 "manufacturer": "Vaisala",
 "manufacturer_slug": "vaisala",
 "model": "GMD110 duct CO2 transmitter (Modbus RTU)",
 "model_slug": "gmd110",
 "short_model": "GMD110",
 "aliases": [
  "GMD110",
  "CARBOCAP GMD110"
 ],
 "equipment_type": "Sensor (CO2 duct transmitter)",
 "applies_to": "GMD110 duct-mount CO2 transmitter, Modbus RTU interface (user guide M212885EN-B).",
 "summary": "The GMD110 is a Vaisala CARBOCAP duct transmitter for CO2 in ventilation ducts. It has analog outputs and a Modbus RTU interface on RS-485. This map covers the CO2 and temperature readings, serial settings, filtering and the status registers.",
 "transport": [
  "RTU"
 ],
 "defaults": {
  "unit_id": 240,
  "baud": 19200,
  "parity": "None",
  "data_bits": 8,
  "stop_bits": 2,
  "tcp_port": null
 },
 "addressing": {
  "convention": "1-based",
  "note": "The guide numbers registers in decimal starting at 1 and also prints the 0-based hex address used in the request; register number 1 is address 0x0000 on the wire."
 },
 "default_word_order": "CDAB",
 "firmware": null,
 "source": {
  "title": "GMD110 User Guide",
  "doc_number": "M212885EN-B",
  "revision_date": "2023-09",
  "url": "https://docs.vaisala.com/r/M212885EN-B/en-US",
  "pages": "Appendix A Modbus reference, pp. 47-52 (Tables 11-18)"
 },
 "notes": [
  "All registers are holding registers: read with function 03, write with function 16.",
  "32-bit floats and 32-bit integers put the least significant word at the listed register (CDAB). The guide states this and its worked read example confirms it.",
  "Unavailable data reads as quiet NaN (float) or 0x8000 (16-bit integer) rather than an exception.",
  "Status registers are sums of the listed values when several conditions are active.",
  "Register 258 must be multiplied by 10 (for readings above 32000 ppm)."
 ],
 "registers": [
  {
   "table": "holding_register",
   "address": 0,
   "documented": "1",
   "name": "Measured CO2",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 1,
   "units": "ppm",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2,
   "documented": "3",
   "name": "Compensation T",
   "description": "Temperature used for compensation.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 1,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 4,
   "documented": "5",
   "name": "Measured T",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 1,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 256,
   "documented": "257",
   "name": "Measured CO2 (integer)",
   "description": "Valid up to 32000 ppm.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "ppm",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 257,
   "documented": "258",
   "name": "Measured CO2 (integer, x10)",
   "description": "Scaled; multiply raw by 10.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 10,
   "units": "ppm",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 768,
   "documented": "769",
   "name": "Modbus address",
   "description": "1-247, default 240.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 769,
   "documented": "770",
   "name": "Serial speed",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "4800",
    "1": "9600",
    "2": "19200",
    "3": "38400",
    "4": "57600",
    "5": "115200"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 770,
   "documented": "771",
   "name": "Serial parity",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "None",
    "1": "Even",
    "2": "Odd"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 771,
   "documented": "772",
   "name": "Serial stop bits",
   "description": "1 or 2, default 2.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 776,
   "documented": "777",
   "name": "CO2 filtering factor",
   "description": "0-100; 100 = no filtering.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2048,
   "documented": "2049",
   "name": "Device status",
   "description": "0 = OK; values add up.",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "0": "Critical error",
    "1": "Error",
    "2": "Warning"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2049,
   "documented": "2050",
   "name": "CO2 status",
   "description": "0 = OK.",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "1": "CO2 reading not reliable (start-up)",
    "8": "Measurement not ready (start-up)"
   },
   "offset": 0
  }
 ],
 "integration": {
  "summary": "Read holding registers 1-2 for CO2 as a CDAB float (or 257 as an integer) and 2049-2050 for status.",
  "minimum_registers": [
   {
    "table": "holding_register",
    "address": 0,
    "why": "CO2 ppm"
   },
   {
    "table": "holding_register",
    "address": 4,
    "why": "Temperature"
   },
   {
    "table": "holding_register",
    "address": 2048,
    "why": "Device status"
   },
   {
    "table": "holding_register",
    "address": 2049,
    "why": "CO2 status"
   }
  ],
  "enable": "Set the output mode switch inside the transmitter to Digital; RS-485 is only active in that position (Analog enables the analog outputs instead). Modbus settings can also be changed in Vaisala Insight PC software via the service port.",
  "watchdog": null,
  "quirks": [
   "Floats are low word first (CDAB); pick \"word-swapped\" float in masters that default to high word first.",
   "Read or write each 32-bit value in one transaction."
  ],
  "setup": [
   "Defaults: address 240, 19200 baud, no parity, 8 data bits, 2 stop bits.",
   "Change address and serial settings with registers 769-772 or in Insight (Configure device)."
  ],
  "gotchas": [
   "The RS-485 port is non-isolated and has no built-in termination; fit termination and bias resistors on the bus yourself."
  ]
 },
 "page": "https://easymodbus.com/modbus-register-maps/vaisala/gmd110",
 "address_note": "address = 0-based Modbus wire (PDU) address; documented = as printed in the source.",
 "note": "Re-typed from the manufacturer's public documentation (see source) and verified against it. Registers vary by firmware and options; verify against the live device before writing."
}