 "manufacturer": "TECO-Westinghouse",
 "manufacturer_slug": "teco-westinghouse",
 "model": "F510 HVAC fan/pump inverter (Modbus RTU/ASCII)",
 "model_slug": "f510",
 "short_model": "F510",
 "aliases": [
  "TECO F510",
  "F510 HVAC drive"
 ],
 "equipment_type": "Variable frequency drive (HVAC fan / pump)",
 "applies_to": "TECO-Westinghouse F510 HVAC inverters using the built-in RS-485 port (CN6) in Modbus mode, per communication addendum DOCUMENT-TECO-F510-AC001 Ver01 (2015-03).",
 "summary": "The F510 is TECO-Westinghouse's HVAC fan and pump inverter; its RS-485 port supports Modbus RTU/ASCII as well as BACnet MS/TP and Metasys N2. Run/stop and frequency (0.01 Hz) are written to 2501H/2502H, and status, fault and warning codes and monitors are read from 2520H-252FH. Each parameter nn-mm has its own register, with the group in the high byte and the number in the low byte.",
 "transport": [
  "RTU",
  "ASCII"
 ],
 "defaults": {
  "unit_id": null,
  "baud": null,
  "parity": null,
  "data_bits": null,
  "stop_bits": null,
  "tcp_port": null
 },
 "addressing": {
  "convention": "hex 0-based",
  "note": "Register numbers are hex and sent unchanged (2520H is sent as 25 20). Parameters map group to the high byte and number to the low byte, except 12-00 which is 32-bit at 2510H (high word) / 2511H (low word)."
 },
 "default_word_order": null,
 "firmware": null,
 "source": {
  "title": "F510 Communication Addendum Modbus RTU/ASCII, BACnet, Metasys N2",
  "doc_number": "DOCUMENT-TECO-F510-AC001 Ver01",
  "revision_date": "2015-03",
  "url": "https://tecowestinghouse.com/PDF/F510_comm_addendum.pdf",
  "pages": "pp. 1-1 to 1-4 (connection, frames, exceptions), p. 1-5 (command data), pp. 1-6 to 1-8 (monitor data), parameter registers from p. 1-13, network p. A-1"
 },
 "notes": [
  "Unlike the A510/E510 Compact addenda, the F510 monitor table prints no units for 2523H, 2524H, 2526H and 2527H, so they are listed raw.",
  "The addendum does not name the drive parameters for node address, baud rate, parity or run/frequency source; set those per the F510 manual.",
  "2521H (faults) and 2528H (warnings) are code tables, mapped as enums.",
  "Left out: 2507H DO, 2529H digital output state (no bit list), 252CH/252DH analog inputs (no unit).",
  "Parameter 12-00 is 32-bit (2510H high word, 2511H low word) and is not listed."
 ],
 "registers": [
  {
   "table": "holding_register",
   "address": 9473,
   "documented": "2501H",
   "name": "Operation signal",
   "description": "Run, direction, fault, reset, comm inputs S1-S6, inverter mode.",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": {
    "0": "Run (0 stop)",
    "1": "Reverse (0 forward)",
    "2": "External fault",
    "3": "Fault reset",
    "6": "Comm input S1",
    "7": "Comm input S2",
    "8": "Comm input S3",
    "9": "Comm input S4",
    "10": "Comm input S5",
    "11": "Comm input S6",
    "14": "Inverter mode"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 9474,
   "documented": "2502H",
   "name": "Frequency command",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "Hz",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 9477,
   "documented": "2505H",
   "name": "AO1 command",
   "description": "0-1000 = 0.00-10.00 V or 4-20 mA.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 9478,
   "documented": "2506H",
   "name": "AO2 command",
   "description": "0-1000 = 0.00-10.00 V or 4-20 mA.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 9504,
   "documented": "2520H",
   "name": "State signal",
   "description": "",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "0": "Running",
    "1": "Reverse",
    "2": "Inverter ready",
    "3": "Fault",
    "4": "Warning",
    "5": "Zero speed",
    "6": "Is 440 V",
    "7": "Frequency agree",
    "8": "Set frequency agree",
    "9": "Frequency detection 1",
    "10": "Frequency detection 2",
    "11": "Under voltage",
    "12": "Baseblock",
    "13": "Frequency reference not from comm",
    "14": "Sequence not from comm",
    "15": "Over torque"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 9505,
   "documented": "2521H",
   "name": "Error description",
   "description": "Active fault code.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "1": "UV",
    "2": "OC",
    "3": "OV",
    "4": "OH1",
    "5": "OL1",
    "6": "OL2",
    "7": "OT",
    "8": "UT",
    "9": "SC",
    "10": "Ground OC",
    "11": "Fuse blown",
    "12": "Input phase loss",
    "13": "Output phase loss",
    "17": "External fault 01",
    "18": "External fault 02",
    "19": "External fault 03",
    "20": "External fault 04",
    "21": "External fault 05",
    "22": "External fault 06",
    "25": "Feedback fault",
    "26": "Keypad removed",
    "27": "Modbus external fault",
    "28": "CE",
    "29": "STO",
    "36": "Low suction fault",
    "37": "Low suction fault (with retry)",
    "38": "CF07",
    "39": "Low flow fault",
    "40": "High flow fault",
    "42": "Low pressure fault",
    "43": "High pressure fault",
    "44": "Feedback loss",
    "46": "Motor overheat (OH4)"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 9506,
   "documented": "2522H",
   "name": "DI state",
   "description": "",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "0": "Comm S1",
    "1": "Comm S2",
    "2": "Comm S3",
    "3": "Comm S4",
    "4": "Comm S5",
    "5": "Comm S6"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 9507,
   "documented": "2523H",
   "name": "Frequency command",
   "description": "Raw; unit not printed in the monitor table.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 9508,
   "documented": "2524H",
   "name": "Output frequency",
   "description": "Raw; unit not printed in the monitor table.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 9510,
   "documented": "2526H",
   "name": "DC voltage command",
   "description": "Raw; unit not printed in the monitor table.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 9511,
   "documented": "2527H",
   "name": "Output current",
   "description": "Raw; unit not printed in the monitor table.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 9512,
   "documented": "2528H",
   "name": "Warning description",
   "description": "Active warning code.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "No alarm",
    "1": "OV",
    "2": "UV",
    "3": "OL2",
    "4": "OH2",
    "6": "OT",
    "9": "UT",
    "13": "CE",
    "16": "EF0",
    "17": "EF1",
    "18": "EF2",
    "19": "EF3",
    "20": "EF4",
    "21": "EF5",
    "22": "EF6",
    "25": "CLA",
    "26": "CLB",
    "29": "USP",
    "30": "RDE",
    "31": "WRE",
    "32": "FB",
    "33": "VRYE",
    "34": "SE01",
    "35": "SE02",
    "36": "SE03",
    "37": "SE04",
    "38": "SE05",
    "39": "HPERR",
    "40": "EF",
    "41": "CTRLE",
    "42": "SUME",
    "43": "RDP",
    "45": "OL1",
    "47": "SE10",
    "49": "BB1",
    "50": "BB2",
    "51": "BB3",
    "52": "BB4",
    "53": "BB5",
    "54": "BB6",
    "57": "LOPb",
    "58": "HIPb",
    "59": "LSCFT",
    "60": "LOPb",
    "61": "RETRY",
    "62": "SE07",
    "63": "SE08",
    "64": "HIPb",
    "65": "OH1",
    "66": "FIRE"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 9514,
   "documented": "252AH",
   "name": "AO1 value",
   "description": "0-1000 = 0.00-10.00 V or 4-20 mA.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 9515,
   "documented": "252BH",
   "name": "AO2 value",
   "description": "0-1000 = 0.00-10.00 V or 4-20 mA.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 9519,
   "documented": "252FH",
   "name": "F510 check",
   "description": "F510 identification value.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  }
 ],
 "integration": {
  "summary": "Set the RS-485 protocol to Modbus, the node address and serial parameters, and select communication as run/frequency source, then write 2501H and 2502H (0.01 Hz) and poll 2520H-2528H.",
  "minimum_registers": [
   {
    "table": "holding_register",
    "address": 9473,
    "why": "Run/stop, direction, reset"
   },
   {
    "table": "holding_register",
    "address": 9474,
    "why": "Frequency command 0.01 Hz"
   },
   {
    "table": "holding_register",
    "address": 9504,
    "why": "Status bits"
   },
   {
    "table": "holding_register",
    "address": 9505,
    "why": "Fault code"
   },
   {
    "table": "holding_register",
    "address": 9508,
    "why": "Output frequency"
   },
   {
    "table": "holding_register",
    "address": 9512,
    "why": "Warning code"
   }
  ],
  "enable": "Select Modbus as the communication protocol (the port also does BACnet and Metasys N2), then set node address, serial settings and run/frequency source at the keypad per the F510 manual.",
  "watchdog": null,
  "quirks": [
   "Registers are hex.",
   "Functions 03H, 06H, 08H and 10H; maximum frame 80 bytes.",
   "Node addresses 01H-FEH; 00H is broadcast.",
   "Write 0 to unused bits and never write reserved registers."
  ],
  "setup": [
   "RS-485 on CN6: S+ / S- per the CN6 pin-out.",
   "The addendum shows 120 ohm terminators on p. 1-1 but says 220 ohm in Appendix A; up to 31 inverters."
  ],
  "gotchas": [
   "Exception codes: 01 function, 02 register number, 03 number, 04 data setting error.",
   "Inverter response time is about 10 ms."
  ]
 },
 "page": "https://easymodbus.com/modbus-register-maps/teco-westinghouse/f510",
 "address_note": "address = 0-based Modbus wire (PDU) address; documented = as printed in the source.",
 "note": "Re-typed from the manufacturer's public documentation (see source) and verified against it. Registers vary by firmware and options; verify against the live device before writing."
}