 "manufacturer": "Teracom",
 "manufacturer_slug": "teracom",
 "model": "TSH300v3 RS-485 humidity and temperature sensor",
 "model_slug": "tsh300",
 "short_model": "TSH300v3",
 "aliases": [
  "TSH300",
  "TSH300v3"
 ],
 "equipment_type": "Sensor (humidity / temperature)",
 "applies_to": "TSH300v3 per the Teracom TSH300v3 user manual Revision R1.17.",
 "summary": "The TSH300v3 is a Teracom humidity and temperature probe that talks Modbus RTU over RS-485 and takes its power from the bus cable (RJ45). It reports temperature, relative humidity and dew point as floats and as x100 integers in both Celsius and Fahrenheit, with user trim registers.",
 "transport": [
  "RTU"
 ],
 "defaults": {
  "unit_id": 1,
  "baud": 19200,
  "parity": "Even",
  "data_bits": 8,
  "stop_bits": 1,
  "tcp_port": null
 },
 "addressing": {
  "convention": "Modicon",
  "note": "The register table prints both a PDU (wire) address and a logical address (PDU + 40001 for holding registers). 'documented' holds the logical number; the PDU number is what goes in the request, e.g. logical 40101 = PDU 100."
 },
 "default_word_order": "ABCD",
 "firmware": null,
 "source": {
  "title": "TSH300v3 User manual",
  "doc_number": "Revision R1.17",
  "revision_date": "2026-10",
  "url": "https://www.teracomsystems.com/download/rs-485-humidity-temperature-sensor-tsh300/",
  "pages": "p. 4 (Modbus address table)"
 },
 "notes": [
  "Addresses are taken from the manual's PDU address column (0-based); the logical column is the same number plus 40001, the holding-register offset the manual states.",
  "All 32-bit values follow the Data order register (PDU 13): 1 = most significant word first (factory default), 2 = least significant word first. The map shows the default, ABCD.",
  "Left out: the 32-bit float/integer test-value registers (PDU 82-95), which only exist to check word order; the 16-bit test values are kept.",
  "Float blocks: PDU 100+ in Â°C and PDU 200+ in Â°F; the integer blocks (PDU 400+ Â°C, 500+ Â°F) hold the same values x100 as 16-bit words. A missing reading returns NaN (float) or -32768 (16-bit integer).",
  "Readings can be trimmed with the multiplier and offset floats near PDU 2100: corrected = measured x multiplier + offset.",
  "The download is titled TSH300 but the manual covers the TSH300v3 successor."
 ],
 "registers": [
  {
   "table": "holding_register",
   "address": 10,
   "documented": "40011",
   "name": "RS-485 address",
   "description": "Modbus slave address of the device.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 11,
   "documented": "40012",
   "name": "Baud rate",
   "description": "Serial baud rate; takes effect after a power cycle.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 12,
   "documented": "40013",
   "name": "Parity, data, stop bits",
   "description": "Parity/data/stop framing; takes effect after a power cycle.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "1": "8 data bits, even parity, 1 stop (E81)",
    "2": "8 data bits, odd parity, 1 stop (O81)",
    "3": "8 data bits, no parity, 1 stop (N81)"
   },
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 13,
   "documented": "40014",
   "name": "Data order",
   "description": "Word order used for all 32-bit values.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "1": "MSWF - most significant word first",
    "2": "LSWF - least significant word first"
   },
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 14,
   "documented": "40015",
   "name": "Device code",
   "description": "Fixed product identification code.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 15,
   "documented": "40016",
   "name": "FW version",
   "description": "Firmware version number.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 18,
   "documented": "40019",
   "name": "Vendor URL",
   "description": "Maker URL as UTF-8 text (64 bytes).",
   "data_type": "STRING",
   "length": 32,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 86,
   "documented": "40087",
   "name": "Signed integer test value",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 91,
   "documented": "40092",
   "name": "Unsigned integer test value",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 100,
   "documented": "40101",
   "name": "Temperature °C",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 102,
   "documented": "40103",
   "name": "Humidity %RH",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "%RH",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 104,
   "documented": "40105",
   "name": "Dew point °C",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 200,
   "documented": "40201",
   "name": "Temperature °F",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "°F",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 202,
   "documented": "40203",
   "name": "Humidity %RH",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "%RH",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 204,
   "documented": "40205",
   "name": "Dew point °F",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "°F",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 400,
   "documented": "40401",
   "name": "Temperature °C x 100",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 401,
   "documented": "40402",
   "name": "Humidity %RH x 100",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "%RH",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 402,
   "documented": "40403",
   "name": "Dew point °C x 100",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 500,
   "documented": "40501",
   "name": "Temperature °F x 100",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "°F",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 501,
   "documented": "40502",
   "name": "Humidity %RH x 100",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "%RH",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 502,
   "documented": "40503",
   "name": "Dew point °F x 100",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "°F",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 2101,
   "documented": "42102",
   "name": "Temperature multiplier",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 2103,
   "documented": "42104",
   "name": "Temperature offset °C",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "°C",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 2105,
   "documented": "42106",
   "name": "Temperature offset °F",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "°F",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 2111,
   "documented": "42112",
   "name": "Humidity multiplier",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 2113,
   "documented": "42114",
   "name": "Humidity offset",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null
  }
 ],
 "integration": {
  "summary": "Read the float block at PDU 100-105 (temperature, humidity, dew point) with function 03, or the 16-bit x100 block at PDU 400-402 if your master has no float support. All registers are holding registers.",
  "minimum_registers": [
   {
    "table": "holding_register",
    "address": 100,
    "why": "Temperature Â°C (float)"
   },
   {
    "table": "holding_register",
    "address": 102,
    "why": "Humidity %RH (float)"
   },
   {
    "table": "holding_register",
    "address": 104,
    "why": "Dew point Â°C (float)"
   },
   {
    "table": "holding_register",
    "address": 400,
    "why": "Temperature Â°C x100 (int16)"
   },
   {
    "table": "holding_register",
    "address": 401,
    "why": "Humidity x100"
   },
   {
    "table": "holding_register",
    "address": 13,
    "why": "Word order setting"
   }
  ],
  "enable": "Modbus RTU is the only interface and is always active; there is nothing to switch on. Factory settings are address 1, 19200 baud, 8E1.",
  "watchdog": null,
  "quirks": [
   "Baud rate and framing changes only take effect after the device is powered off and on again.",
   "Word order for every 32-bit value is set by the Data order register (PDU 13); check it before blaming the scaling."
  ],
  "setup": [
   "Set unit ID (PDU 10), baud (PDU 11) and framing (PDU 12), then power-cycle the device.",
   "Wire sensors as a daisy chain and fit a 120 ohm terminator in the free RJ45 socket of the last sensor."
  ],
  "gotchas": []
 },
 "page": "https://easymodbus.com/modbus-register-maps/teracom/tsh300",
 "address_note": "address = 0-based Modbus wire (PDU) address; documented = as printed in the source.",
 "note": "Re-typed from the manufacturer's public documentation (see source) and verified against it. Registers vary by firmware and options; verify against the live device before writing."
}