 "manufacturer": "Trumeter",
 "manufacturer_slug": "trumeter",
 "model": "APM Power meter (APM-PWR) Modbus map",
 "model_slug": "apm-power",
 "short_model": "APM Power",
 "aliases": [
  "APM-PWR",
  "APM Power",
  "Trumeter APM Power meter"
 ],
 "equipment_type": "Power meter (panel meter)",
 "applies_to": "Trumeter APM-PWR panel power meters with Modbus, per the Trumeter knowledge-base register map.",
 "summary": "Panel-mounted power and energy meter from the Trumeter APM family. Function code 4 input registers return 44 measurements as 32-bit floats (per-phase voltages, currents, powers, angles, power factor, THD, max load, totals and energy); function code 1 coils report ten alarm states.",
 "transport": [
  "RTU"
 ],
 "defaults": {
  "unit_id": null,
  "baud": null,
  "parity": null,
  "data_bits": null,
  "stop_bits": null,
  "tcp_port": null
 },
 "addressing": {
  "convention": "0-based",
  "note": "The table lists a parameter number and an 'Address' that starts at 0 (frequency at address 0, L1-L2 voltage at 2); the address column is used directly as the wire address."
 },
 "default_word_order": "ABCD",
 "firmware": null,
 "source": {
  "title": "Modbus Register Map - APM Power (Trumeter Knowledge Base)",
  "doc_number": null,
  "revision_date": null,
  "url": "https://help.trumeter.com/modbus-register-map-apm-power",
  "pages": "single web page: input register table, coil table, 'Modbus Sentence Protocol'"
 },
 "notes": [
  "Word order: the page states the floats use two 16-bit words with the most significant word sent first, and each word high byte first (ABCD).",
  "Values are the displayed values in whatever unit the meter is configured for (e.g. 415 for V or 8.7 for kVA), so units are not fixed here; check the meter's unit configuration.",
  "Serial settings and default address are not given on this page; set them in the meter's configuration menu.",
  "Transport is listed as RTU on the basis that the APM is an RS-485 panel meter; the page itself does not name the physical layer.",
  "Unsupported functions return exception 1 and unknown addresses exception 2."
 ],
 "registers": [
  {
   "table": "coil",
   "address": 0,
   "documented": "0",
   "name": "Alarm 1 status",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Alarm inactive",
    "1": "Alarm active"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 1,
   "documented": "1",
   "name": "Alarm 2 status",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Alarm inactive",
    "1": "Alarm active"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 2,
   "documented": "2",
   "name": "Alarm 3 status",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Alarm inactive",
    "1": "Alarm active"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 3,
   "documented": "3",
   "name": "Alarm 4 status",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Alarm inactive",
    "1": "Alarm active"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 4,
   "documented": "4",
   "name": "Alarm 5 status",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Alarm inactive",
    "1": "Alarm active"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 5,
   "documented": "5",
   "name": "Alarm 6 status",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Alarm inactive",
    "1": "Alarm active"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 6,
   "documented": "6",
   "name": "Alarm 7 status",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Alarm inactive",
    "1": "Alarm active"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 7,
   "documented": "7",
   "name": "Alarm 8 status",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Alarm inactive",
    "1": "Alarm active"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 8,
   "documented": "8",
   "name": "Alarm 9 status",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Alarm inactive",
    "1": "Alarm active"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 9,
   "documented": "9",
   "name": "Alarm 10 status",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Alarm inactive",
    "1": "Alarm active"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 0,
   "documented": "0",
   "name": "Frequency",
   "description": "Parameter 0. Value as shown on the display, in the configured unit.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 2,
   "documented": "2",
   "name": "L1 to L2 Voltage",
   "description": "Parameter 1. Value as shown on the display, in the configured unit.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 4,
   "documented": "4",
   "name": "L1 to N Voltage",
   "description": "Parameter 2. Value as shown on the display, in the configured unit.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 6,
   "documented": "6",
   "name": "L1 Current",
   "description": "Parameter 3. Value as shown on the display, in the configured unit.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 8,
   "documented": "8",
   "name": "L1 Active Power",
   "description": "Parameter 4. Value as shown on the display, in the configured unit.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 10,
   "documented": "10",
   "name": "L1 Apparent Power",
   "description": "Parameter 5. Value as shown on the display, in the configured unit.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 12,
   "documented": "12",
   "name": "L1 Reactive Power",
   "description": "Parameter 6. Value as shown on the display, in the configured unit.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 14,
   "documented": "14",
   "name": "L1 Current Phase Angle",
   "description": "Parameter 7. Value as shown on the display, in the configured unit.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 16,
   "documented": "16",
   "name": "L1 Power Factor",
   "description": "Parameter 8. Value as shown on the display, in the configured unit.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 18,
   "documented": "18",
   "name": "L1 Voltage THD",
   "description": "Parameter 9. Value as shown on the display, in the configured unit.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 20,
   "documented": "20",
   "name": "L1 Current THD",
   "description": "Parameter 10. Value as shown on the display, in the configured unit.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 22,
   "documented": "22",
   "name": "L1 Max Load",
   "description": "Parameter 11. Value as shown on the display, in the configured unit.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 24,
   "documented": "24",
   "name": "L1 to L2 Voltage Phase Angle",
   "description": "Parameter 12. Value as shown on the display, in the configured unit.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 26,
   "documented": "26",
   "name": "L2 to L3 Voltage",
   "description": "Parameter 13. Value as shown on the display, in the configured unit.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 28,
   "documented": "28",
   "name": "L2 to N Voltage",
   "description": "Parameter 14. Value as shown on the display, in the configured unit.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 30,
   "documented": "30",
   "name": "L2 Current",
   "description": "Parameter 15. Value as shown on the display, in the configured unit.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 32,
   "documented": "32",
   "name": "L2 Active Power",
   "description": "Parameter 16. Value as shown on the display, in the configured unit.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 34,
   "documented": "34",
   "name": "L2 Apparent Power",
   "description": "Parameter 17. Value as shown on the display, in the configured unit.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 36,
   "documented": "36",
   "name": "L2 Reactive Power",
   "description": "Parameter 18. Value as shown on the display, in the configured unit.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 38,
   "documented": "38",
   "name": "L2 Current Phase Angle",
   "description": "Parameter 19. Value as shown on the display, in the configured unit.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 40,
   "documented": "40",
   "name": "L2 Power Factor",
   "description": "Parameter 20. Value as shown on the display, in the configured unit.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 42,
   "documented": "42",
   "name": "L2 Voltage THD",
   "description": "Parameter 21. Value as shown on the display, in the configured unit.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 44,
   "documented": "44",
   "name": "L2 Current THD",
   "description": "Parameter 22. Value as shown on the display, in the configured unit.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 46,
   "documented": "46",
   "name": "L2 Max Load",
   "description": "Parameter 23. Value as shown on the display, in the configured unit.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 48,
   "documented": "48",
   "name": "L1 to L3 Voltage Phase Angle",
   "description": "Parameter 24. Value as shown on the display, in the configured unit.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 50,
   "documented": "50",
   "name": "L3 to L1 Voltage",
   "description": "Parameter 25. Value as shown on the display, in the configured unit.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 52,
   "documented": "52",
   "name": "L3 to N Voltage",
   "description": "Parameter 26. Value as shown on the display, in the configured unit.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 54,
   "documented": "54",
   "name": "L3 Current",
   "description": "Parameter 27. Value as shown on the display, in the configured unit.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 56,
   "documented": "56",
   "name": "L3 Active Power",
   "description": "Parameter 28. Value as shown on the display, in the configured unit.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 58,
   "documented": "58",
   "name": "L3 Apparent Power",
   "description": "Parameter 29. Value as shown on the display, in the configured unit.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 60,
   "documented": "60",
   "name": "L3 Reactive Power",
   "description": "Parameter 30. Value as shown on the display, in the configured unit.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 62,
   "documented": "62",
   "name": "L3 Current Phase Angle",
   "description": "Parameter 31. Value as shown on the display, in the configured unit.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 64,
   "documented": "64",
   "name": "L3 Power Factor",
   "description": "Parameter 32. Value as shown on the display, in the configured unit.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 66,
   "documented": "66",
   "name": "L3 Voltage THD",
   "description": "Parameter 33. Value as shown on the display, in the configured unit.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 68,
   "documented": "68",
   "name": "L3 Current THD",
   "description": "Parameter 34. Value as shown on the display, in the configured unit.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 70,
   "documented": "70",
   "name": "L3 Max Load",
   "description": "Parameter 35. Value as shown on the display, in the configured unit.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 72,
   "documented": "72",
   "name": "Internal Temperature",
   "description": "Parameter 36. Value as shown on the display, in the configured unit.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 74,
   "documented": "74",
   "name": "Active Energy",
   "description": "Parameter 37. Value as shown on the display, in the configured unit.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 76,
   "documented": "76",
   "name": "Apparent Energy",
   "description": "Parameter 38. Value as shown on the display, in the configured unit.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 78,
   "documented": "78",
   "name": "Reactive Energy",
   "description": "Parameter 39. Value as shown on the display, in the configured unit.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 80,
   "documented": "80",
   "name": "Total Active Power",
   "description": "Parameter 40. Value as shown on the display, in the configured unit.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 82,
   "documented": "82",
   "name": "Total Apparent Power",
   "description": "Parameter 41. Value as shown on the display, in the configured unit.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 84,
   "documented": "84",
   "name": "Total Reactive Power",
   "description": "Parameter 42. Value as shown on the display, in the configured unit.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 86,
   "documented": "86",
   "name": "All phase power factor",
   "description": "Parameter 43. Value as shown on the display, in the configured unit.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  }
 ],
 "integration": {
  "summary": "Read input registers 0-87 with FC04 as 44 big-endian floats, and coils 0-9 with FC01 for alarm states.",
  "minimum_registers": [
   {
    "table": "input_register",
    "address": 0,
    "why": "Frequency"
   },
   {
    "table": "input_register",
    "address": 4,
    "why": "L1-N voltage"
   },
   {
    "table": "input_register",
    "address": 6,
    "why": "L1 current"
   },
   {
    "table": "input_register",
    "address": 80,
    "why": "Total active power"
   },
   {
    "table": "input_register",
    "address": 74,
    "why": "Active energy"
   },
   {
    "table": "input_register",
    "address": 86,
    "why": "Power factor"
   },
   {
    "table": "coil",
    "address": 0,
    "why": "Alarm 1"
   }
  ],
  "enable": "Not described on the source page.",
  "watchdog": null,
  "quirks": [
   "Readings follow the configured display unit (V vs kV, kVA etc.).",
   "Floats are high word first."
  ],
  "setup": [
   "Set address and serial settings on the meter; they are not listed in the register map."
  ],
  "gotchas": [
   "The table spells parameter 39 'Reative Energy'; it is reactive energy."
  ]
 },
 "page": "https://easymodbus.com/modbus-register-maps/trumeter/apm-power",
 "address_note": "address = 0-based Modbus wire (PDU) address; documented = as printed in the source.",
 "note": "Re-typed from the manufacturer's public documentation (see source) and verified against it. Registers vary by firmware and options; verify against the live device before writing."
}