 "manufacturer": "Teracom",
 "manufacturer_slug": "teracom",
 "model": "TCW320x-WMG 1-Wire to Modbus gateway",
 "model_slug": "tcw320-wmg",
 "short_model": "TCW320x-WMG",
 "aliases": [
  "TCW320E-WMG",
  "TCW320W-WMG"
 ],
 "equipment_type": "Sensor (1-Wire to Modbus gateway)",
 "applies_to": "TCW320E-WMG (Ethernet) and TCW320W-WMG (Wi-Fi) per the user manual Revision R1.0; both share one fixed register map.",
 "summary": "The TCW320x-WMG is a Teracom gateway that reads up to 20 Teracom 1-Wire sensors (or DS18B20 probes) and publishes their readings on a fixed Modbus map over RS-485 RTU and Modbus TCP. Each sensor slot holds up to two float parameters; the map also has the serial settings, word-order switch and identity strings.",
 "transport": [
  "RTU",
  "TCP"
 ],
 "defaults": {
  "unit_id": 1,
  "baud": 19200,
  "parity": "Even",
  "data_bits": 8,
  "stop_bits": 1,
  "tcp_port": 502
 },
 "addressing": {
  "convention": "0-based",
  "note": "The manual prints PDU (zero-based) addresses only and says so in its addressing section; send them as printed."
 },
 "default_word_order": "ABCD",
 "firmware": null,
 "source": {
  "title": "TCW320E-WMG / TCW320W-WMG User Manual",
  "doc_number": "Revision R1.0",
  "revision_date": "2026-10",
  "url": "https://www.teracomsystems.com/download/tcw320x-wmg-1-wire-to-modbus-gateway-user-manual/",
  "pages": "section 12 Modbus addressing and section 13 register table"
 },
 "notes": [
  "32-bit values follow the Data order register (PDU 13): 1 = most significant word first (default), 2 = least significant word first. The map shows the default, ABCD.",
  "Sensor slot n uses PDU 1000 + 10n for parameter 1 and +2 for parameter 2; the unit depends on the sensor type found in that slot.",
  "Left out: the 32-bit float/integer test-value registers (PDU 82-95)."
 ],
 "registers": [
  {
   "table": "holding_register",
   "address": 10,
   "documented": "10",
   "name": "RS-485 address",
   "description": "Modbus RTU slave address.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 11,
   "documented": "11",
   "name": "Baud rate",
   "description": "Serial baud rate; applied after a power cycle.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 12,
   "documented": "12",
   "name": "Parity, data, stop bits",
   "description": "Serial framing; applied after a power cycle.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "1": "8 data bits, even parity, 1 stop (E81)",
    "2": "8 data bits, odd parity, 1 stop (O81)",
    "3": "8 data bits, no parity, 1 stop (N81)"
   },
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 13,
   "documented": "13",
   "name": "Data order",
   "description": "Word order for all 32-bit values.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "1": "MSWF - most significant word first",
    "2": "LSWF - least significant word first"
   },
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 14,
   "documented": "14",
   "name": "Device code",
   "description": "Fixed product code.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 15,
   "documented": "15",
   "name": "FW version",
   "description": "Firmware version number.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 18,
   "documented": "18",
   "name": "Vendor URL",
   "description": "Maker URL as UTF-8 text.",
   "data_type": "STRING",
   "length": 32,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 86,
   "documented": "86",
   "name": "Signed integer test value",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 91,
   "documented": "91",
   "name": "Unsigned integer test value",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 100,
   "documented": "100",
   "name": "System Name",
   "description": "Device text field, UTF-8.",
   "data_type": "STRING",
   "length": 16,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 200,
   "documented": "200",
   "name": "System Location",
   "description": "Device text field, UTF-8.",
   "data_type": "STRING",
   "length": 16,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 300,
   "documented": "300",
   "name": "System Contact",
   "description": "Device text field, UTF-8.",
   "data_type": "STRING",
   "length": 16,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 1010,
   "documented": "1010",
   "name": "Sensor 1 Parameter 1",
   "description": "Measurement from the 1-Wire sensor in this slot; NaN if unavailable.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 1012,
   "documented": "1012",
   "name": "Sensor 1 Parameter 2",
   "description": "Measurement from the 1-Wire sensor in this slot; NaN if unavailable.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 1020,
   "documented": "1020",
   "name": "Sensor 2 Parameter 1",
   "description": "Measurement from the 1-Wire sensor in this slot; NaN if unavailable.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 1022,
   "documented": "1022",
   "name": "Sensor 2 Parameter 2",
   "description": "Measurement from the 1-Wire sensor in this slot; NaN if unavailable.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 1030,
   "documented": "1030",
   "name": "Sensor 3 Parameter 1",
   "description": "Measurement from the 1-Wire sensor in this slot; NaN if unavailable.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 1032,
   "documented": "1032",
   "name": "Sensor 3 Parameter 2",
   "description": "Measurement from the 1-Wire sensor in this slot; NaN if unavailable.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 1040,
   "documented": "1040",
   "name": "Sensor 4 Parameter 1",
   "description": "Measurement from the 1-Wire sensor in this slot; NaN if unavailable.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 1042,
   "documented": "1042",
   "name": "Sensor 4 Parameter 2",
   "description": "Measurement from the 1-Wire sensor in this slot; NaN if unavailable.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 1050,
   "documented": "1050",
   "name": "Sensor 5 Parameter 1",
   "description": "Measurement from the 1-Wire sensor in this slot; NaN if unavailable.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 1052,
   "documented": "1052",
   "name": "Sensor 5 Parameter 2",
   "description": "Measurement from the 1-Wire sensor in this slot; NaN if unavailable.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 1060,
   "documented": "1060",
   "name": "Sensor 6 Parameter 1",
   "description": "Measurement from the 1-Wire sensor in this slot; NaN if unavailable.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 1062,
   "documented": "1062",
   "name": "Sensor 6 Parameter 2",
   "description": "Measurement from the 1-Wire sensor in this slot; NaN if unavailable.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 1070,
   "documented": "1070",
   "name": "Sensor 7 Parameter 1",
   "description": "Measurement from the 1-Wire sensor in this slot; NaN if unavailable.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 1072,
   "documented": "1072",
   "name": "Sensor 7 Parameter 2",
   "description": "Measurement from the 1-Wire sensor in this slot; NaN if unavailable.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 1080,
   "documented": "1080",
   "name": "Sensor 8 Parameter 1",
   "description": "Measurement from the 1-Wire sensor in this slot; NaN if unavailable.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 1082,
   "documented": "1082",
   "name": "Sensor 8 Parameter 2",
   "description": "Measurement from the 1-Wire sensor in this slot; NaN if unavailable.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 1090,
   "documented": "1090",
   "name": "Sensor 9 Parameter 1",
   "description": "Measurement from the 1-Wire sensor in this slot; NaN if unavailable.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 1092,
   "documented": "1092",
   "name": "Sensor 9 Parameter 2",
   "description": "Measurement from the 1-Wire sensor in this slot; NaN if unavailable.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 1100,
   "documented": "1100",
   "name": "Sensor 10 Parameter 1",
   "description": "Measurement from the 1-Wire sensor in this slot; NaN if unavailable.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 1102,
   "documented": "1102",
   "name": "Sensor 10 Parameter 2",
   "description": "Measurement from the 1-Wire sensor in this slot; NaN if unavailable.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 1110,
   "documented": "1110",
   "name": "Sensor 11 Parameter 1",
   "description": "Measurement from the 1-Wire sensor in this slot; NaN if unavailable.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 1112,
   "documented": "1112",
   "name": "Sensor 11 Parameter 2",
   "description": "Measurement from the 1-Wire sensor in this slot; NaN if unavailable.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 1120,
   "documented": "1120",
   "name": "Sensor 12 Parameter 1",
   "description": "Measurement from the 1-Wire sensor in this slot; NaN if unavailable.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 1122,
   "documented": "1122",
   "name": "Sensor 12 Parameter 2",
   "description": "Measurement from the 1-Wire sensor in this slot; NaN if unavailable.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 1130,
   "documented": "1130",
   "name": "Sensor 13 Parameter 1",
   "description": "Measurement from the 1-Wire sensor in this slot; NaN if unavailable.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 1132,
   "documented": "1132",
   "name": "Sensor 13 Parameter 2",
   "description": "Measurement from the 1-Wire sensor in this slot; NaN if unavailable.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 1140,
   "documented": "1140",
   "name": "Sensor 14 Parameter 1",
   "description": "Measurement from the 1-Wire sensor in this slot; NaN if unavailable.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 1142,
   "documented": "1142",
   "name": "Sensor 14 Parameter 2",
   "description": "Measurement from the 1-Wire sensor in this slot; NaN if unavailable.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 1150,
   "documented": "1150",
   "name": "Sensor 15 Parameter 1",
   "description": "Measurement from the 1-Wire sensor in this slot; NaN if unavailable.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 1152,
   "documented": "1152",
   "name": "Sensor 15 Parameter 2",
   "description": "Measurement from the 1-Wire sensor in this slot; NaN if unavailable.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 1160,
   "documented": "1160",
   "name": "Sensor 16 Parameter 1",
   "description": "Measurement from the 1-Wire sensor in this slot; NaN if unavailable.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 1162,
   "documented": "1162",
   "name": "Sensor 16 Parameter 2",
   "description": "Measurement from the 1-Wire sensor in this slot; NaN if unavailable.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 1170,
   "documented": "1170",
   "name": "Sensor 17 Parameter 1",
   "description": "Measurement from the 1-Wire sensor in this slot; NaN if unavailable.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 1172,
   "documented": "1172",
   "name": "Sensor 17 Parameter 2",
   "description": "Measurement from the 1-Wire sensor in this slot; NaN if unavailable.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 1180,
   "documented": "1180",
   "name": "Sensor 18 Parameter 1",
   "description": "Measurement from the 1-Wire sensor in this slot; NaN if unavailable.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 1182,
   "documented": "1182",
   "name": "Sensor 18 Parameter 2",
   "description": "Measurement from the 1-Wire sensor in this slot; NaN if unavailable.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 1190,
   "documented": "1190",
   "name": "Sensor 19 Parameter 1",
   "description": "Measurement from the 1-Wire sensor in this slot; NaN if unavailable.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 1192,
   "documented": "1192",
   "name": "Sensor 19 Parameter 2",
   "description": "Measurement from the 1-Wire sensor in this slot; NaN if unavailable.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 1200,
   "documented": "1200",
   "name": "Sensor 20 Parameter 1",
   "description": "Measurement from the 1-Wire sensor in this slot; NaN if unavailable.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 1202,
   "documented": "1202",
   "name": "Sensor 20 Parameter 2",
   "description": "Measurement from the 1-Wire sensor in this slot; NaN if unavailable.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  }
 ],
 "integration": {
  "summary": "Read the sensor parameters as floats from PDU 1010 onward with function 03, over RS-485 or Modbus TCP. Lock sensor positions in the web interface so slots do not move.",
  "minimum_registers": [
   {
    "table": "holding_register",
    "address": 1010,
    "why": "Sensor 1 parameter 1"
   },
   {
    "table": "holding_register",
    "address": 1012,
    "why": "Sensor 1 parameter 2"
   },
   {
    "table": "holding_register",
    "address": 1020,
    "why": "Sensor 2 parameter 1"
   },
   {
    "table": "holding_register",
    "address": 13,
    "why": "Word order"
   },
   {
    "table": "holding_register",
    "address": 14,
    "why": "Device code check"
   }
  ],
  "enable": "Modbus TCP is enabled or disabled on the Modbus page of the web interface (default port 502); the RTU slave address, baud and parity are set there too and apply after saving.",
  "watchdog": null,
  "quirks": [
   "Word order of every float is set by PDU 13.",
   "The web Modbus page shows data bits and stop bits but does not let you change them (factory default 8 data, 1 stop).",
   "Baud rate and framing written to PDU 11-12 only take effect after a power cycle."
  ],
  "setup": [
   "Factory network defaults: Ethernet variant 192.168.1.2; Wi-Fi variant in AP mode at 192.168.4.1.",
   "Set RTU address/baud/parity on the Modbus page and save."
  ],
  "gotchas": [
   "A missing or failed sensor reads NaN."
  ]
 },
 "page": "https://easymodbus.com/modbus-register-maps/teracom/tcw320-wmg",
 "address_note": "address = 0-based Modbus wire (PDU) address; documented = as printed in the source.",
 "note": "Re-typed from the manufacturer's public documentation (see source) and verified against it. Registers vary by firmware and options; verify against the live device before writing."
}