 "manufacturer": "Teracom",
 "manufacturer_slug": "teracom",
 "model": "TCW280 Ethernet analog output module",
 "model_slug": "tcw280",
 "short_model": "TCW280",
 "aliases": [
  "TCW280"
 ],
 "equipment_type": "Sensor (Ethernet analog / digital output module)",
 "applies_to": "TCW280 per the Teracom TCW280 user manual TCW280_R1.8.",
 "summary": "The TCW280 is a Teracom Ethernet module with 2 isolated analog outputs (0-5/0-10 V or 0-20/4-20/0-24 mA), 4 open-drain digital outputs with ON/OFF or PWM mode and 2 relays. Over Modbus TCP the relays and digital outputs are coils, and modes, ranges, setpoints and alarms are holding registers.",
 "transport": [
  "TCP"
 ],
 "defaults": {
  "unit_id": null,
  "baud": null,
  "parity": null,
  "data_bits": null,
  "stop_bits": null,
  "tcp_port": 502
 },
 "addressing": {
  "convention": "0-based",
  "note": "The address table prints PDU (wire) addresses in decimal. The manual's example frames use them directly (coil 100 = 0x0064, holding register 500 = 0x01F4), so no offset is applied."
 },
 "default_word_order": "ABCD",
 "firmware": null,
 "source": {
  "title": "TCW280 User manual",
  "doc_number": "TCW280_R1.8",
  "revision_date": "2026-10",
  "url": "https://www.teracomsystems.com/download/analog-output-module-tcw280-user-manual/",
  "pages": "section 7.2 Modbus TCP/IP (address table 7.2.2)"
 },
 "notes": [
  "Word order: the manual says float registers are sent big-endian and its example response 3FA0 0000 is given as 1.25, i.e. high word first (ABCD).",
  "Strings are fixed-length UTF-8, zero padded; 64-byte fields span 32 registers.",
  "Left out: Save configuration, Restart device and HW error (PDU 50000-50002), whose data size column is empty in this manual."
 ],
 "registers": [
  {
   "table": "coil",
   "address": 100,
   "documented": "100",
   "name": "Relay 1",
   "description": "Relay state; write with FC05/15.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "coil",
   "address": 101,
   "documented": "101",
   "name": "Relay 2",
   "description": "Relay state; write with FC05/15.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "coil",
   "address": 102,
   "documented": "102",
   "name": "Digital out 1",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "coil",
   "address": 103,
   "documented": "103",
   "name": "Digital out 2",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "coil",
   "address": 104,
   "documented": "104",
   "name": "Digital out 3",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "coil",
   "address": 105,
   "documented": "105",
   "name": "Digital out 4",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 15000,
   "documented": "15000",
   "name": "Relay 1 description",
   "description": "User label text, UTF-8, zero padded.",
   "data_type": "STRING",
   "length": 32,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 15032,
   "documented": "15032",
   "name": "Relay 2 description",
   "description": "User label text, UTF-8, zero padded.",
   "data_type": "STRING",
   "length": 32,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 15200,
   "documented": "15200",
   "name": "Relay 1 pulse width",
   "description": "Pulse duration; the manual gives no unit here (the web page sets it in seconds, 0.1-999999).",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 15202,
   "documented": "15202",
   "name": "Relay 2 pulse width",
   "description": "Pulse duration; the manual gives no unit here (the web page sets it in seconds, 0.1-999999).",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 15300,
   "documented": "15300",
   "name": "Relay 1 activated from",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "0": "webORm2m",
    "1": "shedule1",
    "2": "shedle2",
    "3": "sheule3",
    "4": "shedule4"
   },
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 15301,
   "documented": "15301",
   "name": "Relay 2 activated from",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "0": "webORm2m",
    "1": "shedule1",
    "2": "shedle2",
    "3": "sheule3",
    "4": "shedule4"
   },
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 15400,
   "documented": "15400",
   "name": "Relay 1 state after restart",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "0": "lastState",
    "1": "on",
    "2": "off"
   },
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 15401,
   "documented": "15401",
   "name": "Relay 2 state after restart",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "0": "lastState",
    "1": "on",
    "2": "off"
   },
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 16000,
   "documented": "16000",
   "name": "Digital out 1 description",
   "description": "User label text, UTF-8, zero padded.",
   "data_type": "STRING",
   "length": 32,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 16032,
   "documented": "16032",
   "name": "Digital out 2 description",
   "description": "User label text, UTF-8, zero padded.",
   "data_type": "STRING",
   "length": 32,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 16064,
   "documented": "16064",
   "name": "Digital out 3 description",
   "description": "User label text, UTF-8, zero padded.",
   "data_type": "STRING",
   "length": 32,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 16096,
   "documented": "16096",
   "name": "Digital out 4 description",
   "description": "User label text, UTF-8, zero padded.",
   "data_type": "STRING",
   "length": 32,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 16200,
   "documented": "16200",
   "name": "Digital out 1 mode",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "0": "onoff",
    "1": "pwm"
   },
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 16201,
   "documented": "16201",
   "name": "Digital out 2 mode",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "0": "onoff",
    "1": "pwm"
   },
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 16202,
   "documented": "16202",
   "name": "Digital out 3 mode",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "0": "onoff",
    "1": "pwm"
   },
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 16203,
   "documented": "16203",
   "name": "Digital out 4 mode",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "0": "onoff",
    "1": "pwm"
   },
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 16300,
   "documented": "16300",
   "name": "Digital out 1 pulse width",
   "description": "Pulse duration; the manual gives no unit here (the web page sets it in seconds, 0.1-999999).",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 16302,
   "documented": "16302",
   "name": "Digital out 2 pulse width",
   "description": "Pulse duration; the manual gives no unit here (the web page sets it in seconds, 0.1-999999).",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 16304,
   "documented": "16304",
   "name": "Digital out 3 pulse width",
   "description": "Pulse duration; the manual gives no unit here (the web page sets it in seconds, 0.1-999999).",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 16306,
   "documented": "16306",
   "name": "Digital out 4 pulse width",
   "description": "Pulse duration; the manual gives no unit here (the web page sets it in seconds, 0.1-999999).",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 16400,
   "documented": "16400",
   "name": "Digital out 1 activated from",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "0": "webORm2m",
    "1": "shedule1",
    "2": "shedle2",
    "3": "sheule3",
    "4": "shedule4"
   },
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 16401,
   "documented": "16401",
   "name": "Digital out 2 activated from",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "0": "webORm2m",
    "1": "shedule1",
    "2": "shedle2",
    "3": "sheule3",
    "4": "shedule4"
   },
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 16402,
   "documented": "16402",
   "name": "Digital out 3 activated from",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "0": "webORm2m",
    "1": "shedule1",
    "2": "shedle2",
    "3": "sheule3",
    "4": "shedule4"
   },
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 16403,
   "documented": "16403",
   "name": "Digital out 4 activated from",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "0": "webORm2m",
    "1": "shedule1",
    "2": "shedle2",
    "3": "sheule3",
    "4": "shedule4"
   },
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 16500,
   "documented": "16500",
   "name": "Digital out 1 state after restart",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "0": "lastState",
    "1": "on",
    "2": "off"
   },
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 16501,
   "documented": "16501",
   "name": "Digital out 2 state after restart",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "0": "lastState",
    "1": "on",
    "2": "off"
   },
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 16502,
   "documented": "16502",
   "name": "Digital out 3 state after restart",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "0": "lastState",
    "1": "on",
    "2": "off"
   },
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 16503,
   "documented": "16503",
   "name": "Digital out 4 state after restart",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "0": "lastState",
    "1": "on",
    "2": "off"
   },
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 16600,
   "documented": "16600",
   "name": "Digital out 1 pwm duty",
   "description": "PWM duty cycle, 0-100 %.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "%",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 16602,
   "documented": "16602",
   "name": "Digital out 2 pwm duty",
   "description": "PWM duty cycle, 0-100 %.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "%",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 16604,
   "documented": "16604",
   "name": "Digital out 3 pwm duty",
   "description": "PWM duty cycle, 0-100 %.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "%",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 16606,
   "documented": "16606",
   "name": "Digital out 4 pwm duty",
   "description": "PWM duty cycle, 0-100 %.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "%",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 16700,
   "documented": "16700",
   "name": "Digital out 1 state",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "0": "off",
    "1": "on"
   },
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 16701,
   "documented": "16701",
   "name": "Digital out 2 state",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "0": "off",
    "1": "on"
   },
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 16702,
   "documented": "16702",
   "name": "Digital out 3 state",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "0": "off",
    "1": "on"
   },
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 16703,
   "documented": "16703",
   "name": "Digital out 4 state",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "0": "off",
    "1": "on"
   },
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 16800,
   "documented": "16800",
   "name": "Digital out 1 pulse",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "0": "off",
    "1": "on"
   },
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 16801,
   "documented": "16801",
   "name": "Digital out 2 pulse",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "0": "off",
    "1": "on"
   },
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 16802,
   "documented": "16802",
   "name": "Digital out 3 pulse",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "0": "off",
    "1": "on"
   },
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 16803,
   "documented": "16803",
   "name": "Digital out 4 pulse",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "0": "off",
    "1": "on"
   },
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 16900,
   "documented": "16900",
   "name": "Digital out pwm frequency",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "0": "1Hz",
    "1": "5Hz",
    "2": "10Hz",
    "3": "50Hz",
    "4": "100Hz",
    "5": "500Hz",
    "6": "1000Hz",
    "7": "2000Hz"
   },
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 18000,
   "documented": "18000",
   "name": "Analog out 1 description",
   "description": "User label text, UTF-8, zero padded.",
   "data_type": "STRING",
   "length": 32,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 18032,
   "documented": "18032",
   "name": "Analog out 2 description",
   "description": "User label text, UTF-8, zero padded.",
   "data_type": "STRING",
   "length": 32,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 18200,
   "documented": "18200",
   "name": "Analog out 1 mode",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "0": "voltage",
    "1": "current"
   },
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 18201,
   "documented": "18201",
   "name": "Analog out 2 mode",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "0": "voltage",
    "1": "current"
   },
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 18300,
   "documented": "18300",
   "name": "Analog out 1 range",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "0": "0V to 5V",
    "1": "0V to 10V",
    "5": "4mA to 20mA",
    "6": "0mA to 20mA",
    "7": "0mA to 24mA"
   },
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 18301,
   "documented": "18301",
   "name": "Analog out 2 range",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "0": "0V to 5V",
    "1": "0V to 10V",
    "5": "4mA to 20mA",
    "6": "0mA to 20mA",
    "7": "0mA to 24mA"
   },
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 18400,
   "documented": "18400",
   "name": "Analog out 1 value after restart",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "0": "lastValue",
    "1": "0V of 5V",
    "2": "2.5V of 5V",
    "3": "5V of 5V",
    "4": "0V of 10V",
    "5": "5V of 10V",
    "6": "10V of 10V",
    "7": "0mA",
    "8": "2mA",
    "9": "4mA",
    "10": "10mA",
    "11": "12mA",
    "12": "20mA",
    "13": "22mA",
    "14": "24mA"
   },
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 18401,
   "documented": "18401",
   "name": "Analog out 2 value after restart",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "0": "lastValue",
    "1": "0V of 5V",
    "2": "2.5V of 5V",
    "3": "5V of 5V",
    "4": "0V of 10V",
    "5": "5V of 10V",
    "6": "10V of 10V",
    "7": "0mA",
    "8": "2mA",
    "9": "4mA",
    "10": "10mA",
    "11": "12mA",
    "12": "20mA",
    "13": "22mA",
    "14": "24mA"
   },
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 18500,
   "documented": "18500",
   "name": "Analog out 1 value",
   "description": "Analog output setpoint in the units of the selected range (V or mA).",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 18502,
   "documented": "18502",
   "name": "Analog out 2 value",
   "description": "Analog output setpoint in the units of the selected range (V or mA).",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 18600,
   "documented": "18600",
   "name": "Analog out 1 alarm",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": {
    "0": "none",
    "1": "over temperature",
    "4": "out fault",
    "5": "over temperature and out fault"
   },
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 18601,
   "documented": "18601",
   "name": "Analog out 2 alarm",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": {
    "0": "none",
    "1": "over temperature",
    "4": "out fault",
    "5": "over temperature and out fault"
   },
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 50100,
   "documented": "50100",
   "name": "Device ID",
   "description": "Sensor ROM ID as text.",
   "data_type": "STRING",
   "length": 9,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 50200,
   "documented": "50200",
   "name": "Hostname",
   "description": "",
   "data_type": "STRING",
   "length": 8,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 50300,
   "documented": "50300",
   "name": "Device IP",
   "description": "",
   "data_type": "STRING",
   "length": 8,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  }
 ],
 "integration": {
  "summary": "Enable Modbus TCP, set each analog output's mode and range (holding 18200/18300), then write the output value as a float to holding 18500/18502 with function 16.",
  "minimum_registers": [
   {
    "table": "coil",
    "address": 100,
    "why": "Relay 1"
   },
   {
    "table": "holding_register",
    "address": 18500,
    "why": "Analog output 1 value"
   },
   {
    "table": "holding_register",
    "address": 18200,
    "why": "Analog output 1 mode"
   },
   {
    "table": "holding_register",
    "address": 18300,
    "why": "Analog output 1 range"
   },
   {
    "table": "holding_register",
    "address": 18600,
    "why": "Analog output 1 alarm"
   },
   {
    "table": "holding_register",
    "address": 16700,
    "why": "Digital output 1 state"
   }
  ],
  "enable": "Modbus TCP is off by default. Turn it on in the Modbus TCP/IP settings of the web interface (default port 502).",
  "watchdog": null,
  "quirks": [
   "Floats are high word first (ABCD)."
  ],
  "setup": [
   "The factory IP is 192.168.1.2 (web login admin/admin); change it in the network settings, then enable Modbus TCP/IP."
  ],
  "gotchas": []
 },
 "page": "https://easymodbus.com/modbus-register-maps/teracom/tcw280",
 "address_note": "address = 0-based Modbus wire (PDU) address; documented = as printed in the source.",
 "note": "Re-typed from the manufacturer's public documentation (see source) and verified against it. Registers vary by firmware and options; verify against the live device before writing."
}