 "manufacturer": "Unipi Technology",
 "manufacturer_slug": "unipi-technology",
 "model": "MM-OT101 Modbus / OpenTherm gateway",
 "model_slug": "mm-ot101",
 "short_model": "MM-OT101",
 "aliases": [
  "MM-OT101",
  "MM-OT1010",
  "Unipi OpenTherm gateway"
 ],
 "equipment_type": "Boiler gateway (OpenTherm to Modbus RTU)",
 "applies_to": "Unipi MM-OT101 DIN-rail gateway between Modbus RTU (RS-485) and OpenTherm/Plus boilers and thermostats, per its technical documentation.",
 "summary": "The MM-OT101 sits between an OpenTherm boiler and its thermostat (monitor mode) or replaces the thermostat (controller mode) and exposes the OpenTherm data on Modbus RTU. Each OpenTherm message ID maps straight to the register with the same number. This map covers the status flags, setpoints, temperatures, modulation, pressure, counters and remote parameters, the gateway's line settings and timing statistics, and the two mode coils.",
 "transport": [
  "RTU"
 ],
 "defaults": {
  "unit_id": 1,
  "baud": 19200,
  "parity": "Even",
  "data_bits": 8,
  "stop_bits": null,
  "tcp_port": null
 },
 "addressing": {
  "convention": "0-based",
  "note": "Register numbers equal OpenTherm message IDs (0-127) and are sent unchanged; register 0 (status flags) exists, so the numbering is 0-based. Gateway registers 1000+ and coils 0/1 follow the same rule."
 },
 "default_word_order": null,
 "firmware": null,
 "source": {
  "title": "Technical documentation - Communication gateway with Modbus and Opentherm MM-OT101",
  "doc_number": null,
  "revision_date": null,
  "url": "https://kb.unipi.technology/_media/files:products:extensions_gateyways:mm-ot101:mm-ot101-technical_manual_en.pdf",
  "pages": "p. 4 (modes, DIP switches), p. 5 (functions, mapping), pp. 5-9 (registers and coils)"
 },
 "notes": [
  "OpenTherm f8.8 values are signed 16-bit numbers divided by 256 (the manual's example: 1.3 is stored as 333).",
  "Registers that hold two 8-bit OpenTherm fields (flag8/u8, u8/u8, s8 pairs) are listed as one UINT16; split them into high and low byte yourself. The manual does not say which byte holds which field for every pair, so check against the OpenTherm specification.",
  "Left out: the 32-bit statistics counters (2004-2018 and 2104-2118), because the manual does not state their word order.",
  "In monitor mode, registers 0-127 hold the last value seen passing between boiler and thermostat; messages that never passed read 0. Unmapped registers and coils also read 0.",
  "The manual names separate read functions (a single-register read goes straight to the boiler in controller mode, a multi-register read returns the memory map) but gives no function-code numbers; registers are listed here as holding registers.",
  "Statistics units (bit times) are not stated.",
  "Register 0: the minimum-configuration table puts the master status flags (bit 0 CH enable, bit 1 DHW enable, bit 2 cooling enable, bit 3 OTC active, bit 4 CH2) in the high byte and the slave flags (bit 0 fault, 1 CH mode, 2 DHW mode, 3 flame, 4 cooling, 5 CH2 mode, 6 diagnostic) in the low byte, but the register map table prints the register as LB(flag8)/HB(flag8) for master and slave. Because the byte order is not settled, the bits are not mapped here; confirm on site."
 ],
 "registers": [
  {
   "table": "coil",
   "address": 0,
   "documented": "0",
   "name": "Monitor mode active",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Controller mode",
    "1": "Monitor mode"
   },
   "bits": null
  },
  {
   "table": "coil",
   "address": 1,
   "documented": "1",
   "name": "Active scan",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Send on each register write",
    "1": "Cycle all mapped messages to the boiler"
   },
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 0,
   "documented": "0",
   "name": "Master / slave status flags",
   "description": "Master and slave status flag bytes; byte order unclear in the manual (see notes).",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 1,
   "documented": "1",
   "name": "Control setpoint (CH water)",
   "description": "f8.8: signed, divide by 256. Required in controller mode.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.00390625,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "°C",
   "access": "W",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 2,
   "documented": "2",
   "name": "Master configuration flags / member ID",
   "description": "High/low byte pair (flag8 / u8).",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "W",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 3,
   "documented": "3",
   "name": "Slave configuration flags / member ID",
   "description": "High/low byte pair (flag8 / u8).",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 4,
   "documented": "4",
   "name": "Remote command",
   "description": "Byte pair (u8 / u8).",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "W",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 5,
   "documented": "5",
   "name": "Application fault flags / OEM fault code",
   "description": "Fault flag byte plus OEM fault code.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 6,
   "documented": "6",
   "name": "Remote parameter transfer-enable / read-write flags",
   "description": "Two flag bytes.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 7,
   "documented": "7",
   "name": "Cooling control signal",
   "description": "f8.8: signed, divide by 256.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.00390625,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "%",
   "access": "W",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 8,
   "documented": "8",
   "name": "Control setpoint CH2",
   "description": "f8.8: signed, divide by 256.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.00390625,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "°C",
   "access": "W",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 9,
   "documented": "9",
   "name": "Remote override room setpoint",
   "description": "f8.8: signed, divide by 256.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.00390625,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 10,
   "documented": "10",
   "name": "Number of transparent slave parameters",
   "description": "u8.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 11,
   "documented": "11",
   "name": "Transparent slave parameter index / value",
   "description": "Index byte and value byte.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 12,
   "documented": "12",
   "name": "Fault history buffer size",
   "description": "u8.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 13,
   "documented": "13",
   "name": "Fault history entry index / value",
   "description": "Index byte and value byte.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 14,
   "documented": "14",
   "name": "Max relative modulation setting",
   "description": "f8.8: signed, divide by 256.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.00390625,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "%",
   "access": "W",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 15,
   "documented": "15",
   "name": "Max boiler capacity (kW) / min modulation (%)",
   "description": "Two u8 bytes.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 16,
   "documented": "16",
   "name": "Room setpoint",
   "description": "f8.8: signed, divide by 256.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.00390625,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "°C",
   "access": "W",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 17,
   "documented": "17",
   "name": "Relative modulation level",
   "description": "f8.8: signed, divide by 256.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.00390625,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 18,
   "documented": "18",
   "name": "CH water pressure",
   "description": "f8.8: signed, divide by 256.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.00390625,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "bar",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 19,
   "documented": "19",
   "name": "DHW flow rate",
   "description": "f8.8: signed, divide by 256.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.00390625,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "l/min",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 20,
   "documented": "20",
   "name": "Day of week and time of day",
   "description": "OpenTherm packed u8 bytes.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 21,
   "documented": "21",
   "name": "Calendar date",
   "description": "Two u8 bytes.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 22,
   "documented": "22",
   "name": "Calendar year",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 23,
   "documented": "23",
   "name": "Room setpoint CH2",
   "description": "f8.8: signed, divide by 256.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.00390625,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "°C",
   "access": "W",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 24,
   "documented": "24",
   "name": "Room temperature",
   "description": "f8.8: signed, divide by 256. Sent by the thermostat/controller.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.00390625,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "°C",
   "access": "W",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 25,
   "documented": "25",
   "name": "Boiler flow water temperature",
   "description": "f8.8: signed, divide by 256.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.00390625,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 26,
   "documented": "26",
   "name": "DHW temperature",
   "description": "f8.8: signed, divide by 256.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.00390625,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 27,
   "documented": "27",
   "name": "Outside temperature",
   "description": "f8.8: signed, divide by 256.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.00390625,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 28,
   "documented": "28",
   "name": "Return water temperature",
   "description": "f8.8: signed, divide by 256.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.00390625,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 29,
   "documented": "29",
   "name": "Solar storage temperature",
   "description": "f8.8: signed, divide by 256.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.00390625,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 30,
   "documented": "30",
   "name": "Solar collector temperature",
   "description": "f8.8: signed, divide by 256.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.00390625,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 31,
   "documented": "31",
   "name": "CH2 flow water temperature",
   "description": "f8.8: signed, divide by 256.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.00390625,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 32,
   "documented": "32",
   "name": "DHW temperature 2",
   "description": "f8.8: signed, divide by 256.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.00390625,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 33,
   "documented": "33",
   "name": "Boiler exhaust temperature",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 48,
   "documented": "48",
   "name": "DHW setpoint bounds",
   "description": "Upper / lower bound bytes, s8, °C.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 49,
   "documented": "49",
   "name": "Max CH setpoint bounds",
   "description": "Upper / lower bound bytes, s8, °C.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 50,
   "documented": "50",
   "name": "OTC heat curve ratio bounds",
   "description": "Upper / lower bound bytes, s8.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 56,
   "documented": "56",
   "name": "DHW setpoint (remote parameter 1)",
   "description": "f8.8: signed, divide by 256.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.00390625,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "°C",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 57,
   "documented": "57",
   "name": "Max CH water setpoint (remote parameter 2)",
   "description": "f8.8: signed, divide by 256.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.00390625,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "°C",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 58,
   "documented": "58",
   "name": "OTC heat curve ratio (remote parameter 3)",
   "description": "f8.8: signed, divide by 256.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.00390625,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 100,
   "documented": "100",
   "name": "Remote override function flags",
   "description": "flag8: manual / program change handling.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 115,
   "documented": "115",
   "name": "OEM diagnostic / service code",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 116,
   "documented": "116",
   "name": "Burner starts",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 117,
   "documented": "117",
   "name": "CH pump starts",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 118,
   "documented": "118",
   "name": "DHW pump/valve starts",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 119,
   "documented": "119",
   "name": "Burner starts in DHW mode",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 120,
   "documented": "120",
   "name": "Burner operating hours",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "h",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 121,
   "documented": "121",
   "name": "CH pump running hours",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "h",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 122,
   "documented": "122",
   "name": "DHW pump/valve running hours",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "h",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 123,
   "documented": "123",
   "name": "Burner hours in DHW mode",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "h",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 124,
   "documented": "124",
   "name": "OpenTherm version, master",
   "description": "f8.8: signed, divide by 256.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.00390625,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "W",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 125,
   "documented": "125",
   "name": "OpenTherm version, slave",
   "description": "f8.8: signed, divide by 256.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.00390625,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 126,
   "documented": "126",
   "name": "Master product version and type",
   "description": "Two u8 bytes.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "W",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 127,
   "documented": "127",
   "name": "Slave product version and type",
   "description": "Two u8 bytes.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 1000,
   "documented": "1000",
   "name": "OT line logical 0 current",
   "description": "Gateway setting (memory only).",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "mA",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 1001,
   "documented": "1001",
   "name": "OT line logical 1 current",
   "description": "Gateway setting (memory only).",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "mA",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 1002,
   "documented": "1002",
   "name": "Gap before reply to thermostat",
   "description": "Gateway setting (memory only).",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "µs",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 1003,
   "documented": "1003",
   "name": "Boiler transaction timeout",
   "description": "Gateway setting (memory only).",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "ms",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 1004,
   "documented": "1004",
   "name": "Sanity gap before reply",
   "description": "Gateway setting (memory only).",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "ms",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 2000,
   "documented": "2000",
   "name": "Max time of 1 bit (boiler line)",
   "description": "OpenTherm line timing statistic; unit not stated.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 2001,
   "documented": "2001",
   "name": "Min time of 1 bit (boiler line)",
   "description": "OpenTherm line timing statistic; unit not stated.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 2002,
   "documented": "2002",
   "name": "Pulse time min (boiler line)",
   "description": "OpenTherm line timing statistic; unit not stated.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 2003,
   "documented": "2003",
   "name": "Pulse time threshold (boiler line)",
   "description": "OpenTherm line timing statistic; unit not stated.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 2020,
   "documented": "2020",
   "name": "Average long bit time (boiler line)",
   "description": "OpenTherm line timing statistic; unit not stated.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 2021,
   "documented": "2021",
   "name": "Min long bit time (boiler line)",
   "description": "OpenTherm line timing statistic; unit not stated.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 2022,
   "documented": "2022",
   "name": "Max long bit time (boiler line)",
   "description": "OpenTherm line timing statistic; unit not stated.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 2023,
   "documented": "2023",
   "name": "Average short bit time (boiler line)",
   "description": "OpenTherm line timing statistic; unit not stated.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 2024,
   "documented": "2024",
   "name": "Min short bit time (boiler line)",
   "description": "OpenTherm line timing statistic; unit not stated.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 2025,
   "documented": "2025",
   "name": "Max short bit time (boiler line)",
   "description": "OpenTherm line timing statistic; unit not stated.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 2026,
   "documented": "2026",
   "name": "Start bit min time (boiler line)",
   "description": "OpenTherm line timing statistic; unit not stated.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 2027,
   "documented": "2027",
   "name": "Start bit max time (boiler line)",
   "description": "OpenTherm line timing statistic; unit not stated.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 2100,
   "documented": "2100",
   "name": "Max time of 1 bit (boiler line, set 2)",
   "description": "OpenTherm line timing statistic; unit not stated.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 2101,
   "documented": "2101",
   "name": "Min time of 1 bit (boiler line, set 2)",
   "description": "OpenTherm line timing statistic; unit not stated.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 2102,
   "documented": "2102",
   "name": "Pulse time min (boiler line, set 2)",
   "description": "OpenTherm line timing statistic; unit not stated.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 2103,
   "documented": "2103",
   "name": "Pulse time threshold (boiler line, set 2)",
   "description": "OpenTherm line timing statistic; unit not stated.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 2120,
   "documented": "2120",
   "name": "Average long bit time (boiler line, set 2)",
   "description": "OpenTherm line timing statistic; unit not stated.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 2121,
   "documented": "2121",
   "name": "Min long bit time (boiler line, set 2)",
   "description": "OpenTherm line timing statistic; unit not stated.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 2122,
   "documented": "2122",
   "name": "Max long bit time (boiler line, set 2)",
   "description": "OpenTherm line timing statistic; unit not stated.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 2123,
   "documented": "2123",
   "name": "Average short bit time (boiler line, set 2)",
   "description": "OpenTherm line timing statistic; unit not stated.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 2124,
   "documented": "2124",
   "name": "Min short bit time (boiler line, set 2)",
   "description": "OpenTherm line timing statistic; unit not stated.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 2125,
   "documented": "2125",
   "name": "Max short bit time (boiler line, set 2)",
   "description": "OpenTherm line timing statistic; unit not stated.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 2126,
   "documented": "2126",
   "name": "Start bit min time (boiler line, set 2)",
   "description": "OpenTherm line timing statistic; unit not stated.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 2127,
   "documented": "2127",
   "name": "Start bit max time (boiler line, set 2)",
   "description": "OpenTherm line timing statistic; unit not stated.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  }
 ],
 "integration": {
  "summary": "In controller mode, clear coil 0, set the CH/DHW enable flags in the master status byte of register 0 and write the control setpoint to register 1 (f8.8), one register per write, repeated periodically. Read boiler status and temperatures from registers 0, 17, 25, 26 and 28.",
  "minimum_registers": [
   {
    "table": "holding_register",
    "address": 0,
    "why": "Status flags (CH/DHW enable, flame, fault)"
   },
   {
    "table": "holding_register",
    "address": 1,
    "why": "Control setpoint"
   },
   {
    "table": "holding_register",
    "address": 17,
    "why": "Relative modulation level"
   },
   {
    "table": "holding_register",
    "address": 25,
    "why": "Boiler flow temperature"
   },
   {
    "table": "holding_register",
    "address": 28,
    "why": "Return water temperature"
   },
   {
    "table": "coil",
    "address": 0,
    "why": "Monitor / controller mode"
   }
  ],
  "enable": "Set address (1-7), baud (9600/19200) and parity with the internal DIP switch: switch 1 = baud (ON 19200), switch 2 = parity (ON even), switches 3-5 = address weights 4/2/1. The gateway starts in monitor mode after power-up.",
  "watchdog": null,
  "quirks": [
   "Registers 0-127 must be written one register at a time; multi-register writes work only for 1000 and up (memory only).",
   "f8.8 values: read as signed 16-bit and divide by 256.",
   "Direct reads to the boiler can take up to about 800 ms; set the master timeout accordingly."
  ],
  "setup": [
   "Default: address 1, 19200 baud, even parity.",
   "On some versions parity is fixed to even regardless of the switch.",
   "120-ohm termination is enabled with switch SW2."
  ],
  "gotchas": [
   "The gateway returns to monitor mode after power-up, so the controller must re-select controller mode.",
   "In controller mode the PLC must send commands to the boiler periodically."
  ]
 },
 "page": "https://easymodbus.com/modbus-register-maps/unipi-technology/mm-ot101",
 "address_note": "address = 0-based Modbus wire (PDU) address; documented = as printed in the source.",
 "note": "Re-typed from the manufacturer's public documentation (see source) and verified against it. Registers vary by firmware and options; verify against the live device before writing."
}