 "manufacturer": "Toshiba",
 "manufacturer_slug": "toshiba",
 "model": "TOSVERT VF-AS3 inverter (RS485 Modbus RTU)",
 "model_slug": "vf-as3",
 "short_model": "Toshiba VF-AS3",
 "aliases": [
  "VF-AS3",
  "TOSVERT VF-AS3"
 ],
 "equipment_type": "Variable frequency drive",
 "applies_to": "Toshiba TOSVERT VF-AS3 inverters on RS485 port 1 or 2 with the protocol set to MODBUS (F807/F827 = 1); RS485 Communication Function Instruction Manual E6582143.",
 "summary": "The VF-AS3 inverter's RS485 ports speak either the Toshiba protocol or Modbus RTU. In Modbus every parameter and monitor is addressed by its hexadecimal communication number: FA codes are commands (run word, frequency), FD/FE codes are monitors and trip-held values, and 08xx codes are the RS485 settings. This map covers control, the main monitors, trip history and the port 1 settings.",
 "transport": [
  "RTU"
 ],
 "defaults": {
  "unit_id": 0,
  "baud": 19200,
  "parity": "Even",
  "data_bits": 8,
  "stop_bits": null,
  "tcp_port": null
 },
 "addressing": {
  "convention": "hex 0-based",
  "note": "The register address is the parameter's hexadecimal communication number sent unchanged: the manual's example reads output frequency FD00 with the frame 01 03 FD 00 00 01. Parameter F800 has communication number 0800 (wire 0x0800)."
 },
 "default_word_order": null,
 "firmware": null,
 "source": {
  "title": "TOSVERT VF-AS3 RS485 Communication Function Instruction Manual",
  "doc_number": "E6582143",
  "revision_date": null,
  "url": "https://cdn.automationdirect.com/static/manuals/toshibamotors/as3rs485manual.pdf",
  "pages": "ch. 6 (Modbus RTU frames and examples), ch. 8 pp. 8-1 to 8-3 (communication parameters), ch. 9 pp. 9-1 to 9-10 (command and status bits), ch. 10 pp. 10-2 to 10-8 (command and monitor lists)",
  "unofficial": true
 },
 "notes": [
  "Toshiba's own download host refused automated access (HTTP 403), so the link is the copy on AutomationDirect, a Toshiba drive distributor; it appears to be the unaltered Toshiba manual.",
  "Every value is a single 16-bit word; negative values are two's complement.",
  "FE versions of the FD monitors (FE00-FE07, FE15 ...) hold the value captured just before the last trip; only a few are listed.",
  "Output current and voltages are in % of the drive rating (0.01 % steps); convert with FE70/FE71.",
  "Input and output cumulative power (FE76/FE77) are left out because their unit depends on parameter F749.",
  "The Modbus implementation is partial: function 03 reads one word, an indirect block (F875-F879) or up to 8 consecutive numbers; 06 and 10 write one word; 10 also writes the F870/F871 block and 17 combines block write and read."
 ],
 "registers": [
  {
   "table": "holding_register",
   "address": 2048,
   "documented": "0800",
   "name": "RS485 (1) baud rate [F800]",
   "description": "Takes effect after reset.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "9600 bps",
    "1": "19200 bps",
    "2": "38400 bps"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2049,
   "documented": "0801",
   "name": "RS485 (1) parity [F801]",
   "description": "Takes effect after reset.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Disabled (none)",
    "1": "Even parity",
    "2": "Odd parity"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2050,
   "documented": "0802",
   "name": "Inverter number [F802]",
   "description": "0-247; use 1-247 for Modbus (0 = broadcast).",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2051,
   "documented": "0803",
   "name": "RS485 (1) time-out time [F803]",
   "description": "0.0 = disabled, 0.1-100.0 s.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "s",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2052,
   "documented": "0804",
   "name": "RS485 (1) time-out operation [F804]",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "1": "Continue running",
    "4": "Trip",
    "6": "Trip after deceleration stop"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2053,
   "documented": "0805",
   "name": "RS485 (1) transmission wait time [F805]",
   "description": "0.00-2.00 s.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "s",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2055,
   "documented": "0807",
   "name": "RS485 (1) protocol [F807]",
   "description": "Takes effect after reset.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "TOSHIBA",
    "1": "MODBUS"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2056,
   "documented": "0808",
   "name": "RS485 (1) time-out detection [F808]",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Always",
    "1": "When run and frequency commands come from comms",
    "2": "During run by communication"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2096,
   "documented": "0830",
   "name": "MODBUS continuous address [F830]",
   "description": "How block reads step through missing numbers.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Disabled (skip non-existent numbers)",
    "1": "Enabled (all addresses)"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 64000,
   "documented": "FA00",
   "name": "RS485 (1) command 1",
   "description": "Run/stop and control bits; set bit 15 for run priority, bit 14 for frequency priority.",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": {
    "0": "Preset speed bit 1",
    "1": "Preset speed bit 2",
    "2": "Preset speed bit 3",
    "3": "Preset speed bit 4",
    "4": "V/f switching (1 = V/f2)",
    "5": "PID control off",
    "6": "Acc/Dec switching (1 = Acc/Dec 2)",
    "7": "Forced DC braking",
    "8": "Jog run",
    "9": "Direction (0 = forward, 1 = reverse)",
    "10": "Run (0 = stop, 1 = run)",
    "11": "Coast stop",
    "12": "Emergency off (E trip)",
    "13": "Reset",
    "14": "Frequency command priority (comms)",
    "15": "Run command priority (comms)"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 64001,
   "documented": "FA01",
   "name": "RS485 (1) frequency command",
   "description": "0 to maximum frequency (FH).",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "Hz",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 64004,
   "documented": "FA04",
   "name": "RS485 (2) command 1",
   "description": "Same bit layout as FA00, for RS485 port 2.",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": {
    "0": "Preset speed bit 1",
    "1": "Preset speed bit 2",
    "2": "Preset speed bit 3",
    "3": "Preset speed bit 4",
    "4": "V/f switching (1 = V/f2)",
    "5": "PID control off",
    "6": "Acc/Dec switching (1 = Acc/Dec 2)",
    "7": "Forced DC braking",
    "8": "Jog run",
    "9": "Direction (0 = forward, 1 = reverse)",
    "10": "Run (0 = stop, 1 = run)",
    "11": "Coast stop",
    "12": "Emergency off (E trip)",
    "13": "Reset",
    "14": "Frequency command priority (comms)",
    "15": "Run command priority (comms)"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 64005,
   "documented": "FA05",
   "name": "RS485 (2) frequency command",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "Hz",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 64019,
   "documented": "FA13",
   "name": "RS485 (1) motor speed command",
   "description": "0-32700 rpm.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "rpm",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 64048,
   "documented": "FA30",
   "name": "RS485 (1) torque command",
   "description": "-250.00 to 250.00 %.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "%",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 64080,
   "documented": "FA50",
   "name": "Terminal output data",
   "description": "Drives outputs assigned to 'designated data' functions.",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 64081,
   "documented": "FA51",
   "name": "Terminal FM output data",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "%",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 64082,
   "documented": "FA52",
   "name": "Terminal AM output data",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "%",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 64263,
   "documented": "FB07",
   "name": "Inverter series type",
   "description": "Reads 178 on a VF-AS3.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 64656,
   "documented": "FC90",
   "name": "Current trip",
   "description": "Trip code of the present trip.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 64657,
   "documented": "FC91",
   "name": "Alarm",
   "description": "Alarm information word.",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 64768,
   "documented": "FD00",
   "name": "Output frequency",
   "description": "Current value.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "Hz",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 64769,
   "documented": "FD01",
   "name": "Status information 1",
   "description": "Current status.",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "0": "Failure FL output",
    "1": "Tripped",
    "2": "Alarm occurring",
    "3": "Main circuit undervoltage (MOFF)",
    "4": "V/f2 active",
    "5": "PID control off",
    "6": "Acc/Dec 2 active",
    "7": "DC braking",
    "8": "Jog run",
    "9": "Reverse run",
    "10": "Running",
    "11": "Coast stop (ST off)",
    "12": "Emergency off",
    "13": "Ready for run 1 (ST on)",
    "14": "Ready for run 2",
    "15": "HAND / LOC (0 = AUTO / REM)"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 64770,
   "documented": "FD02",
   "name": "Frequency command value",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "Hz",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 64771,
   "documented": "FD03",
   "name": "Output current",
   "description": "% of inverter rated current.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 64772,
   "documented": "FD04",
   "name": "Input voltage (DC detection)",
   "description": "% of rated voltage.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 64773,
   "documented": "FD05",
   "name": "Output voltage",
   "description": "% of rated voltage.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 64774,
   "documented": "FD06",
   "name": "Input terminal status",
   "description": "",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 64775,
   "documented": "FD07",
   "name": "Output terminal status",
   "description": "",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 64789,
   "documented": "FD15",
   "name": "Motor primary frequency",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "Hz",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 64792,
   "documented": "FD18",
   "name": "Torque",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 64802,
   "documented": "FD22",
   "name": "PID feedback value",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "Hz",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 64803,
   "documented": "FD23",
   "name": "Motor overload factor (OL2)",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 64804,
   "documented": "FD24",
   "name": "Inverter overload factor (OL1)",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 64806,
   "documented": "FD26",
   "name": "Motor load factor",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 64807,
   "documented": "FD27",
   "name": "Inverter load factor",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 64809,
   "documented": "FD29",
   "name": "Input power",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "kW",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 64816,
   "documented": "FD30",
   "name": "Output power",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "kW",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 64833,
   "documented": "FD41",
   "name": "Cumulative cooling fan run time",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 10,
   "units": "h",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 64834,
   "documented": "FD42",
   "name": "Inverter status 2",
   "description": "",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 64856,
   "documented": "FD58",
   "name": "PID set value",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "Hz",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 64888,
   "documented": "FD78",
   "name": "Power circuit board temperature",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 64899,
   "documented": "FD83",
   "name": "Internal temperature 1",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 64912,
   "documented": "FD90",
   "name": "Motor speed (estimated)",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "rpm",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 65032,
   "documented": "FE08",
   "name": "Inverter CPU version",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 65040,
   "documented": "FE10",
   "name": "Past trip 1 (latest)",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 65041,
   "documented": "FE11",
   "name": "Past trip 2",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 65042,
   "documented": "FE12",
   "name": "Past trip 3",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 65043,
   "documented": "FE13",
   "name": "Past trip 4",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 65044,
   "documented": "FE14",
   "name": "Cumulative run time",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "h",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 65077,
   "documented": "FE35",
   "name": "Terminal RR input value",
   "description": "0-100.00 %.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 65078,
   "documented": "FE36",
   "name": "Terminal RX input value",
   "description": "-100.00 to 100.00 %.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 65079,
   "documented": "FE37",
   "name": "Terminal II input value",
   "description": "0-100.00 %.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 65136,
   "documented": "FE70",
   "name": "Inverter rated current",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "A",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 65137,
   "documented": "FE71",
   "name": "Inverter rated voltage",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "V",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 65145,
   "documented": "FE79",
   "name": "Parts replacement alarm status",
   "description": "",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 65152,
   "documented": "FE80",
   "name": "Cumulative power-on time",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 10,
   "units": "h",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  }
 ],
 "integration": {
  "summary": "Set F807 = 1 (MODBUS), F802 to a non-zero address and F800/F801 for the line, then power-cycle. Write FA01 with the frequency and FA00 = 8400h (bit 15 run priority + bit 10 run) to run forward, adding bit 14 (C400h) when the frequency also comes from comms; read FD00, FD01, FD03 and FC90 for status.",
  "minimum_registers": [
   {
    "table": "holding_register",
    "address": 64000,
    "why": "Command word FA00"
   },
   {
    "table": "holding_register",
    "address": 64001,
    "why": "Frequency command FA01"
   },
   {
    "table": "holding_register",
    "address": 64768,
    "why": "Output frequency FD00"
   },
   {
    "table": "holding_register",
    "address": 64769,
    "why": "Status word FD01"
   },
   {
    "table": "holding_register",
    "address": 64771,
    "why": "Output current FD03"
   },
   {
    "table": "holding_register",
    "address": 64656,
    "why": "Current trip FC90"
   }
  ],
  "enable": "Set F807 (port 1) or F827 (port 2) to 1: MODBUS and reset the drive. Commands from FA00/FA01 are accepted regardless of CMOd/FMOd once FA00 bit 15 (run priority) and/or bit 14 (frequency priority) are set; that priority stays until cleared, power-off or reset.",
  "watchdog": "F803 sets the RS485 time-out (0.0 = off, 0.1-100.0 s); F804 picks continue, trip, or trip after deceleration stop; F808 sets when the time-out is checked. The manual says the time-out should be set so the drive stops on comm loss.",
  "quirks": [
   "Addresses are the hexadecimal communication numbers (FA00, FD00 ...), not 4xxxx numbers.",
   "A plain 03 read returns one word; multi-word direct reads are limited to 8 words and skip numbers that do not exist unless F830 = 1. Missing numbers read as 8000H.",
   "Manual examples: 8400H = run forward with run priority; 8600H / C600H = run reverse (C600H also takes frequency priority)."
  ],
  "setup": [
   "F800 baud: 0 = 9600, 1 = 19200 (default), 2 = 38400; F801 parity default even; both take effect after reset. With F809 (operation panel connection) at its default 1 = connector 1, port 1 is fixed at 19200 bps / even parity whatever F800/F801 say (likewise F820/F821 for port 2 when F809 = 2).",
   "F802 inverter number defaults to 0 (broadcast): set 1-247 for Modbus.",
   "Inverter-to-inverter communication (F806/F826) does not work in Modbus mode."
  ],
  "gotchas": [
   "Emergency off (bit 12) and PID-off bits in FA00 act even without the priority bits set.",
   "Changing F809 (operation panel connection priority) can lock out the LCD panel until it is rewritten over comms.",
   "F806/F826 inverter-to-inverter settings are disabled on the connector chosen in F809."
  ]
 },
 "page": "https://easymodbus.com/modbus-register-maps/toshiba/vf-as3",
 "address_note": "address = 0-based Modbus wire (PDU) address; documented = as printed in the source.",
 "note": "Re-typed from the manufacturer's public documentation (see source) and verified against it. Registers vary by firmware and options; verify against the live device before writing."
}