    "15": "Torque command set by communication"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 9474,
   "documented": "2502H",
   "name": "Frequency command",
   "description": "0.1 Hz instead if max output frequency exceeds 300 Hz.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "Hz",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 9475,
   "documented": "2503H",
   "name": "Torque command",
   "description": "+/-8192 = +/-100 % of rated torque.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01220703125,
   "units": "%",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 9476,
   "documented": "2504H",
   "name": "Speed limit",
   "description": "+/-120 = +/-120 %.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "%",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 9504,
   "documented": "2520H",
   "name": "State signal",
   "description": "",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "0": "Running",
    "1": "Reverse",
    "2": "Inverter ready",
    "3": "Fault active",
    "4": "Warning",
    "5": "Zero speed",
    "6": "Is 440 V",
    "7": "Frequency agree",
    "8": "Set frequency agree",
    "9": "Frequency detection 1",
    "10": "Frequency detection 2",
    "11": "Under voltage",
    "12": "Baseblock",
    "13": "Frequency reference not from comm",
    "14": "Sequence not from comm",
    "15": "Over torque"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 9505,
   "documented": "2521H",
   "name": "Error description",
   "description": "Active fault code.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "1": "UV",
    "2": "OC",
    "3": "OV",
    "4": "OH1",
    "5": "OL1",
    "6": "OL2",
    "7": "OT",
    "8": "UT",
    "9": "SC",
    "10": "Ground OC",
    "11": "Fuse broken",
    "12": "Input phase loss",
    "13": "Output phase loss",
    "14": "PG overspeed",
    "15": "PG open",
    "16": "PG speed deviation",
    "17": "External fault 01",
    "18": "External fault 02",
    "19": "External fault 03",
    "20": "External fault 04",
    "21": "External fault 05",
    "22": "External fault 06",
    "23": "External fault 07",
    "24": "External fault 08",
    "25": "FB",
    "26": "OPR",
    "28": "CE",
    "29": "STO",
    "30": "Over torque 2",
    "38": "CF07",
    "41": "OLDOP",
    "47": "SS1",
    "48": "CF20",
    "49": "RUN"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 9506,
   "documented": "2522H",
   "name": "DI state",
   "description": "Terminals S1-S8.",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "0": "Terminal S1",
    "1": "Terminal S2",
    "2": "Terminal S3",
    "3": "Terminal S4",
    "4": "Terminal S5",
    "5": "Terminal S6",
    "6": "Terminal S7",
    "7": "Terminal S8"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 9507,
   "documented": "2523H",
   "name": "Frequency command",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "Hz",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 9508,
   "documented": "2524H",
   "name": "Output frequency",
   "description": "0.1 Hz instead if max output frequency exceeds 300 Hz.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "Hz",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 9510,
   "documented": "2526H",
   "name": "DC voltage",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "V",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 9511,
   "documented": "2527H",
   "name": "Output current",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "A",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 9512,
   "documented": "2528H",
   "name": "Alarm description",
   "description": "Active warning code.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "No alarm",
    "1": "OV",
    "2": "UV",
    "3": "OL2",
    "4": "OH2",
    "6": "OT",
    "9": "UT",
    "10": "OS",
    "11": "PGO",
    "12": "DEV",
    "13": "CE",
    "14": "CALL",
    "16": "EF0",
    "17": "EF1",
    "18": "EF2",
    "19": "EF3",
    "20": "EF4",
    "21": "EF5",
    "22": "EF6",
    "23": "EF7",
    "24": "EF8",
    "26": "CLB",
    "28": "CT",
    "29": "USP",
    "30": "RDE",
    "31": "WRE",
    "32": "FB",
    "33": "VRYE",
    "34": "SE01",
    "35": "SE02",
    "36": "SE03",
    "38": "SE05",
    "39": "HPERR",
    "40": "EF",
    "43": "RDP",
    "45": "OL1",
    "46": "HP_ER",
    "47": "SE10",
    "49": "BB1",
    "50": "BB2",
    "51": "BB3",
    "52": "BB4",
    "53": "BB5",
    "54": "BB6",
    "55": "BB7",
    "56": "BB8",
    "61": "RETRY",
    "62": "SE07",
    "63": "SE08",
    "65": "OH1",
    "66": "FIRE",
    "67": "ES",
    "68": "STP1",
    "69": "BDERR",
    "70": "EPERR",
    "71": "ADCER",
    "73": "STP0",
    "74": "ENC",
    "75": "STP2"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 9515,
   "documented": "252BH",
   "name": "AO2 value",
   "description": "0-1000 = 0.00-10.00 V or 4-20 mA.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 9516,
   "documented": "252CH",
   "name": "AI1 input",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 9517,
   "documented": "252DH",
   "name": "AI2 input",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 9519,
   "documented": "252FH",
   "name": "Model check",
   "description": "A510 identification value.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  }
 ],
 "integration": {
  "summary": "Set the node address and serial parameters and select communication as run/frequency source, then write 2501H and 2502H (0.01 Hz) and poll 2520H-2528H.",
  "minimum_registers": [
   {
    "table": "holding_register",
    "address": 9473,
    "why": "Run/stop, direction, reset"
   },
   {
    "table": "holding_register",
    "address": 9474,
    "why": "Frequency command"
   },
   {
    "table": "holding_register",
    "address": 9504,
    "why": "Status bits"
   },
   {
    "table": "holding_register",
    "address": 9505,
    "why": "Fault code"
   },
   {
    "table": "holding_register",
    "address": 9508,
    "why": "Output frequency"
   },
   {
    "table": "holding_register",
    "address": 9511,
    "why": "Output current"
   },
   {
    "table": "holding_register",
    "address": 9512,
    "why": "Warning code"
   }
  ],
  "enable": "Set node address and communication settings at the keypad and select communication as run and frequency source (parameter numbers are in the A510 manual). Bit 15 of 2501H with 2503H gives torque control by communication.",
  "watchdog": null,
  "quirks": [
   "Registers are hex.",
   "Functions 03H, 06H, 08H and 10H; maximum frame 80 bytes.",
   "Node addresses 01H-FEH; 00H is broadcast.",
   "Exception 04 means more than 32 registers were requested."
  ],
  "setup": [
   "RS-485 on CN6: S+ / S- per the CN6 pin-out.",
   "The addendum shows 120 ohm terminators on p. 1-1 but says 220 ohm in Appendix A; up to 31 inverters."
  ],
  "gotchas": [
   "Exception codes: 01 function, 02 register number, 03 data setting, 04 more than 32 registers.",
   "Inverter response time is about 10 ms."
  ]
 },
 "page": "https://easymodbus.com/modbus-register-maps/teco-westinghouse/a510",
 "address_note": "address = 0-based Modbus wire (PDU) address; documented = as printed in the source.",
 "note": "Re-typed from the manufacturer's public documentation (see source) and verified against it. Registers vary by firmware and options; verify against the live device before writing."
}