 "manufacturer": "Unipi Technology",
 "manufacturer_slug": "unipi-technology",
 "model": "Unipi Extension xS11 I/O module",
 "model_slug": "extension-xs11",
 "short_model": "Extension xS11",
 "aliases": [
  "Unipi Extension xS11",
  "xS11"
 ],
 "equipment_type": "Sensor (remote I/O module)",
 "applies_to": "Unipi Extension xS11 RS-485 module per the Unipi Extension xS11 Modbus map v2.0.",
 "summary": "The Unipi Extension xS11 is an RS-485 Modbus RTU extension module with 12 digital inputs and 13 relay outputs. The map covers I/O state words, coils, per-input counters and debounce, DirectSwitch settings, the master watchdog and RS-485 configuration.",
 "transport": [
  "RTU"
 ],
 "defaults": {
  "unit_id": 15,
  "baud": 19200,
  "parity": "None",
  "data_bits": 8,
  "stop_bits": 1,
  "tcp_port": null
 },
 "addressing": {
  "convention": "0-based",
  "note": "The map lists each register in decimal and hex starting at 0; the number is the wire address."
 },
 "default_word_order": "CDAB",
 "firmware": null,
 "source": {
  "title": "Extension xS11 Modbus map",
  "doc_number": "v2.0",
  "revision_date": null,
  "url": "https://kb.unipi.technology/_media/files:products:extensions:unipi-extension-xs11-modbus-map-v2.0.pdf",
  "pages": "holding registers, coils and description sheets"
 },
 "notes": [
  "Word order: the description sheet states 16-bit values are big endian (AB) and 32-bit values are mid-little endian (CDAB, low word first).",
  "Registers marked Reserved - Do Not Use are left out.",
  "Baud codes for the RS-485 configuration register: 11 = 2400, 12 = 4800, 13 = 9600, 14 = 19200, 15 = 38400, 4097 = 57600, 4098 = 115200 bps.",
  "The register-0/1 bit words carry one bit per input/relay in order; the PDF lists the bit numbers."
 ],
 "registers": [
  {
   "table": "coil",
   "address": 0,
   "documented": "0x0000",
   "name": "Relay Output 1",
   "description": "Relay output state.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "coil",
   "address": 1,
   "documented": "0x0001",
   "name": "Relay Output 2",
   "description": "Relay output state.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "coil",
   "address": 2,
   "documented": "0x0002",
   "name": "Relay Output 3",
   "description": "Relay output state.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "coil",
   "address": 3,
   "documented": "0x0003",
   "name": "Relay Output 4",
   "description": "Relay output state.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "coil",
   "address": 4,
   "documented": "0x0004",
   "name": "Relay Output 5",
   "description": "Relay output state.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "coil",
   "address": 5,
   "documented": "0x0005",
   "name": "Relay Output 6",
   "description": "Relay output state.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "coil",
   "address": 6,
   "documented": "0x0006",
   "name": "Relay Output 7",
   "description": "Relay output state.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "coil",
   "address": 7,
   "documented": "0x0007",
   "name": "Relay Output 8",
   "description": "Relay output state.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "coil",
   "address": 8,
   "documented": "0x0008",
   "name": "Relay Output 9",
   "description": "Relay output state.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "coil",
   "address": 9,
   "documented": "0x0009",
   "name": "Relay Output 10",
   "description": "Relay output state.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "coil",
   "address": 10,
   "documented": "0x000A",
   "name": "Relay Output 11",
   "description": "Relay output state.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "coil",
   "address": 11,
   "documented": "0x000B",
   "name": "Relay Output 12",
   "description": "Relay output state.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "coil",
   "address": 12,
   "documented": "0x000C",
   "name": "Relay Output 13",
   "description": "Relay output state.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "coil",
   "address": 13,
   "documented": "0x000D",
   "name": "Digital Input 1",
   "description": "Digital input state (read with FC01).",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "coil",
   "address": 14,
   "documented": "0x000E",
   "name": "Digital Input 2",
   "description": "Digital input state (read with FC01).",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "coil",
   "address": 15,
   "documented": "0x000F",
   "name": "Digital Input 3",
   "description": "Digital input state (read with FC01).",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "coil",
   "address": 16,
   "documented": "0x0010",
   "name": "Digital Input 4",
   "description": "Digital input state (read with FC01).",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "coil",
   "address": 17,
   "documented": "0x0011",
   "name": "Digital Input 5",
   "description": "Digital input state (read with FC01).",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "coil",
   "address": 18,
   "documented": "0x0012",
   "name": "Digital Input 6",
   "description": "Digital input state (read with FC01).",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "coil",
   "address": 19,
   "documented": "0x0013",
   "name": "Digital Input 7",
   "description": "Digital input state (read with FC01).",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "coil",
   "address": 20,
   "documented": "0x0014",
   "name": "Digital Input 8",
   "description": "Digital input state (read with FC01).",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "coil",
   "address": 21,
   "documented": "0x0015",
   "name": "Digital Input 9",
   "description": "Digital input state (read with FC01).",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "coil",
   "address": 22,
   "documented": "0x0016",
   "name": "Digital Input 10",
   "description": "Digital input state (read with FC01).",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "coil",
   "address": 23,
   "documented": "0x0017",
   "name": "Digital Input 11",
   "description": "Digital input state (read with FC01).",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "coil",
   "address": 24,
   "documented": "0x0018",
   "name": "Digital Input 12",
   "description": "Digital input state (read with FC01).",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "coil",
   "address": 25,
   "documented": "0x0019",
   "name": "User Programmable LED 1",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "coil",
   "address": 26,
   "documented": "0x001A",
   "name": "User Programmable LED 2",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "coil",
   "address": 27,
   "documented": "0x001B",
   "name": "User Programmable LED 3",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "coil",
   "address": 1000,
   "documented": "0x03E8",
   "name": "MWD reset indication",
   "description": "Set when the master watchdog has reset the module.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "coil",
   "address": 1002,
   "documented": "0x03EA",
   "name": "Reset group MCU",
   "description": "Write 1 to reset the module processor.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "W",
   "values": null,
   "bits": null
  },
  {
   "table": "coil",
   "address": 1003,
   "documented": "0x03EB",
   "name": "Save current configuration and use on startup",
   "description": "Write 1 to store the current settings as power-up defaults.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "W",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 0,
   "documented": "0x0000",
   "name": "Digital Inputs",
   "description": "",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "0": "Digital Input 1",
    "1": "Digital Input 2",
    "2": "Digital Input 3",
    "3": "Digital Input 4",
    "4": "Digital Input 5",
    "5": "Digital Input 6",
    "6": "Digital Input 7",
    "7": "Digital Input 8",
    "8": "Digital Input 9",
    "9": "Digital Input 10",
    "10": "Digital Input 11",
    "11": "Digital Input 12"
   }
  },
  {
   "table": "holding_register",
   "address": 1,
   "documented": "0x0001",
   "name": "Relay Outputs",
   "description": "",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": {
    "0": "Relay Output 1",
    "1": "Relay Output 2",
    "2": "Relay Output 3",
    "3": "Relay Output 4",
    "4": "Relay Output 5",
    "5": "Relay Output 6",
    "6": "Relay Output 7",
    "7": "Relay Output 8",
    "8": "Relay Output 9",
    "9": "Relay Output 10",
    "10": "Relay Output 11",
    "11": "Relay Output 12",
    "12": "Relay Output 13"
   }
  },
  {
   "table": "holding_register",
   "address": 2,
   "documented": "0x0002",
   "name": "Group MasterWatchDog (MWD) Status",
   "description": "",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": {
    "0": "MWD Enable",
    "1": "MWD Reboot Detected"
   }
  },
  {
   "table": "holding_register",
   "address": 3,
   "documented": "0x0003",
   "name": "Counter of Digital Input 1",
   "description": "Pulse counter for this input; writable to preset.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 5,
   "documented": "0x0005",
   "name": "Counter of Digital Input 2",
   "description": "Pulse counter for this input; writable to preset.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 7,
   "documented": "0x0007",
   "name": "Counter of Digital Input 3",
   "description": "Pulse counter for this input; writable to preset.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 9,
   "documented": "0x0009",
   "name": "Counter of Digital Input 4",
   "description": "Pulse counter for this input; writable to preset.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 11,
   "documented": "0x000B",
   "name": "Counter of Digital Input 5",
   "description": "Pulse counter for this input; writable to preset.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 13,
   "documented": "0x000D",
   "name": "Counter of Digital Input 6",
   "description": "Pulse counter for this input; writable to preset.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 15,
   "documented": "0x000F",
   "name": "Counter of Digital Input 7",
   "description": "Pulse counter for this input; writable to preset.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 17,
   "documented": "0x0011",
   "name": "Counter of Digital Input 8",
   "description": "Pulse counter for this input; writable to preset.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 19,
   "documented": "0x0013",
   "name": "Counter of Digital Input 9",
   "description": "Pulse counter for this input; writable to preset.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 21,
   "documented": "0x0015",
   "name": "Counter of Digital Input 10",
   "description": "Pulse counter for this input; writable to preset.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 23,
   "documented": "0x0017",
   "name": "Counter of Digital Input 11",
   "description": "Pulse counter for this input; writable to preset.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 25,
   "documented": "0x0019",
   "name": "Counter of Digital Input 12",
   "description": "Pulse counter for this input; writable to preset.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 31,
   "documented": "0x001F",
   "name": "User-programmable LED states",
   "description": "",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": {
    "0": "User LED 1",
    "1": "User LED 2",
    "2": "User LED 3"
   }
  },
  {
   "table": "holding_register",
   "address": 32,
   "documented": "0x0020",
   "name": "Synchronised Relay Outputs",
   "description": "",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": {
    "0": "Synchronised RO 1",
    "1": "Synchronised RO 2",
    "2": "Synchronised RO 3",
    "3": "Synchronised RO 4",
    "4": "Synchronised RO 5",
    "5": "Synchronised RO 6",
    "6": "Synchronised RO 7",
    "7": "Synchronised RO 8",
    "8": "Synchronised RO 9",
    "9": "Synchronised RO 10",
    "10": "Synchronised RO 11",
    "11": "Synchronised RO 12",
    "12": "Synchronised RO 13"
   }
  },
  {
   "table": "holding_register",
   "address": 33,
   "documented": "0x0021",
   "name": "Synchronised Relay Output Locks",
   "description": "",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": {
    "0": "Synchronised RO Lock 1",
    "1": "Synchronised RO Lock 2",
    "2": "Synchronised RO Lock 3",
    "3": "Synchronised RO Lock 4",
    "4": "Synchronised RO Lock 5",
    "5": "Synchronised RO Lock 6",
    "6": "Synchronised RO Lock 7",
    "7": "Synchronised RO Lock 8",
    "8": "Synchronised RO Lock 9",
    "9": "Synchronised RO Lock 10",
    "10": "Synchronised RO Lock 11",
    "11": "Synchronised RO Lock 12",
    "12": "Synchronised RO Lock 13"
   }
  },
  {
   "table": "holding_register",
   "address": 1000,
   "documented": "0x03E8",
   "name": "Firmware Version",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 1001,
   "documented": "0x03E9",
   "name": "Number of I/Os",
   "description": "Packed counts: bits 0-7 DOs, bits 8-15 DIs.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 1002,
   "documented": "0x03EA",
   "name": "Number of peripherals",
   "description": "Packed counts: bits 0-3 RS485 lines, bits 4-7 AOs, bits 8-15 AIs.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 1003,
   "documented": "0x03EB",
   "name": "Firmware ID",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 1004,
   "documented": "0x03EC",
   "name": "Hardware ID",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 1005,
   "documented": "0x03ED",
   "name": "PCB Serial Number",
   "description": "",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 1008,
   "documented": "0x03F0",
   "name": "MasterWatchDog (MWD) Timeout (in 1ms)",
   "description": "Master watchdog timeout; default 5000 ms.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "ms",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 1009,
   "documented": "0x03F1",
   "name": "VRef of MCU",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 1010,
   "documented": "0x03F2",
   "name": "Debounce time (in 100us) for DI 1",
   "description": "Input debounce time in 100 us steps.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "ms",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 1011,
   "documented": "0x03F3",
   "name": "Debounce time (in 100us) for DI 2",
   "description": "Input debounce time in 100 us steps.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "ms",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 1012,
   "documented": "0x03F4",
   "name": "Debounce time (in 100us) for DI 3",
   "description": "Input debounce time in 100 us steps.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "ms",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 1013,
   "documented": "0x03F5",
   "name": "Debounce time (in 100us) for DI 4",
   "description": "Input debounce time in 100 us steps.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "ms",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 1014,
   "documented": "0x03F6",
   "name": "Debounce time (in 100us) for DI 5",
   "description": "Input debounce time in 100 us steps.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "ms",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 1015,
   "documented": "0x03F7",
   "name": "Debounce time (in 100us) for DI 6",
   "description": "Input debounce time in 100 us steps.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "ms",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 1016,
   "documented": "0x03F8",
   "name": "Debounce time (in 100us) for DI 7",
   "description": "Input debounce time in 100 us steps.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "ms",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 1017,
   "documented": "0x03F9",
   "name": "Debounce time (in 100us) for DI 8",
   "description": "Input debounce time in 100 us steps.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "ms",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 1018,
   "documented": "0x03FA",
   "name": "Debounce time (in 100us) for DI 9",
   "description": "Input debounce time in 100 us steps.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "ms",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 1019,
   "documented": "0x03FB",
   "name": "Debounce time (in 100us) for DI 10",
   "description": "Input debounce time in 100 us steps.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "ms",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 1020,
   "documented": "0x03FC",
   "name": "Debounce time (in 100us) for DI 11",
   "description": "Input debounce time in 100 us steps.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "ms",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 1021,
   "documented": "0x03FD",
   "name": "Debounce time (in 100us) for DI 12",
   "description": "Input debounce time in 100 us steps.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "ms",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 1022,
   "documented": "0x03FE",
   "name": "Enable DirectSwitch functionality",
   "description": "",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": {
    "0": "Enable DirectSwitch on DI 1",
    "1": "Enable DirectSwitch on DI 2",
    "2": "Enable DirectSwitch on DI 3",
    "3": "Enable DirectSwitch on DI 4",
    "4": "Enable DirectSwitch on DI 5",
    "5": "Enable DirectSwitch on DI 6",
    "6": "Enable DirectSwitch on DI 7",
    "7": "Enable DirectSwitch on DI 8",
    "8": "Enable DirectSwitch on DI 9",
    "9": "Enable DirectSwitch on DI 10",
    "10": "Enable DirectSwitch on DI 11",
    "11": "Enable DirectSwitch on DI 12"
   }
  },
  {
   "table": "holding_register",
   "address": 1023,
   "documented": "0x03FF",
   "name": "Invert DirectSwitch Polarity",
   "description": "",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": {
    "0": "Invert DirectSwitch Polarity on DI 1",
    "1": "Invert DirectSwitch Polarity on DI 2",
    "2": "Invert DirectSwitch Polarity on DI 3",
    "3": "Invert DirectSwitch Polarity on DI 4",
    "4": "Invert DirectSwitch Polarity on DI 5",
    "5": "Invert DirectSwitch Polarity on DI 6",
    "6": "Invert DirectSwitch Polarity on DI 7",
    "7": "Invert DirectSwitch Polarity on DI 8",
    "8": "Invert DirectSwitch Polarity on DI 9",
    "9": "Invert DirectSwitch Polarity on DI 10",
    "10": "Invert DirectSwitch Polarity on DI 11",
    "11": "Invert DirectSwitch Polarity on DI 12"
   }
  },
  {
   "table": "holding_register",
   "address": 1024,
   "documented": "0x0400",
   "name": "Enabled DirectSwitch Toggle",
   "description": "",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": {
    "0": "Enable DirectSwitch Toggle on DI 1",
    "1": "Enable DirectSwitch Toggle on DI 2",
    "2": "Enable DirectSwitch Toggle on DI 3",
    "3": "Enable DirectSwitch Toggle on DI 4",
    "4": "Enable DirectSwitch Toggle on DI 5",
    "5": "Enable DirectSwitch Toggle on DI 6",
    "6": "Enable DirectSwitch Toggle on DI 7",
    "7": "Enable DirectSwitch Toggle on DI 8",
    "8": "Enable DirectSwitch Toggle on DI 9",
    "9": "Enable DirectSwitch Toggle on DI 10",
    "10": "Enable DirectSwitch Toggle on DI 11",
    "11": "Enable DirectSwitch Toggle on DI 12"
   }
  },
  {
   "table": "holding_register",
   "address": 1027,
   "documented": "0x0403",
   "name": "RS485 Configuration - see Description sheet",
   "description": "Bits 0-12 baud code, bit 13 parity on, bit 14 odd parity; default 14 (19200 8N1).",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 1028,
   "documented": "0x0404",
   "name": "Modbus Address Configuration (1-254)",
   "description": "Modbus RTU slave address (default 15).",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null
  }
 ],
 "integration": {
  "summary": "Read inputs and relays as bit words at registers 0 and 1, or switch relays with FC05 on coils 0-12; inputs are coils 13-24.",
  "minimum_registers": [
   {
    "table": "holding_register",
    "address": 0,
    "why": "Digital input states"
   },
   {
    "table": "holding_register",
    "address": 1,
    "why": "Relay output states"
   },
   {
    "table": "coil",
    "address": 0,
    "why": "Relay 1"
   },
   {
    "table": "coil",
    "address": 13,
    "why": "Digital input 1"
   },
   {
    "table": "holding_register",
    "address": 3,
    "why": "DI 1 counter"
   }
  ],
  "enable": "Modbus RTU is the native interface; nothing needs enabling. Factory settings are address 15, 19200 bps, 8N1.",
  "watchdog": "Master watchdog (MWD): enable it with the MWD Enable bit of the MWD status register and set the timeout in register 1008 (default 5000 ms). A watchdog reboot is flagged by the MWD Reboot Detected bit and coil 1000; the map does not describe the timeout behaviour further.",
  "quirks": [
   "32-bit values (counters and the PCB serial number) are low word first (CDAB).",
   "Changes to RS-485 settings and other configuration need the Save configuration coil to survive a power cycle."
  ],
  "setup": [
   "Set the address register (1028) and the packed RS-485 configuration register (1027), then write 1 to the save coil (1003) so the settings are used on startup."
  ],
  "gotchas": []
 },
 "page": "https://easymodbus.com/modbus-register-maps/unipi-technology/extension-xs11",
 "address_note": "address = 0-based Modbus wire (PDU) address; documented = as printed in the source.",
 "note": "Re-typed from the manufacturer's public documentation (see source) and verified against it. Registers vary by firmware and options; verify against the live device before writing."
}