 "manufacturer": "TECO-Westinghouse",
 "manufacturer_slug": "teco-westinghouse",
 "model": "EV micro inverter (Modbus RTU/ASCII)",
 "model_slug": "ev",
 "short_model": "EV",
 "aliases": [
  "TECO EV",
  "EV Inverter Series"
 ],
 "equipment_type": "Variable frequency drive",
 "applies_to": "TECO-Westinghouse EV series micro inverters with the RS-485 option card, per the EV Inverter Series Modbus Communication Manual.",
 "summary": "The EV is a legacy TECO-Westinghouse micro inverter that speaks Modbus RTU or ASCII through an RS-485 option card. The run command and frequency go to 00E6H/00E7H, status, fault code and monitors are read from 00EFH-00F8H, and each F/C parameter has its own register listed in section 6. This map covers the command and monitor data.",
 "transport": [
  "RTU",
  "ASCII"
 ],
 "defaults": {
  "unit_id": null,
  "baud": null,
  "parity": null,
  "data_bits": null,
  "stop_bits": null,
  "tcp_port": null
 },
 "addressing": {
  "convention": "hex 0-based",
  "note": "Register numbers are hex and sent unchanged: the 03H example reads start address 00 F2 (frequency command monitor) and gets 1770H. Parameters use the register table in section 6 (e.g. F01 = 0001H, C00 = 0064H), which is not sequential."
 },
 "default_word_order": null,
 "firmware": null,
 "source": {
  "title": "EV Inverter Series: Modbus Communication Manual",
  "doc_number": null,
  "revision_date": null,
  "url": "https://tecowestinghouse.com/PDF/ev_modbus_manual.pdf",
  "pages": "p. 1 (hardware), p. 7 (command data), pp. 8-9 (monitor data), pp. 10-14 (function examples), pp. 15-16 (parameter register addresses)"
 },
 "notes": [
  "00E7H frequency command has no printed scale; the 06H example labels the write '60.0 Hz' but sends 1770H (6000), so it is left unscaled. The 00F2H/00F3H monitors are 100 = 1 Hz.",
  "Left out: 00F9H/00FAH AIN values (footnote *1 not explained) and the remote-keypad registers.",
  "The section 6 table maps every F and C parameter to an individual hex register; those are not expanded here.",
  "Communication setup parameters (address, baud, protocol) are not named in this manual; see the EV drive manual."
 ],
 "registers": [
  {
   "table": "holding_register",
   "address": 230,
   "documented": "00E6H",
   "name": "Operation command",
   "description": "Run, direction, EFO, reset, jog, comm inputs S1-S3.",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": {
    "0": "Run (0 stop)",
    "1": "Reverse (0 forward)",
    "2": "External fault (EFO)",
    "3": "Fault reset",
    "4": "Jog",
    "5": "Comm input S1",
    "6": "Comm input S2",
    "7": "Comm input S3"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 231,
   "documented": "00E7H",
   "name": "Frequency command",
   "description": "Scale not printed; see notes.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 239,
   "documented": "00EFH",
   "name": "Operation state",
   "description": "",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "0": "Running",
    "1": "Reverse",
    "2": "Ready",
    "3": "Abnormal",
    "4": "Data setting error"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 240,
   "documented": "00F0H",
   "name": "Fault description",
   "description": "Active fault code.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Normal",
    "1": "Inverter over heat (OH)",
    "2": "Over current at stop (OC)",
    "3": "Under voltage (LV)",
    "4": "Over voltage (OV)",
    "5": "External BB (b.b.)",
    "6": "CPU interrupted (CT)",
    "7": "PID feedback signal loss (PID)",
    "8": "EEPROM abnormal (EPR)",
    "9": "Inverter overload (OL2)",
    "10": "Motor overload (OL1)",
    "11": "Emergency stop (E.S.)",
    "13": "Over current at constant speed (OCC)",
    "14": "Over current during accelerating (OCA)",
    "15": "Over current during decelerating (OCD)",
    "16": "Over current at startup (OCS)",
    "17": "Under voltage during running (LVC)",
    "18": "Over voltage at constant speed / decelerating (OVC)",
    "19": "Inverter over heat at constant speed (OHC)",
    "20": "Stop at 0 Hz (SP0)",
    "21": "Direct start disable (SP1)",
    "22": "Control panel emergency stop (SP2)",
    "23": "Keypad operation error (ER1)",
    "24": "Parameter setting error (ER2)",
    "25": "Analog converting error (ER4)",
    "26": "Modifying parameter in communication (ER5)",
    "27": "Communication failure (ER6)",
    "28": "Incorrect parameter setting (ER7)",
    "29": "Factory setting error (ER8)",
    "30": "Copy (CPY)",
    "31": "Compare (CPR)",
    "32": "Copy error (EP1)",
    "33": "Compare error (EP2)",
    "34": "Inverter over speed (OVS)",
    "35": "Over current limit (OCL)"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 241,
   "documented": "00F1H",
   "name": "Terminal status",
   "description": "",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "0": "S1 closed",
    "1": "S2 closed",
    "2": "S3 closed",
    "3": "S4 closed",
    "6": "AIN closed",
    "7": "Relay 1 on"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 242,
   "documented": "00F2H",
   "name": "Frequency command",
   "description": "100 = 1 Hz.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "Hz",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 243,
   "documented": "00F3H",
   "name": "Output frequency",
   "description": "100 = 1 Hz.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "Hz",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 244,
   "documented": "00F4H",
   "name": "Output voltage command",
   "description": "10 = 1 V.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "V",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 245,
   "documented": "00F5H",
   "name": "DC voltage",
   "description": "1 = 1 V.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "V",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 246,
   "documented": "00F6H",
   "name": "Output current",
   "description": "10 = 1 A.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "A",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 247,
   "documented": "00F7H",
   "name": "PID feedback",
   "description": "10 = 1 % of max output frequency.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 248,
   "documented": "00F8H",
   "name": "PID input",
   "description": "Signed; 10 = 1 % of max output frequency.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  }
 ],
 "integration": {
  "summary": "Fit the RS-485 option card, set the follower address and serial settings on the drive, then write 00E6H (run bits) and 00E7H (frequency) and poll 00EFH-00F6H.",
  "minimum_registers": [
   {
    "table": "holding_register",
    "address": 230,
    "why": "Run/stop, direction, reset"
   },
   {
    "table": "holding_register",
    "address": 231,
    "why": "Frequency command"
   },
   {
    "table": "holding_register",
    "address": 239,
    "why": "Operation state"
   },
   {
    "table": "holding_register",
    "address": 240,
    "why": "Fault code"
   },
   {
    "table": "holding_register",
    "address": 243,
    "why": "Output frequency"
   },
   {
    "table": "holding_register",
    "address": 246,
    "why": "Output current"
   }
  ],
  "enable": "Install the RS-485 option card and set address and communication parameters per the EV drive manual.",
  "watchdog": null,
  "quirks": [
   "Registers are hex.",
   "Functions 03H, 06H, 08H and 10H; maximum frame 80 bytes.",
   "Follower addresses 01H-FEH.",
   "Parameter registers in section 6 are not in parameter order (e.g. F07 = 0008H, F08 = 0007H)."
  ],
  "setup": [
   "RS-485 via the option card terminals RSA/RSB; 120 ohm, 1/4 W terminators at both ends."
  ],
  "gotchas": [
   "Unused bits read as 0; registers marked not used are read-only."
  ]
 },
 "page": "https://easymodbus.com/modbus-register-maps/teco-westinghouse/ev",
 "address_note": "address = 0-based Modbus wire (PDU) address; documented = as printed in the source.",
 "note": "Re-typed from the manufacturer's public documentation (see source) and verified against it. Registers vary by firmware and options; verify against the live device before writing."
}