 "manufacturer": "Unipi Technology",
 "manufacturer_slug": "unipi-technology",
 "model": "Unipi Extension xG18 1-Wire temperature gateway",
 "model_slug": "extension-xg18",
 "short_model": "Extension xG18",
 "aliases": [
  "Unipi Extension xG18",
  "xG18"
 ],
 "equipment_type": "Sensor (1-Wire temperature gateway)",
 "applies_to": "Unipi Extension xG18 RS-485 module per the Unipi Extension xG18 Modbus map v1.1.",
 "summary": "The Unipi Extension xG18 is an RS-485 Modbus RTU gateway for up to eight Unipi 1-Wire temperature sensors, one per channel. The map gives each channel's temperature in hundredths of a degree, a validity bit word, measuring intervals, the master watchdog and RS-485 configuration.",
 "transport": [
  "RTU"
 ],
 "defaults": {
  "unit_id": 15,
  "baud": 19200,
  "parity": "None",
  "data_bits": 8,
  "stop_bits": 1,
  "tcp_port": null
 },
 "addressing": {
  "convention": "0-based",
  "note": "The map lists each register in decimal and hex starting at 0; the number is the wire address."
 },
 "default_word_order": "CDAB",
 "firmware": null,
 "source": {
  "title": "Extension xG18 Modbus map",
  "doc_number": "v1.1",
  "revision_date": null,
  "url": "https://kb.unipi.technology/_media/files:products:extensions:unipi-extension-xg18-modbus-map-v1.0.pdf",
  "pages": "holding registers, coils and description sheets"
 },
 "notes": [
  "Word order: the description sheet states 16-bit values are big endian (AB) and 32-bit values are mid-little endian (CDAB, low word first).",
  "Registers marked Reserved - Do Not Use are left out.",
  "Baud codes for the RS-485 configuration register: 11 = 2400, 12 = 4800, 13 = 9600, 14 = 19200, 15 = 38400, 4097 = 57600, 4098 = 115200 bps.",
  "The PDF file name says v1.0 but the sheet itself is marked v1.1.",
  "Temperature scaling (x0.01 °C) comes from the default-values table, which shows the power-up value -32768 as -327.68 °C; a validity bit of 0 means an unconnected or faulty sensor."
 ],
 "registers": [
  {
   "table": "coil",
   "address": 1000,
   "documented": "0x03E8",
   "name": "MWD reset indication",
   "description": "Set when the master watchdog has reset the module.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "coil",
   "address": 1002,
   "documented": "0x03EA",
   "name": "Reset group MCU",
   "description": "Write 1 to reset the module processor.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "coil",
   "address": 1003,
   "documented": "0x03EB",
   "name": "Save current configuration and use on startup",
   "description": "Write 1 to store the current settings as power-up defaults.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 0,
   "documented": "0x0000",
   "name": "Group MasterWatchDog (MWD) Status",
   "description": "",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": {
    "0": "MWD Enable",
    "1": "MWD Reboot Detected"
   }
  },
  {
   "table": "holding_register",
   "address": 1,
   "documented": "0x0001",
   "name": "Temperature CH1",
   "description": "1-Wire temperature in 0.01 °C; reads -32768 by default (no reading).",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 2,
   "documented": "0x0002",
   "name": "Temperature CH2",
   "description": "1-Wire temperature in 0.01 °C; reads -32768 by default (no reading).",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 3,
   "documented": "0x0003",
   "name": "Temperature CH3",
   "description": "1-Wire temperature in 0.01 °C; reads -32768 by default (no reading).",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 4,
   "documented": "0x0004",
   "name": "Temperature CH4",
   "description": "1-Wire temperature in 0.01 °C; reads -32768 by default (no reading).",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 5,
   "documented": "0x0005",
   "name": "Temperature CH5",
   "description": "1-Wire temperature in 0.01 °C; reads -32768 by default (no reading).",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 6,
   "documented": "0x0006",
   "name": "Temperature CH6",
   "description": "1-Wire temperature in 0.01 °C; reads -32768 by default (no reading).",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 7,
   "documented": "0x0007",
   "name": "Temperature CH7",
   "description": "1-Wire temperature in 0.01 °C; reads -32768 by default (no reading).",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 8,
   "documented": "0x0008",
   "name": "Temperature CH8",
   "description": "1-Wire temperature in 0.01 °C; reads -32768 by default (no reading).",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 9,
   "documented": "0x0009",
   "name": "Temperature validity",
   "description": "",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": {
    "0": "CH1",
    "1": "CH2",
    "2": "CH3",
    "3": "CH4",
    "4": "CH5",
    "5": "CH6",
    "6": "CH7",
    "7": "CH8"
   }
  },
  {
   "table": "holding_register",
   "address": 1000,
   "documented": "0x03E8",
   "name": "Firmware Version",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 1001,
   "documented": "0x03E9",
   "name": "Number of I/Os",
   "description": "Packed counts: bits 0-7 DOs, bits 8-15 DIs.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 1002,
   "documented": "0x03EA",
   "name": "Number of peripherals",
   "description": "Packed counts: bits 0-3 RS485 lines, bits 4-7 AOs, bits 8-15 AIs.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 1003,
   "documented": "0x03EB",
   "name": "Firmware ID",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 1004,
   "documented": "0x03EC",
   "name": "Hardware ID",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 1005,
   "documented": "0x03ED",
   "name": "PCB Serial Number",
   "description": "",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 1008,
   "documented": "0x03F0",
   "name": "MasterWatchDog (MWD) Timeout (ms)",
   "description": "Master watchdog timeout; default 5000 ms.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "ms",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 1009,
   "documented": "0x03F1",
   "name": "VRef of MCU",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 1010,
   "documented": "0x03F2",
   "name": "Measuring interval CH1 (seconds)",
   "description": "Measurement interval for this channel (default 2 s).",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "s",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 1011,
   "documented": "0x03F3",
   "name": "Measuring interval CH2 (seconds)",
   "description": "Measurement interval for this channel (default 2 s).",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "s",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 1012,
   "documented": "0x03F4",
   "name": "Measuring interval CH3 (seconds)",
   "description": "Measurement interval for this channel (default 2 s).",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "s",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 1013,
   "documented": "0x03F5",
   "name": "Measuring interval CH4 (seconds)",
   "description": "Measurement interval for this channel (default 2 s).",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "s",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 1014,
   "documented": "0x03F6",
   "name": "Measuring interval CH5 (seconds)",
   "description": "Measurement interval for this channel (default 2 s).",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "s",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 1015,
   "documented": "0x03F7",
   "name": "Measuring interval CH6 (seconds)",
   "description": "Measurement interval for this channel (default 2 s).",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "s",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 1016,
   "documented": "0x03F8",
   "name": "Measuring interval CH7 (seconds)",
   "description": "Measurement interval for this channel (default 2 s).",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "s",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 1017,
   "documented": "0x03F9",
   "name": "Measuring interval CH8 (seconds)",
   "description": "Measurement interval for this channel (default 2 s).",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "s",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 1018,
   "documented": "0x03FA",
   "name": "RS485 Configuration - see Description sheet",
   "description": "Bits 0-12 baud code, bit 13 parity on, bit 14 odd parity; default 14 (19200 8N1).",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 1019,
   "documented": "0x03FB",
   "name": "Modbus Address Configuration (1-254)",
   "description": "Modbus RTU slave address (default 15).",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null
  }
 ],
 "integration": {
  "summary": "Read temperatures CH1-CH8 at registers 1-8 (signed, x0.01 °C) and check the validity bits at register 9 before trusting a value.",
  "minimum_registers": [
   {
    "table": "holding_register",
    "address": 1,
    "why": "Temperature CH1"
   },
   {
    "table": "holding_register",
    "address": 2,
    "why": "Temperature CH2"
   },
   {
    "table": "holding_register",
    "address": 9,
    "why": "Temperature validity bits"
   },
   {
    "table": "holding_register",
    "address": 1010,
    "why": "CH1 measuring interval"
   },
   {
    "table": "holding_register",
    "address": 1019,
    "why": "Modbus address"
   }
  ],
  "enable": "Modbus RTU is the native interface; nothing needs enabling. Factory settings are address 15, 19200 bps, 8N1.",
  "watchdog": "Master watchdog (MWD): enable it with bit 0 of register 0 and set the timeout in register 1008 (default 5000 ms). A watchdog reboot is flagged in bit 1 of register 0 and in coil 1000; the map does not describe the timeout behaviour further.",
  "quirks": [
   "32-bit values (here only the PCB serial number) are low word first (CDAB).",
   "Changes to RS-485 settings and other configuration need the Save configuration coil to survive a power cycle."
  ],
  "setup": [
   "Set the address register (1019) and the packed RS-485 configuration register (1018), then write 1 to the save coil (1003) so the settings are used on startup."
  ],
  "gotchas": []
 },
 "page": "https://easymodbus.com/modbus-register-maps/unipi-technology/extension-xg18",
 "address_note": "address = 0-based Modbus wire (PDU) address; documented = as printed in the source.",
 "note": "Re-typed from the manufacturer's public documentation (see source) and verified against it. Registers vary by firmware and options; verify against the live device before writing."
}