 "manufacturer": "Toshiba",
 "manufacturer_slug": "toshiba",
 "model": "TOSVERT VF-nC3 compact inverter (Modbus RTU)",
 "model_slug": "vf-nc3",
 "short_model": "VF-nC3",
 "aliases": [
  "VF-nC3",
  "VF-nC3M",
  "TOSVERT VF-nC3",
  "VFNC3"
 ],
 "equipment_type": "Variable frequency drive",
 "applies_to": "Toshiba TOSVERT VF-nC3 series inverters using the built-in RS-485 port with f829 = 1 (Modbus RTU), per manual E6581657.",
 "summary": "The VF-nC3 is a small Toshiba inverter whose RS-485 port speaks either Toshiba's own protocol or a subset of Modbus RTU. Every value has a hex communication number that is used directly as the Modbus register address. This map covers the comms command words (FA..), the monitor block (FC../FD../FE..) and the communication setup parameters.",
 "transport": [
  "RTU"
 ],
 "defaults": {
  "unit_id": 0,
  "baud": 19200,
  "parity": "Even",
  "data_bits": 8,
  "stop_bits": null,
  "tcp_port": null
 },
 "addressing": {
  "convention": "hex 0-based",
  "note": "Communication numbers are hex and go on the wire unchanged: the manual's read example sends 01 03 FD 00 00 01 for output frequency FD00, and the direct block-read example sends 01 03 01 30 for parameter f130 (communication number 0130). Parameters f### use communication number 0###."
 },
 "default_word_order": null,
 "firmware": null,
 "source": {
  "title": "TOSVERT VF-nC3 Series RS485 Communication Function Instruction Manual",
  "doc_number": "E6581657",
  "revision_date": null,
  "url": "https://www.toshiba.com/tic/datafiles/manuals/NC3_RS485_Communication_Manual.pdf",
  "pages": "pp. 23-38 (Modbus RTU), p. 40 (comm parameters), pp. 44-54 (commands, status, alarms, trip codes), pp. 60-61 (command and monitor tables)"
 },
 "notes": [
  "Every register here is a single 16-bit word; the manual has no 32-bit values.",
  "FD.. registers give live values; the matching FE.. numbers (FE00-FE49) hold the same item frozen at the last trip. Only the live set is listed, plus the FE-only items.",
  "Left out: torque (FD18) and torque current (FD20), because the manual does not say whether these words are signed; FB05 capacity code (needs the Appendix 3 lookup); LED/keypad registers FA10/FA11/FA65-FA80; block-communication parameters f870-f879.",
  "Output current, output voltage and DC voltage are percentages of the drive rating, not amps or volts.",
  "Section 7.2 names the VI monitor FE35, while the block-read list calls it FE36; the monitor table on p. 61 says FE35, which is used here.",
  "The frequency command FA01 and command words FA00/FA20 are RAM only and reset at power-off, fault reset or factory reset.",
  "Other drive parameters follow the same rule (f### = communication number 0###); scale = the minimum setting unit in the drive's parameter list."
 ],
 "registers": [
  {
   "table": "holding_register",
   "address": 2048,
   "documented": "0800H",
   "name": "Baud rate (f800)",
   "description": "Applies after reset.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "3": "9600 bps",
    "4": "19200 bps",
    "5": "38400 bps"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2049,
   "documented": "0801H",
   "name": "Parity (f801)",
   "description": "Applies after reset.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "None",
    "1": "Even",
    "2": "Odd"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2050,
   "documented": "0802H",
   "name": "Inverter number (f802)",
   "description": "Modbus slave address 0-247; 0 is broadcast.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2051,
   "documented": "0803H",
   "name": "Comm time-out time (f803)",
   "description": "0.0 = disabled, 0.1-100.0 s.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "s",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2052,
   "documented": "0804H",
   "name": "Comm time-out action (f804)",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Alarm only",
    "1": "Trip, coast stop",
    "2": "Trip, slowdown stop"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2053,
   "documented": "0805H",
   "name": "Send waiting time (f805)",
   "description": "0.00 = normal, up to 2.00 s.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "s",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2056,
   "documented": "0808H",
   "name": "Comm time-out detection (f808)",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Always",
    "1": "During communication",
    "2": "During communication and running"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2089,
   "documented": "0829H",
   "name": "Communication protocol (f829)",
   "description": "Applies after reset.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "TOSHIBA protocol",
    "1": "MODBUS-RTU"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 64000,
   "documented": "FA00H",
   "name": "Command 1",
   "description": "Run/stop, direction, presets, reset; bits 14/15 hand control to comms.",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": {
    "0": "Preset speed bit 1",
    "1": "Preset speed bit 2",
    "2": "Preset speed bit 3",
    "3": "Preset speed bit 4",
    "4": "Motor 2 (THR2) select",
    "5": "PID control off",
    "6": "Accel/decel pattern 2 (AD2)",
    "7": "Forced DC braking",
    "8": "Jog run",
    "9": "Reverse (0 = forward)",
    "10": "Run (0 = stop)",
    "11": "Coast stop",
    "12": "Emergency stop (always enabled)",
    "13": "Fault reset (no reply sent)",
    "14": "Frequency priority: take frequency from comms",
    "15": "Command priority: take run commands from comms"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 64001,
   "documented": "FA01H",
   "name": "Frequency command",
   "description": "Comms frequency reference; needs FA00 bit 14 or fmod = 3.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "Hz",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 64003,
   "documented": "FA03H",
   "name": "Panel operation frequency",
   "description": "Between LL and UL; stored in EEPROM.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "Hz",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 64032,
   "documented": "FA20H",
   "name": "Command 2",
   "description": "Needs FA00 bit 15 set; write 0 to reserved bits.",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": {
    "7": "Maximum deceleration forced stop",
    "12": "OC stall level 2 (F185) instead of 1 (F601)"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 64080,
   "documented": "FA50H",
   "name": "Terminal output data",
   "description": "Drives the OUT terminal when f130-f132 = 92/93.",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": {
    "0": "Specified data output 1"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 64081,
   "documented": "FA51H",
   "name": "FM analog output data",
   "description": "Used when fmsl = 18; 8-bit resolution.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "%",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 64135,
   "documented": "FA87H",
   "name": "Reset information",
   "description": "Write 1; the drive clears it to 0 after it resets.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 64263,
   "documented": "FB07H",
   "name": "Inverter series type",
   "description": "Reads 208 on a VF-nC3.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 64656,
   "documented": "FC90H",
   "name": "Trip code",
   "description": "Present trip.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "No error",
    "1": "Over-current during acceleration",
    "2": "Over-current during deceleration",
    "3": "Over-current at constant speed",
    "4": "Over-current in load at startup",
    "5": "Arm over-current at start-up",
    "8": "Input phase failure",
    "9": "Output phase failure",
    "10": "Overvoltage during acceleration",
    "11": "Overvoltage during deceleration",
    "12": "Overvoltage at constant speed",
    "13": "Inverter overload",
    "14": "Motor overload",
    "15": "Braking resistor overload",
    "16": "Overheat",
    "17": "Emergency stop",
    "18": "EEPROM fault",
    "19": "Initial read error",
    "20": "Initial read error",
    "21": "Inverter RAM fault",
    "22": "Inverter ROM fault",
    "23": "CPU fault",
    "24": "Communication time-out",
    "26": "Output current detector error",
    "27": "Option error",
    "29": "Low current operation",
    "30": "Main circuit undervoltage",
    "32": "Over-torque trip",
    "34": "Ground fault",
    "40": "Tuning error",
    "41": "Inverter type error",
    "42": "Analog input overvoltage",
    "45": "Speed error",
    "46": "External thermal",
    "50": "Terminal input error",
    "51": "CPU2 communication fault",
    "52": "V/f control error",
    "53": "CPU2 fault",
    "58": "CPU3 fault",
    "62": "Main device overheat",
    "81": "External power logic switching check alarm",
    "82": "Source logic switching check alarm",
    "83": "Sink logic switching check alarm",
    "84": "Auto-tuning error"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 64657,
   "documented": "FC91H",
   "name": "Alarm information 1",
   "description": "",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "0": "Over-current alarm",
    "1": "Inverter overload alarm",
    "2": "Motor overload alarm",
    "3": "Overheat alarm",
    "4": "Overvoltage alarm",
    "5": "Main circuit undervoltage alarm",
    "6": "Main device overheat alarm",
    "7": "Low current alarm",
    "10": "Cumulative operation time alarm",
    "13": "Main circuit undervoltage (MOFF)",
    "14": "Forced decel/stop on momentary power failure",
    "15": "Auto stop on prolonged lower-limit running"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 64658,
   "documented": "FC92H",
   "name": "Alarm information 2",
   "description": "",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "2": "Life time alarm",
    "3": "Over-torque alarm",
    "4": "Overload stall alarm",
    "7": "Output frequency upper limit alarm"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 64768,
   "documented": "FD00H",
   "name": "Output frequency",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "Hz",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 64769,
   "documented": "FD01H",
   "name": "Inverter status 1",
   "description": "",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "0": "FL fault output active",
    "1": "Tripped (incl. retry / trip hold)",
    "2": "Alarm issued",
    "3": "Main circuit undervoltage",
    "4": "Motor 2 (THR2) selected",
    "5": "PID control prohibited",
    "6": "Accel/decel pattern 2 (AD2)",
    "7": "Forced DC braking",
    "8": "Jog run",
    "9": "Reverse (0 = forward)",
    "10": "Run (0 = stop)",
    "11": "Coast stop: ST off",
    "12": "Emergency stop state",
    "13": "Standby with ST on",
    "14": "Standby"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 64770,
   "documented": "FD02H",
   "name": "Frequency command value",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "Hz",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 64771,
   "documented": "FD03H",
   "name": "Output current",
   "description": "Percent of drive rated current.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 64772,
   "documented": "FD04H",
   "name": "Input voltage (DC detection)",
   "description": "Percent value.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 64773,
   "documented": "FD05H",
   "name": "Output voltage",
   "description": "Percent value.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 64774,
   "documented": "FD06H",
   "name": "Input terminal information",
   "description": "",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "0": "F",
    "1": "R",
    "2": "S1",
    "3": "S2",
    "4": "VI (logic input mode)"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 64775,
   "documented": "FD07H",
   "name": "Output terminal information",
   "description": "",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "0": "OUT",
    "2": "FL"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 64789,
   "documented": "FD15H",
   "name": "Compensated frequency",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "Hz",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 64790,
   "documented": "FD16H",
   "name": "Estimated speed",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "Hz",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 64802,
   "documented": "FD22H",
   "name": "PID feedback value",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "Hz",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 64803,
   "documented": "FD23H",
   "name": "Motor overload factor (OL2)",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 64804,
   "documented": "FD24H",
   "name": "Inverter overload factor (OL1)",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 64806,
   "documented": "FD26H",
   "name": "Motor load factor",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 64807,
   "documented": "FD27H",
   "name": "Inverter load factor",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 64809,
   "documented": "FD29H",
   "name": "Input power",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "kW",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 64816,
   "documented": "FD30H",
   "name": "Output power",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "kW",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 64834,
   "documented": "FD42H",
   "name": "Inverter status 2",
   "description": "",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "7": "Maximum deceleration forced stop active",
    "8": "Accel/decel pattern 2 (AD2)",
    "12": "OC stall level 2"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 64837,
   "documented": "FD45H",
   "name": "Command mode status",
   "description": "Which source the run command comes from.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Terminal input",
    "1": "Operation panel",
    "2": "RS485 communication"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 64838,
   "documented": "FD46H",
   "name": "Frequency setting mode status",
   "description": "Which source sets the frequency.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "VI input",
    "1": "Operation panel (auto-save off)",
    "2": "Operation panel (auto-save on)",
    "3": "RS485 communication",
    "5": "UP/DOWN frequency",
    "255": "Preset speed operation"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 64841,
   "documented": "FD49H",
   "name": "Inverter status 3",
   "description": "",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "10": "Running at constant speed",
    "11": "Healthy signal",
    "12": "Accel/decel complete (RCH)",
    "13": "Specified speed reached (RCHF)",
    "14": "Accelerating",
    "15": "Decelerating"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 65032,
   "documented": "FE08H",
   "name": "CPU version 1 (application)",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 65040,
   "documented": "FE10H",
   "name": "Past trip 1 (latest)",
   "description": "Same codes as FC90.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "No error",
    "1": "Over-current during acceleration",
    "2": "Over-current during deceleration",
    "3": "Over-current at constant speed",
    "4": "Over-current in load at startup",
    "5": "Arm over-current at start-up",
    "8": "Input phase failure",
    "9": "Output phase failure",
    "10": "Overvoltage during acceleration",
    "11": "Overvoltage during deceleration",
    "12": "Overvoltage at constant speed",
    "13": "Inverter overload",
    "14": "Motor overload",
    "15": "Braking resistor overload",
    "16": "Overheat",
    "17": "Emergency stop",
    "18": "EEPROM fault",
    "19": "Initial read error",
    "20": "Initial read error",
    "21": "Inverter RAM fault",
    "22": "Inverter ROM fault",
    "23": "CPU fault",
    "24": "Communication time-out",
    "26": "Output current detector error",
    "27": "Option error",
    "29": "Low current operation",
    "30": "Main circuit undervoltage",
    "32": "Over-torque trip",
    "34": "Ground fault",
    "40": "Tuning error",
    "41": "Inverter type error",
    "42": "Analog input overvoltage",
    "45": "Speed error",
    "46": "External thermal",
    "50": "Terminal input error",
    "51": "CPU2 communication fault",
    "52": "V/f control error",
    "53": "CPU2 fault",
    "58": "CPU3 fault",
    "62": "Main device overheat",
    "81": "External power logic switching check alarm",
    "82": "Source logic switching check alarm",
    "83": "Sink logic switching check alarm",
    "84": "Auto-tuning error"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 65041,
   "documented": "FE11H",
   "name": "Past trip 2",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "No error",
    "1": "Over-current during acceleration",
    "2": "Over-current during deceleration",
    "3": "Over-current at constant speed",
    "4": "Over-current in load at startup",
    "5": "Arm over-current at start-up",
    "8": "Input phase failure",
    "9": "Output phase failure",
    "10": "Overvoltage during acceleration",
    "11": "Overvoltage during deceleration",
    "12": "Overvoltage at constant speed",
    "13": "Inverter overload",
    "14": "Motor overload",
    "15": "Braking resistor overload",
    "16": "Overheat",
    "17": "Emergency stop",
    "18": "EEPROM fault",
    "19": "Initial read error",
    "20": "Initial read error",
    "21": "Inverter RAM fault",
    "22": "Inverter ROM fault",
    "23": "CPU fault",
    "24": "Communication time-out",
    "26": "Output current detector error",
    "27": "Option error",
    "29": "Low current operation",
    "30": "Main circuit undervoltage",
    "32": "Over-torque trip",
    "34": "Ground fault",
    "40": "Tuning error",
    "41": "Inverter type error",
    "42": "Analog input overvoltage",
    "45": "Speed error",
    "46": "External thermal",
    "50": "Terminal input error",
    "51": "CPU2 communication fault",
    "52": "V/f control error",
    "53": "CPU2 fault",
    "58": "CPU3 fault",
    "62": "Main device overheat",
    "81": "External power logic switching check alarm",
    "82": "Source logic switching check alarm",
    "83": "Sink logic switching check alarm",
    "84": "Auto-tuning error"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 65042,
   "documented": "FE12H",
   "name": "Past trip 3",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "No error",
    "1": "Over-current during acceleration",
    "2": "Over-current during deceleration",
    "3": "Over-current at constant speed",
    "4": "Over-current in load at startup",
    "5": "Arm over-current at start-up",
    "8": "Input phase failure",
    "9": "Output phase failure",
    "10": "Overvoltage during acceleration",
    "11": "Overvoltage during deceleration",
    "12": "Overvoltage at constant speed",
    "13": "Inverter overload",
    "14": "Motor overload",
    "15": "Braking resistor overload",
    "16": "Overheat",
    "17": "Emergency stop",
    "18": "EEPROM fault",
    "19": "Initial read error",
    "20": "Initial read error",
    "21": "Inverter RAM fault",
    "22": "Inverter ROM fault",
    "23": "CPU fault",
    "24": "Communication time-out",
    "26": "Output current detector error",
    "27": "Option error",
    "29": "Low current operation",
    "30": "Main circuit undervoltage",
    "32": "Over-torque trip",
    "34": "Ground fault",
    "40": "Tuning error",
    "41": "Inverter type error",
    "42": "Analog input overvoltage",
    "45": "Speed error",
    "46": "External thermal",
    "50": "Terminal input error",
    "51": "CPU2 communication fault",
    "52": "V/f control error",
    "53": "CPU2 fault",
    "58": "CPU3 fault",
    "62": "Main device overheat",
    "81": "External power logic switching check alarm",
    "82": "Source logic switching check alarm",
    "83": "Sink logic switching check alarm",
    "84": "Auto-tuning error"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 65043,
   "documented": "FE13H",
   "name": "Past trip 4 (earliest)",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "No error",
    "1": "Over-current during acceleration",
    "2": "Over-current during deceleration",
    "3": "Over-current at constant speed",
    "4": "Over-current in load at startup",
    "5": "Arm over-current at start-up",
    "8": "Input phase failure",
    "9": "Output phase failure",
    "10": "Overvoltage during acceleration",
    "11": "Overvoltage during deceleration",
    "12": "Overvoltage at constant speed",
    "13": "Inverter overload",
    "14": "Motor overload",
    "15": "Braking resistor overload",
    "16": "Overheat",
    "17": "Emergency stop",
    "18": "EEPROM fault",
    "19": "Initial read error",
    "20": "Initial read error",
    "21": "Inverter RAM fault",
    "22": "Inverter ROM fault",
    "23": "CPU fault",
    "24": "Communication time-out",
    "26": "Output current detector error",
    "27": "Option error",
    "29": "Low current operation",
    "30": "Main circuit undervoltage",
    "32": "Over-torque trip",
    "34": "Ground fault",
    "40": "Tuning error",
    "41": "Inverter type error",
    "42": "Analog input overvoltage",
    "45": "Speed error",
    "46": "External thermal",
    "50": "Terminal input error",
    "51": "CPU2 communication fault",
    "52": "V/f control error",
    "53": "CPU2 fault",
    "58": "CPU3 fault",
    "62": "Main device overheat",
    "81": "External power logic switching check alarm",
    "82": "Source logic switching check alarm",
    "83": "Sink logic switching check alarm",
    "84": "Auto-tuning error"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 65044,
   "documented": "FE14H",
   "name": "Cumulative operation time",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "h",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 65077,
   "documented": "FE35H",
   "name": "VI input",
   "description": "10-bit analog input, 0-100%.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 65136,
   "documented": "FE70H",
   "name": "Rated current",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "A",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 65137,
   "documented": "FE71H",
   "name": "Rated voltage",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "V",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 65139,
   "documented": "FE73H",
   "name": "CPU version 2 (motor)",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 65145,
   "documented": "FE79H",
   "name": "Part replacement alarm information",
   "description": "",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "0": "Fan life alarm",
    "1": "Circuit board life alarm",
    "2": "Main-circuit capacitor life alarm",
    "3": "Cumulative operation time alarm"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 65152,
   "documented": "FE80H",
   "name": "Cumulative power-on time",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "h",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  }
 ],
 "integration": {
  "summary": "Set f829 = 1 (Modbus RTU) and f802 to a non-zero address, then power-cycle. Write FA00 = C400H (command and frequency priority + run forward) and the speed in FA01 (0.01 Hz), and poll FD00/FD01/FC90 for speed, status and trip.",
  "minimum_registers": [
   {
    "table": "holding_register",
    "address": 64000,
    "why": "Run/stop and comms priority bits"
   },
   {
    "table": "holding_register",
    "address": 64001,
    "why": "Speed reference, 0.01 Hz"
   },
   {
    "table": "holding_register",
    "address": 64768,
    "why": "Output frequency"
   },
   {
    "table": "holding_register",
    "address": 64769,
    "why": "Running / tripped / alarm status"
   },
   {
    "table": "holding_register",
    "address": 64771,
    "why": "Output current, % of rating"
   },
   {
    "table": "holding_register",
    "address": 64656,
    "why": "Present trip code"
   },
   {
    "table": "holding_register",
    "address": 64657,
    "why": "Pre-alarm bits"
   }
  ],
  "enable": "Set f829 (communication protocol) to 1 = MODBUS-RTU; the factory setting is 0 (Toshiba protocol). Baud f800, parity f801 and the protocol take effect only after a reset or power cycle. Comms run/frequency control is taken by setting FA00 bits 15 and 14, independent of cmod/fmod.",
  "watchdog": "f803 sets a communication time-out (0.0 = off, 0.1-100.0 s); f804 picks alarm only, trip with coast stop or trip with slowdown stop (trip shows err5); f808 sets when it is checked (always, during comms mode, or comms mode and running).",
  "quirks": [
   "The inverter number factory value is 0, which Modbus treats as broadcast with no reply; set 1-247 first.",
   "FA00 bit 13 (fault reset) gets no reply from the drive.",
   "Missing communication numbers inside a multi-word read come back as 8000H.",
   "An input terminal set to function 48/49 (forced local) overrides comms commands and frequency.",
   "Function 03 reads at most 8 consecutive words in one request (direct block read); a plain read is one word."
  ],
  "setup": [
   "f800 baud: 3 = 9600, 4 = 19200 (default), 5 = 38400.",
   "f801 parity: 0 none, 1 even (default), 2 odd.",
   "f802 address 1-247.",
   "f805 adds reply delay for slow RS-485 converters (CPU1 v108 and later).",
   "Power-cycle after changing f800, f801 or f829."
  ],
  "gotchas": [
   "Do not write EEPROM-backed parameters cyclically; the manual rates the EEPROM at about 10,000 writes.",
   "Comms do not answer for about one second after power-up.",
   "f700 = 2 blocks parameter writes over RS-485 (error code 04)."
  ]
 },
 "page": "https://easymodbus.com/modbus-register-maps/toshiba/vf-nc3",
 "address_note": "address = 0-based Modbus wire (PDU) address; documented = as printed in the source.",
 "note": "Re-typed from the manufacturer's public documentation (see source) and verified against it. Registers vary by firmware and options; verify against the live device before writing."
}