 "manufacturer": "Teledyne Gas and Flame Detection",
 "manufacturer_slug": "teledyne",
 "model": "Spyglass SG50-F flame detector (Modbus RTU)",
 "model_slug": "spyglass-sg50-f",
 "short_model": "SG50-F",
 "aliases": [
  "SG50-F",
  "Spyglass SG50-F",
  "IR3-HD",
  "UV-IR",
  "IR3",
  "UV-IR-HD",
  "IR3-H2-HD",
  "IR3-H2",
  "UV-IR-F",
  "UV-IR-F-HD"
 ],
 "equipment_type": "Sensor (flame detector)",
 "applies_to": "Teledyne Spyglass SG50-F optical flame detectors (IR3, UV-IR, IR3-H2 and HD video variants) with RS-485 Modbus RTU, communication manual SG50FMODBUS-EN rev 1.0.",
 "summary": "The Spyglass SG50-F is a family of optical flame detectors (multi-IR, UV/IR and hydrogen-flame types, some with HD video). Its RS-485 port speaks Modbus RTU: input registers carry alarm, fault, built-in-test flags and the detector type, and holding registers set sensitivity, delays, latching, heater, video and the clock. This map covers every register the manual defines except the 32-bit and IP fields.",
 "transport": [
  "RTU"
 ],
 "defaults": {
  "unit_id": null,
  "baud": 9600,
  "parity": "None",
  "data_bits": 8,
  "stop_bits": 1,
  "tcp_port": null
 },
 "addressing": {
  "convention": "hex 0-based",
  "note": "The manual prints register addresses in hex starting at 0x0000 (alarm relay), so the hex value is the wire address: 0x0010 = address 16."
 },
 "default_word_order": null,
 "firmware": null,
 "source": {
  "title": "Spyglass SG50-F Modbus Communication Manual",
  "doc_number": "SG50FMODBUS-EN Revision 1.0",
  "revision_date": "2023-02",
  "url": "https://www.teledynegasandflamedetection.com/en-us/Products/docs/fixedflame-spyglass-sg50-f-modbus-communication-manual-english.pdf",
  "pages": "p. 1 (line settings), p. 2 (input registers), p. 3 (holding registers)"
 },
 "notes": [
  "Left out: 0-20 mA output value (input 0x0004-0x0005), Ethernet IP address (0x0006-0x0007, HD only) and detector serial ID (u32 at 0x0019-0x001A): the manual does not give their word order or encoding.",
  "Input registers and holding registers are separate tables, so input 0x0001 (fault relay) and holding 0x0001 (sensitivity) are different values.",
  "The factory default Modbus address is not stated in this manual.",
  "Up to 32 detectors per segment; up to 247 with repeaters. 120 ohm end-of-line resistor required."
 ],
 "registers": [
  {
   "table": "input_register",
   "address": 0,
   "documented": "0x0000",
   "name": "Alarm relay",
   "description": "Fire alarm state.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "No alarm",
    "1": "Alarm"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 1,
   "documented": "0x0001",
   "name": "Fault relay",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "No fault",
    "1": "Fault"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 2,
   "documented": "0x0002",
   "name": "BIT status",
   "description": "Built-in-test flags needing maintenance.",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "0": "Dirty window fault",
    "1": "24 V power supply fault"
   },
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 16,
   "documented": "0x0010",
   "name": "FGD detector identifier",
   "description": "Always ASCII \"FG\" for this product family.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 27,
   "documented": "0x001B",
   "name": "Detector type",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "101": "IR3-HD",
    "110": "UV-IR (small)",
    "120": "IR3 (small)",
    "130": "UV-IR-HD",
    "140": "IR3-H2-HD",
    "150": "IR3-H2",
    "160": "UV-IR-F",
    "170": "UV-IR-F-HD"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1,
   "documented": "0x0001",
   "name": "Sensitivity",
   "description": "Detection sensitivity level.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Low",
    "1": "Medium",
    "2": "High",
    "3": "Extreme"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2,
   "documented": "0x0002",
   "name": "Ultra-fast detection",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Disabled",
    "1": "Enabled"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 3,
   "documented": "0x0003",
   "name": "Alarm delay",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "0 s",
    "1": "5 s",
    "2": "10 s",
    "3": "20 s",
    "4": "30 s"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 4,
   "documented": "0x0004",
   "name": "Alarm latch",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "No latch",
    "1": "Latch"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 5,
   "documented": "0x0005",
   "name": "Window heater",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Disabled",
    "1": "Enabled"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 6,
   "documented": "0x0006",
   "name": "Video enable",
   "description": "HD models only.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Disabled",
    "1": "Enabled"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 7,
   "documented": "0x0007",
   "name": "Post-alarm video recording duration",
   "description": "HD models only, 1-3.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "min",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8,
   "documented": "0x0008",
   "name": "Analog video output",
   "description": "HD models only.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Disabled",
    "2": "NTSC",
    "3": "PAL"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 9,
   "documented": "0x0009",
   "name": "Manual BIT alarm output test",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Disabled",
    "1": "Enabled"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 32,
   "documented": "0x0020",
   "name": "Detector Modbus address",
   "description": "1-247.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 33,
   "documented": "0x0021",
   "name": "Manual BIT",
   "description": "Write 1 to start a manual built-in test.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 64,
   "documented": "0x0040",
   "name": "Time: hour and minute",
   "description": "Hour in high byte, minutes in low byte.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 65,
   "documented": "0x0041",
   "name": "Time: second and year",
   "description": "Seconds in high byte, year in low byte.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 66,
   "documented": "0x0042",
   "name": "Date: month and day",
   "description": "Month in high byte, day in low byte.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  }
 ],
 "integration": {
  "summary": "Set a unique address per detector, wire RS-485 at 9600 8N1 and poll input registers 0-2 (alarm, fault, BIT flags) with function 04.",
  "minimum_registers": [
   {
    "table": "input_register",
    "address": 0,
    "why": "Fire alarm"
   },
   {
    "table": "input_register",
    "address": 1,
    "why": "Fault"
   },
   {
    "table": "input_register",
    "address": 2,
    "why": "Maintenance flags"
   },
   {
    "table": "input_register",
    "address": 27,
    "why": "Detector type"
   },
   {
    "table": "holding_register",
    "address": 1,
    "why": "Sensitivity"
   },
   {
    "table": "holding_register",
    "address": 32,
    "why": "Modbus address"
   }
  ],
  "enable": "Modbus RTU is available on the RS-485 terminals of all SG50-F detectors; the address is register 0x0020 (1-247).",
  "watchdog": null,
  "quirks": [
   "Addresses are printed in hex and are the wire addresses.",
   "Clock registers pack two fields per register (high byte, low byte)."
  ],
  "setup": [
   "9600 baud, 8N1, half duplex 2-wire, no echo.",
   "Terminate the line with 120 ohm."
  ],
  "gotchas": [
   "Video and analog-video registers only work on HD models."
  ]
 },
 "page": "https://easymodbus.com/modbus-register-maps/teledyne/spyglass-sg50-f",
 "address_note": "address = 0-based Modbus wire (PDU) address; documented = as printed in the source.",
 "note": "Re-typed from the manufacturer's public documentation (see source) and verified against it. Registers vary by firmware and options; verify against the live device before writing."
}