 "manufacturer": "Trafag",
 "manufacturer_slug": "trafag",
 "model": "8775 gas density sensor / 879x hybrid gas density monitor (legacy Modbus map)",
 "model_slug": "8775-879x-legacy",
 "short_model": "8775 / 879x",
 "aliases": [
  "8775",
  "8791",
  "8792",
  "8793",
  "879x",
  "Trafag gas density monitor"
 ],
 "equipment_type": "Sensor (gas density)",
 "applies_to": "Trafag 8775 and 879x (8791/8792/8793) running the 'Legacy' Modbus configuration of software description H73622a (10/2025).",
 "summary": "The Trafag 8775 sensor and 879x hybrid monitor measure the density of a specified gas or gas mixture with a pair of quartz oscillators, and report it over Modbus RTU. This map is the manual's 'Legacy' configuration: scaled 16-bit density, pressure and temperature, identification, serial settings and a sensor-status discrete input.",
 "transport": [
  "RTU"
 ],
 "defaults": {
  "unit_id": null,
  "baud": null,
  "parity": null,
  "data_bits": null,
  "stop_bits": null,
  "tcp_port": null
 },
 "addressing": {
  "convention": "0-based",
  "note": "Addresses are protocol addresses. The manual's example reads density (address 0) with start address 0x0000 and the serial number (address 5) with 0x0005."
 },
 "default_word_order": "ABCD",
 "firmware": null,
 "source": {
  "title": "Software Instruction Sensor/Monitor - 8775 Gas Density Sensor, 879x Hybrid Gas Density Monitor",
  "doc_number": "H73622a",
  "revision_date": "2025-10",
  "url": "https://media.trafag.com/instruction/H73622a_87xx_Software-Instruction-Density-Sensor_A4.pdf",
  "pages": "Legacy input registers p. 8; legacy holding registers p. 9; discrete input p. 10"
 },
 "notes": [
  "The manual describes two Modbus configurations, 'Legacy' and 'Standard', with different maps at the same addresses. This file is the Legacy map only; it does not say which units ship with which.",
  "Left out: the Standard map (float density/pressure/temperature at 0-48, hour meter, status flag words, serial number U64), because the manual gives no word order for its floats and 32/64-bit values.",
  "32-bit values in the Legacy map are marked big-endian; the serial-number example (0x075BCD15 split as 0x075B, 0xCD15) shows high word first.",
  "Left out: 'Quartz frequency difference' (address 8), a fixed dummy value of 1000 from firmware V2.0, and 'Mode' (holding 6), marked non-functional.",
  "Parity choice also fixes stop bits: none = 2 stop bits, odd/even = 1 stop bit.",
  "Holding registers are stored in EEPROM; the manual warns that excessive writing can wear it out.",
  "Server ID can also be changed by broadcast using the serial number (section 5.4)."
 ],
 "registers": [
  {
   "table": "discrete_input",
   "address": 0,
   "documented": "0",
   "name": "Sensor status",
   "description": "0 = working properly, 1 = sensor error.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 0,
   "documented": "0",
   "name": "Gas density",
   "description": "0xFFFF when out of range.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "kg/m3",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 1,
   "documented": "1",
   "name": "Gas pressure (abs, @20°C)",
   "description": "0xFFFF when out of range.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "kPa",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 2,
   "documented": "2",
   "name": "Gas temperature",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "K",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 3,
   "documented": "3",
   "name": "Gas pressure (abs, at gas temperature)",
   "description": "0xFFFF when out of range.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "kPa",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 4,
   "documented": "4",
   "name": "Server ID",
   "description": "1-247.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 5,
   "documented": "5+6",
   "name": "Serial number",
   "description": "Big-endian; e.g. 0x075BCD15 = 123456-789.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 7,
   "documented": "7",
   "name": "Firmware release version",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2,
   "documented": "2",
   "name": "Server ID",
   "description": "1-247.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 3,
   "documented": "3+4",
   "name": "Baud rate",
   "description": "1200, 2400, 4800, 9600, 14400, 19200, 28800, 38400, 56000 or 57600.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "baud",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 5,
   "documented": "5",
   "name": "Parity",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "None (2 stop bits)",
    "1": "Odd (1 stop bit)",
    "2": "Even (1 stop bit)"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 7,
   "documented": "7",
   "name": "Change to bootloader",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "1": "Enter bootloader mode for 10 s"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8,
   "documented": "8",
   "name": "Write permissions",
   "description": "Bit = 0 means writable, 1 means locked.",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "0": "Server ID locked",
    "1": "Baud rate locked",
    "2": "Parity locked"
   },
   "offset": 0
  }
 ],
 "integration": {
  "summary": "Read input registers 0-3 (function 04) for density, pressure and temperature as scaled integers, and discrete input 0 (function 02) for sensor status.",
  "minimum_registers": [
   {
    "table": "input_register",
    "address": 0,
    "why": "Gas density, kg/m3 x 0.01"
   },
   {
    "table": "input_register",
    "address": 1,
    "why": "Pressure @20°C, kPa x 0.1"
   },
   {
    "table": "input_register",
    "address": 2,
    "why": "Gas temperature, K x 0.1"
   },
   {
    "table": "discrete_input",
    "address": 0,
    "why": "Sensor error flag"
   }
  ],
  "enable": "Modbus RTU is always active. Server ID, baud rate and parity are holding registers 2-5; register 8 shows which of them are write-protected.",
  "watchdog": null,
  "quirks": [
   "0xFFFF in a measurement register means its range was exceeded.",
   "Temperature is in kelvin (x 0.1)."
  ],
  "setup": [
   "Terminate both bus ends with 120 Ohm (jumper J4 on hybrid units) and use 560 Ohm line polarisation."
  ],
  "gotchas": [
   "Confirm the unit runs the Legacy map; the Standard map puts floats at the same addresses."
  ]
 },
 "page": "https://easymodbus.com/modbus-register-maps/trafag/8775-879x-legacy",
 "address_note": "address = 0-based Modbus wire (PDU) address; documented = as printed in the source.",
 "note": "Re-typed from the manufacturer's public documentation (see source) and verified against it. Registers vary by firmware and options; verify against the live device before writing."
}