Danfoss VACON VACON 100 family (built-in Modbus RTU / Modbus TCP) Modbus register map

Updated 24 October 2026

Short answer

Danfoss VACON's general purpose and flow-application variable frequency drive family, with Modbus RTU on the RS-485 terminals and Modbus TCP/UDP on the Ethernet port as standard. Fieldbus process data sits at 2001-2011 (control word, speed reference, process data in) and 2101-2111 (status word, actual speed, eight monitoring values), and every application parameter or monitor can be read directly by its ID number. This map covers the process data, key monitoring IDs, control-place parameters and the Modbus RTU/TCP settings.

This page lists 78 Modbus registers for the Danfoss VACON VACON 100 family (built-in Modbus RTU / Modbus TCP) — 26 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Danfoss VACON’s own free documentation (linked below) and checked against it.

Manufacturer
Danfoss VACON
Model
VACON 100 family (built-in Modbus RTU / Modbus TCP)
Equipment type
Variable frequency drive
Registers
78 (26 writable)
Transport
Modbus RTU, Modbus TCP
Default unit ID
1
Default serial
9600 baud, 8E1
Documented addressing
1-based (subtract 1 for the wire address)
32-bit word order
ABCD high word first (big-endian)
Firmware
Application IDs per VACON 100 INDUSTRIAL software FW0072V037 (application guide DPD00927L)
Also known as
VACON 100 INDUSTRIAL, VACON 100 FLOW, VACON 100 HVAC, VACON 100 X, VACON0100
Source document
VACON 100 INDUSTRIAL / FLOW / HVAC / 100 X AC drives - Modbus TCP/UDP and Modbus RTU User Manual · DPD00156D · rev. 2016-11-30
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: Danfoss VACON VACON 100 family (built-in Modbus RTU / Modbus TCP)

Integration in brief

Enable Modbus RTU with ID 2208 = 1 (Modbus TCP is always on), set Remote control place ID 172 = 1, then write FB control word 2001 (1 = run) and FB speed reference 2003 (0-10000 = 0-100 % of min-max frequency) and poll 2101-2111 for status, actual speed, frequency, current and fault code. Every register number in the manual is 1-based: subtract 1 on the wire.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
HR 2000FB control wordBITMAP16FB control word: run, direction, fault resetRead/write
HR 2002FB speed referenceUINT16FB speed reference, 0.01 % of min-max rangeRead/write
HR 2100FB status wordBITMAP16FB status word: ready/run/fault/alarmRead
HR 2103Process data out 1 (output frequency)UINT16Output frequency, 0.01 HzRead
HR 44Motor current 1 decimalUINT16Motor current, 0.1 A (ID 45)Read
HR 2109Process data out 7 (DC link voltage)UINT16DC link voltageRead
HR 2110Process data out 8 (active fault code)UINT16Active fault codeRead
HR 171Remote control placeUINT16ID 172 remote control place (1 = fieldbus)Read/write

Enable Modbus control & writes

Modbus RTU: set P5.8.1.1 RS-485 protocol (ID 2208) = Modbus RTU, after which its settings appear under P5.8.3 (slave address ID 2320, baud ID 2378, parity ID 2379, stop bits ID 2380, time-out ID 2321). Modbus TCP/UDP is always enabled; set the IP mode and address under P5.9.1. For control set Remote control place P3.2.1 (ID 172) = Fieldbus control, Local/remote (ID 211) = Remote, and leave Fieldbus control reference selection (ID 122) = 3 Fieldbus. Control word bits 8/9 can also force fieldbus control and reference.

Communication loss & watchdog

RTU: ID 2321 communication time-out (seconds, default 10, 0 = off). TCP/UDP: ID 2448 time-out (seconds, default 10); a connection can also set its own timeout at register 40501. The reaction is ID 733 Response to fieldbus communication fault (default 3 = fault, stop per stop function); the fault is code 53 Fieldbus communication fault.

Byte order & addressing

Network setup

Watch out for

Danfoss VACON VACON 100 family (built-in Modbus RTU / Modbus TCP) Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

78 of 78 shown
Danfoss VACON VACON 100 family (built-in Modbus RTU / Modbus TCP) Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
CO0doc 0001Run/stop (control word bit 0)Modbus TCP/UDP only.BITRead/write
CO1doc 0002Direction (control word bit 1)Modbus TCP/UDP only.BITRead/write
CO2doc 0003Fault reset (control word bit 2)Modbus TCP/UDP only.BITRead/write
CO16doc 0017Reset operation days trip counterWrite 1 to clear. Modbus TCP/UDP only.BITWrite
CO17doc 0018Reset energy trip counterWrite 1 to clear. Modbus TCP/UDP only.BITWrite
DI0doc 10001Ready (status word bit 0)Modbus TCP/UDP only.BITRead
DI1doc 10002Run (status word bit 1)Modbus TCP/UDP only.BITRead
DI2doc 10003Direction (status word bit 2)Modbus TCP/UDP only.BITRead
DI3doc 10004Fault (status word bit 3)Modbus TCP/UDP only.BITRead
DI4doc 10005Alarm (status word bit 4)Modbus TCP/UDP only.BITRead
DI5doc 10006At reference (status word bit 5)Modbus TCP/UDP only.BITRead
DI6doc 10007Zero speed (status word bit 6)Modbus TCP/UDP only.BITRead
DI7doc 10008Flux ready (status word bit 7)Modbus TCP/UDP only.BITRead
HR0doc ID 1 (register 1)Output frequencyINT16× 0.01HzRead
HR1doc ID 2 (register 2)Motor speedINT16rpmRead
HR2doc ID 3 (register 3)Motor currentScale varies with drive size; use ID 45 for fixed 0.1 A.UINT16Read
HR3doc ID 4 (register 4)Motor torqueINT16× 0.1%Read
HR4doc ID 5 (register 5)Motor shaft powerINT16× 0.1%Read
HR5doc ID 6 (register 6)Motor voltageUINT16× 0.1VRead
HR6doc ID 7 (register 7)DC link voltageUINT16VRead
HR7doc ID 8 (register 8)Unit temperatureINT16× 0.1°CRead
HR8doc ID 9 (register 9)Motor temperatureINT16× 0.1%Read
HR17doc ID 18 (register 18)Torque referenceINT16× 0.1%Read
HR22doc ID 23 (register 23)PID1 outputINT16× 0.01%Read
HR23doc ID 24 (register 24)PID1 statusUINT16Read0 = Stopped; 1 = Running; 3 = Sleep mode; 4 = In dead band
HR24doc ID 25 (register 25)Frequency referenceINT16× 0.01HzRead
HR36doc ID 37 (register 37)Last active fault code53 = fieldbus communication fault.UINT16Read
HR42doc ID 43 (register 43)Drive status wordBit numbers as printed in the application guide.BITMAP16Readbit 1 = Ready; bit 2 = Run; bit 3 = Fault; bit 6 = Run enable; bit 7 = Alarm active; bit 10 = DC current in stop; bit 11 = DC brake active; bit 12 = Run request; bit 13 = Motor regulator active; bit 15 = Brake chopper active
HR44doc ID 45 (register 45)Motor current 1 decimalFixed 0.1 A resolution regardless of drive size.UINT16× 0.1ARead
HR58doc ID 59 (register 59)Analog input 1Slot A.1 by default.INT16× 0.01%Read
HR59doc ID 60 (register 60)Analog input 2Slot A.2 by default.INT16× 0.01%Read
HR73doc ID 74 (register 74)Last active alarm codeUINT16Read
HR76doc ID 77 (register 77)Motor regulator statusBITMAP16Readbit 0 = Current limit (motor); bit 1 = Current limit (generator); bit 2 = Torque limit (motor); bit 3 = Torque limit (generator); bit 4 = Overvoltage control; bit 5 = Undervoltage control; bit 6 = Power limit (motor); bit 7 = Power limit (generator)
HR77doc ID 78 (register 78)Ready statusConditions needed before the drive is ready.BITMAP16Readbit 0 = Run enable high; bit 1 = No fault active; bit 2 = Charge switch closed; bit 3 = DC voltage within limits; bit 4 = Power manager initialised; bit 5 = Power unit not blocking start; bit 6 = System software not blocking start
HR88doc ID 89 (register 89)Application status word 1BITMAP16Readbit 0 = Interlock 1; bit 1 = Interlock 2; bit 3 = Ramp 2 active; bit 4 = Mechanical brake control; bit 5 = I/O A control active; bit 6 = I/O B control active; bit 7 = Fieldbus control active; bit 8 = Local control active; bit 9 = PC control active; bit 10 = Preset frequencies active; bit 11 = Jogging active; bit 12 = Fire mode active; bit 13 = Motor preheat active; bit 14 = Quick stop active; bit 15 = Drive stopped from keypad
HR94doc ID 95 (register 95)Last active fault IDUINT16Read
HR102doc ID 103 (register 103)Acceleration time 10.1-300.0 s.UINT16× 0.1sRead/write
HR103doc ID 104 (register 104)Deceleration time 10.1-300.0 s.UINT16× 0.1sRead/write
HR121doc ID 122 (register 122)Fieldbus control reference selectionReference used in fieldbus control place (default 3).UINT16Read/write1 = Preset frequency 0; 2 = Keypad reference; 3 = Fieldbus; 4 = AI1; 5 = AI2; 6 = AI1+AI2; 7 = PID reference; 8 = Motor potentiometer; 9 = Joystick reference; 10 = Jogging reference; 11 = Block Out.1; 12 = Block Out.2; 13 = Block Out.3; 14 = Block Out.4; 15 = Block Out.5; 16 = Block Out.6; 17 = Block Out.7; 18 = Block Out.8; 19 = Block Out.9; 20 = Block Out.10
HR171doc ID 172 (register 172)Remote control placeSet 1 so the drive takes start/stop from fieldbus.UINT16Read/write0 = I/O control; 1 = Fieldbus control
HR210doc ID 211 (register 211)Local/remoteUINT16Read/write0 = Remote; 1 = Local
HR504doc ID 505 (register 505)Start functionUINT16Read/write0 = Ramping; 1 = Flying start
HR505doc ID 506 (register 506)Stop functionUINT16Read/write0 = Coasting; 1 = Ramping
HR732doc ID 733 (register 733)Response to fieldbus communication faultDefault 3.UINT16Read/write0 = No action; 1 = Alarm; 2 = Alarm + preset fault frequency; 3 = Fault (stop according to stop function); 4 = Fault (stop by coasting)
HR887doc ID 888 (register 888)FB sign of actualSign used for FB actual speed (2103).UINT16Read/write0 = Positive; 1 = Actual direction; 2 = Follow reference
HR1494doc ID 1495 (register 1495)Frequency reference sourceWhere the active frequency reference comes from.UINT16Read0 = PC; 1 = Preset freqs; 2 = Keypad reference; 3 = Fieldbus; 4 = AI1; 5 = AI2; 6 = AI1+AI2; 7 = PID controller; 8 = Motor potentiometer; 9 = Joystick; 10 = Jogging; 100 = Not defined; 101 = Alarm, preset freq; 102 = Auto-cleaning
HR2000doc 2001FB control wordLow 16 bits of the 32-bit fieldbus control word.BITMAP16Read/writebit 0 = Start/stop: 1 = run request, 0 = stop request; bit 1 = Direction: 0 = forward, 1 = reverse; bit 2 = Fault reset on rising edge 0->1 (faults, alarms, infos); bit 3 = Stop mode 1: 1 = override stop mode to coasting; bit 4 = Stop mode 2: 1 = override stop mode to ramping; bit 5 = Quick ramp time: 1 = shorter deceleration ramp (not on 100 HVAC); bit 6 = Freeze setpoint: 1 = ignore changes to FB speed reference; bit 7 = Setpoint to zero: 1 = fieldbus setpoint forced to 0 (not on 100 HVAC); bit 8 = Request fieldbus control: 1 = control place forced to fieldbus; bit 9 = Request fieldbus reference: 1 = reference source forced to fieldbus; bit 10 = Jogging 1 (not on 100 HVAC); bit 11 = Jogging 2 (not on 100 HVAC); bit 12 = Quick stop / emergency stop (not on 100 HVAC)
HR2001doc 2002FB general control wordApplication-specific bits; write 0 if unused.UINT16Read/write
HR2002doc 2003FB speed reference0-10000 = 0.00-100.00 % between min and max frequency.UINT16× 0.01%Read/write
HR2100doc 2101FB status wordLow 16 bits of the 32-bit fieldbus status word.BITMAP16Readbit 0 = Ready: drive ready to run; bit 1 = Run: motor running; bit 2 = Direction: 0 = clockwise, 1 = counterclockwise; bit 3 = Fault active; bit 4 = Alarm active; bit 5 = At reference speed; bit 6 = At zero speed; bit 7 = Flux ready (motor magnetized)
HR2101doc 2102FB general status wordApplication-specific (high half of the 32-bit status word).UINT16Read
HR2102doc 2103FB actual speed0.00-100.00 % between min and max frequency; sign per ID 888.INT16× 0.01%Read
HR2103doc 2104Process data out 1 (output frequency)Default ID 1; remap with P3.6.1 (ID 852).UINT16× 0.01HzRead
HR2104doc 2105Process data out 2 (motor speed)Default ID 2; remap with ID 853.UINT16rpmRead
HR2105doc 2106Process data out 3 (motor current)Default ID 3 (45 on 100 HVAC); scale varies by drive size.UINT16Read
HR2106doc 2107Process data out 4 (motor torque)Default ID 4; remap with ID 855.UINT16× 0.1%Read
HR2107doc 2108Process data out 5 (motor power)Default ID 5; remap with ID 856.UINT16× 0.1%Read
HR2108doc 2109Process data out 6 (motor voltage)Default ID 6; remap with ID 857.UINT16× 0.1VRead
HR2109doc 2110Process data out 7 (DC link voltage)Default ID 7; remap with ID 858.UINT16VRead
HR2110doc 2111Process data out 8 (active fault code)Default ID 37; remap with ID 859.UINT16Read
HR2150doc 2151-2152FB status word (32-bit)Full 32-bit status word incl. control place bits 29-31.UINT32ABCDReadbit 0 = Ready: drive ready to run; bit 1 = Run: motor running; bit 2 = Direction: 0 = clockwise, 1 = counterclockwise; bit 3 = Fault active; bit 4 = Alarm active; bit 5 = At reference speed; bit 6 = At zero speed; bit 7 = Flux ready (motor magnetized); bit 29 = Control place, read with bits 30-31: only bit 31 set = fieldbus, only bit 30 = keypad, bits 30+31 = PC tool, only bit 29 = I/O terminals; bit 30 = Control place (see bit 29); bit 31 = Control place (see bit 29)
HR2207doc ID 2208 (register 2208)RS-485 protocolMust be 1 for Modbus RTU.UINT16Read/write0 = No protocol; 1 = Modbus RTU; 2 = BACnet MSTP; 3 = N2
HR2319doc ID 2320 (register 2320)RTU slave address1-247, default 1.UINT16Read/write
HR2320doc ID 2321 (register 2321)RTU communication time-out0 = not used; default 10 s.UINT16sRead/write
HR2377doc ID 2378 (register 2378)RTU baud rateCoded selection; default code 6 = 9600 baud.UINT16Read/write
HR2378doc ID 2379 (register 2379)RTU parity typeUINT16Read/write0 = Even; 1 = Odd; 2 = None
HR2379doc ID 2380 (register 2380)RTU stop bitsUINT16Read/write1 = 1 stop bit; 2 = 1.5 stop bits; 3 = 2 stop bits
HR2380doc ID 2381 (register 2381)RTU fieldbus protocol statusUINT16Read0 = Init; 1 = Stopped; 2 = Operational; 3 = Faulted
HR2382doc ID 2383 (register 2383)RTU illegal functionsCount of exception 01h replies.UINT16Read
HR2383doc ID 2384 (register 2384)RTU illegal data addressesCount of exception 02h replies.UINT16Read
HR2384doc ID 2385 (register 2385)RTU illegal data valuesCount of exception 03h replies.UINT16Read
HR2388doc ID 2389 (register 2389)RTU last fault responseLast exception code sent.UINT16Read
HR2389doc ID 2390 (register 2390)RTU control word (monitor)Control word last received over RTU.UINT16Read
HR2390doc ID 2391 (register 2391)RTU status word (monitor)Status word currently sent over RTU.UINT16Read
HR2445doc ID 2446 (register 2446)TCP connection limit0-3 simultaneous Modbus TCP/UDP clients, default 3.UINT16Read/write
HR2446doc ID 2447 (register 2447)TCP unit identifier0-255, default 255; checked on TCP and UDP.UINT16Read/write
HR2447doc ID 2448 (register 2448)TCP communication time-out0 = not used; default 10 s.UINT16sRead/write
HR2448doc ID 2449 (register 2449)TCP fieldbus protocol statusUINT16Read1 = Stopped; 2 = Operational; 3 = Faulted

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the Danfoss VACON VACON 100 family (built-in Modbus RTU / Modbus TCP)

What Modbus registers does the Danfoss VACON VACON 100 family (built-in Modbus RTU / Modbus TCP) have?

This map lists 78 registers: 5 coils, 8 discrete inputs, 65 holding registers. 26 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the Danfoss VACON VACON 100 family (built-in Modbus RTU / Modbus TCP) Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers 1-based (subtract 1 for the wire address). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The manual states that addresses in Modbus messages start at zero and prints its register map 1-based: its write example sends starting address 07D0h (2000) for control word 2001, and its read example sends 0836h (2102) for register 2103. So subtract 1 from every printed number; application ID n is register n and wire address n-1 (ID 172 -> 171). Coils 0001-0018 are 1-based too (coil 1 = wire 0), and discrete inputs printed 10001-10008 are Modicon-style references for wire 0-7.

What byte order does the Danfoss VACON VACON 100 family (built-in Modbus RTU / Modbus TCP) use for 32-bit values?

Multi-register values in this map use ABCD (high word first (big-endian)). Set your client to this order for every 32/64-bit value in the table.

What are the minimum Modbus registers to integrate the Danfoss VACON VACON 100 family (built-in Modbus RTU / Modbus TCP)?

Start with HR 2000 FB control word (FB control word: run, direction, fault reset); HR 2002 FB speed reference (FB speed reference, 0.01 % of min-max range); HR 2100 FB status word (FB status word: ready/run/fault/alarm); HR 2103 Process data out 1 (output frequency) (Output frequency, 0.01 Hz); HR 44 Motor current 1 decimal (Motor current, 0.1 A (ID 45)); HR 2109 Process data out 7 (DC link voltage) (DC link voltage); HR 2110 Process data out 8 (active fault code) (Active fault code); HR 171 Remote control place (ID 172 remote control place (1 = fieldbus)).

How do I enable Modbus control of the Danfoss VACON VACON 100 family (built-in Modbus RTU / Modbus TCP)?

Modbus RTU: set P5.8.1.1 RS-485 protocol (ID 2208) = Modbus RTU, after which its settings appear under P5.8.3 (slave address ID 2320, baud ID 2378, parity ID 2379, stop bits ID 2380, time-out ID 2321). Modbus TCP/UDP is always enabled; set the IP mode and address under P5.9.1. For control set Remote control place P3.2.1 (ID 172) = Fieldbus control, Local/remote (ID 211) = Remote, and leave Fieldbus control reference selection (ID 122) = 3 Fieldbus. Control word bits 8/9 can also force fieldbus control and reference.

What happens when the Danfoss VACON VACON 100 family (built-in Modbus RTU / Modbus TCP) loses Modbus communication?

RTU: ID 2321 communication time-out (seconds, default 10, 0 = off). TCP/UDP: ID 2448 time-out (seconds, default 10); a connection can also set its own timeout at register 40501. The reaction is ID 733 Response to fieldbus communication fault (default 3 = fault, stop per stop function); the fault is code 53 Fieldbus communication fault.

Where is the official Danfoss VACON VACON 100 family (built-in Modbus RTU / Modbus TCP) Modbus documentation?

The source is VACON 100 INDUSTRIAL / FLOW / HVAC / 100 X AC drives - Modbus TCP/UDP and Modbus RTU User Manual (DPD00156D), revision 2016-11-30, published free by Danfoss VACON at https://assets.danfoss.com/documents/270144/BC361182856709en-000401.pdf.

Source: VACON 100 INDUSTRIAL / FLOW / HVAC / 100 X AC drives - Modbus TCP/UDP and Modbus RTU User Manual · DPD00156D · rev. 2016-11-30. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.