 "manufacturer": "Teracom",
 "manufacturer_slug": "teracom",
 "model": "TSF400-4 water-leak detector with Modbus RTU",
 "model_slug": "tsf400-4",
 "short_model": "TSF400-4",
 "aliases": [
  "TSF400-4"
 ],
 "equipment_type": "Sensor (water leak detector)",
 "applies_to": "TSF400-4 per the Teracom TSF400-4 user manual Revision R1.2.",
 "summary": "The TSF400-4 is a Teracom floor-standing water-leak detector with five electrodes on its base and a Modbus RTU RS-485 interface. It reports the leak state as a normal and an inverted flag, in both holding and input registers.",
 "transport": [
  "RTU"
 ],
 "defaults": {
  "unit_id": 1,
  "baud": 19200,
  "parity": "Even",
  "data_bits": 8,
  "stop_bits": 1,
  "tcp_port": null
 },
 "addressing": {
  "convention": "Modicon",
  "note": "The register table prints both a PDU (wire) address and a logical address (PDU + 40001 for holding registers). 'documented' holds the logical number; the PDU number is what goes in the request, e.g. logical 40101 = PDU 100."
 },
 "default_word_order": null,
 "firmware": null,
 "source": {
  "title": "TSF400-4 User manual",
  "doc_number": "Revision R1.2",
  "revision_date": "2026-10",
  "url": "https://www.teracomsystems.com/download/tsf400-4-water-leak-detector-with-modbus-rtu-interface-user-manual/",
  "pages": "p. 6 (Modbus address table)"
 },
 "notes": [
  "Addresses are taken from the manual's PDU address column (0-based); the logical column adds 40001 for holding registers and 30001 for input registers, as the manual states.",
  "All 32-bit values follow the Data order register (PDU 13): 1 = most significant word first (factory default), 2 = least significant word first. The map shows the default, ABCD.",
  "Left out: the 32-bit float/integer test-value registers (PDU 82-95), which only exist to check word order; the 16-bit test values are kept.",
  "The same two alarm flags are readable as holding registers (PDU 100, 102) and as input registers (PDU 1, 2); the normal flag reads 1 when the floor is dry.",
  "The device has no 32-bit measurement registers; the Data order register only affects the test values."
 ],
 "registers": [
  {
   "table": "input_register",
   "address": 1,
   "documented": "30002",
   "name": "Alarm",
   "description": "Leak state; reads 1 while dry.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": {
    "1": "Water absent",
    "0": "Water present"
   },
   "bits": null
  },
  {
   "table": "input_register",
   "address": 2,
   "documented": "30003",
   "name": "Alarm (inverse)",
   "description": "Inverted leak state; reads 1 when water is present.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": {
    "1": "Water present",
    "0": "Water absent"
   },
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 10,
   "documented": "40011",
   "name": "Modbus address",
   "description": "Modbus slave address of the device.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 11,
   "documented": "40012",
   "name": "Baud rate",
   "description": "Serial baud rate; takes effect after a power cycle.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 12,
   "documented": "40013",
   "name": "Parity, data, stop bits",
   "description": "Parity/data/stop framing; takes effect after a power cycle.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "1": "8 data bits, even parity, 1 stop (E81)",
    "2": "8 data bits, odd parity, 1 stop (O81)",
    "3": "8 data bits, no parity, 1 stop (N81)"
   },
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 13,
   "documented": "40014",
   "name": "Data order",
   "description": "Word order used for all 32-bit values.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "1": "MSWF - most significant word first",
    "2": "LSWF - least significant word first"
   },
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 14,
   "documented": "40015",
   "name": "Device code",
   "description": "Fixed product identification code.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 15,
   "documented": "40016",
   "name": "FW version",
   "description": "Firmware version number.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 18,
   "documented": "40019",
   "name": "Vendor URL",
   "description": "Maker URL as UTF-8 text (64 bytes).",
   "data_type": "STRING",
   "length": 32,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 86,
   "documented": "40087",
   "name": "Signed integer test value",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 91,
   "documented": "40092",
   "name": "Unsigned integer test value",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 100,
   "documented": "40101",
   "name": "Alarm",
   "description": "Leak state; reads 1 while dry.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": {
    "1": "Water absent",
    "0": "Water present"
   },
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 102,
   "documented": "40103",
   "name": "Alarm (inverse)",
   "description": "Inverted leak state; reads 1 when water is present.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": {
    "1": "Water present",
    "0": "Water absent"
   },
   "bits": null
  }
 ],
 "integration": {
  "summary": "Poll PDU 102 with function 03 (1 = water present) or input register PDU 2 with function 04. Mind the polarity of the non-inverted flag.",
  "minimum_registers": [
   {
    "table": "holding_register",
    "address": 100,
    "why": "Leak flag (1 = dry)"
   },
   {
    "table": "holding_register",
    "address": 102,
    "why": "Leak flag inverted (1 = water)"
   },
   {
    "table": "input_register",
    "address": 1,
    "why": "Leak flag via FC04"
   },
   {
    "table": "input_register",
    "address": 2,
    "why": "Inverted leak flag via FC04"
   }
  ],
  "enable": "Modbus RTU is the only interface and is always active; there is nothing to switch on. Factory settings are address 1, 19200 baud, 8E1.",
  "watchdog": null,
  "quirks": [
   "Baud rate and framing changes only take effect after the device is powered off and on again.",
   "Word order for every 32-bit value is set by the Data order register (PDU 13); check it before blaming the scaling."
  ],
  "setup": [
   "Set unit ID (PDU 10), baud (PDU 11) and framing (PDU 12), then power-cycle the device.",
   "Terminate both ends of the RS-485 bus with 120 ohm resistors; a daisy chain is recommended."
  ],
  "gotchas": [
   "The non-inverted Alarm flag is 1 when no water is present, so treat a comms timeout as a fault rather than as dry."
  ]
 },
 "page": "https://easymodbus.com/modbus-register-maps/teracom/tsf400-4",
 "address_note": "address = 0-based Modbus wire (PDU) address; documented = as printed in the source.",
 "note": "Re-typed from the manufacturer's public documentation (see source) and verified against it. Registers vary by firmware and options; verify against the live device before writing."
}