 "manufacturer": "Vaisala",
 "manufacturer_slug": "vaisala",
 "model": "MMT143 moisture in oil transmitter (Modbus RTU)",
 "model_slug": "mmt143",
 "short_model": "MMT143",
 "aliases": [
  "MMT143"
 ],
 "equipment_type": "Sensor (moisture in oil transmitter)",
 "applies_to": "MMT143 moisture-in-oil transmitter ordered with the Modbus RTU option (user guide M213308EN-B).",
 "summary": "The MMT143 is a compact Vaisala transmitter for moisture in transformer, lubrication and hydraulic oils. Units with the Modbus option are Modbus RTU slaves on RS-485. This map covers water activity, ppm water content, relative saturation and temperature, oil type coefficients, serial settings and test registers.",
 "transport": [
  "RTU"
 ],
 "defaults": {
  "unit_id": 240,
  "baud": 19200,
  "parity": "None",
  "data_bits": 8,
  "stop_bits": null,
  "tcp_port": null
 },
 "addressing": {
  "convention": "1-based",
  "note": "The guide numbers registers in decimal starting at 1 and also prints the 0-based hex address used in the request; register number 1 is address 0x0000 on the wire."
 },
 "default_word_order": "CDAB",
 "firmware": null,
 "source": {
  "title": "MMT143 User Guide",
  "doc_number": "M213308EN-B",
  "revision_date": "2026-11",
  "url": "https://docs.vaisala.com/r/M213308EN-B/en-US",
  "pages": "Appendix A Modbus reference, pp. 71-80 (Tables 26-36)"
 },
 "notes": [
  "All registers are holding registers: read with function 03, write with function 16.",
  "32-bit floats put the least significant word at the listed register (CDAB). The guide states this and its worked read example confirms it.",
  "Unavailable data reads as quiet NaN (float) or 0x8000 (16-bit integer) rather than an exception.",
  "Left out: status code (516) and security hash (518). They are 32-bit integers, and this guide only states the word order for 32-bit floats.",
  "The ppmw value depends on the oil type setting (771) or custom coefficients A/B.",
  "Integer copies: temperature and relative saturation are x10, water activity x1000.",
  "Left out: the 16-character identification strings at 7425-7449; use Read Device Identification (function 43/14) instead."
 ],
 "registers": [
  {
   "table": "holding_register",
   "address": 2,
   "documented": "3",
   "name": "Temperature",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 1,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 28,
   "documented": "29",
   "name": "Water activity",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 34,
   "documented": "35",
   "name": "Water content",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 1,
   "units": "ppmw",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 40,
   "documented": "41",
   "name": "Relative saturation",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 1,
   "units": "%RS",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 257,
   "documented": "258",
   "name": "Temperature (integer)",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 270,
   "documented": "271",
   "name": "Water activity (integer)",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.001,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 273,
   "documented": "274",
   "name": "Water content (integer)",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "ppmw",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 276,
   "documented": "277",
   "name": "Relative saturation (integer)",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "%RS",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 512,
   "documented": "513",
   "name": "Error status",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "1": "No errors"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 770,
   "documented": "771",
   "name": "Oil type",
   "description": "Custom uses coefficients A and B.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Custom",
    "1": "Mineral oil",
    "2": "Synthetic ester (Midel 7131)",
    "3": "Natural ester (FR3)",
    "4": "Silicone liquid (Dow Corning 561)"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 776,
   "documented": "777",
   "name": "Oil coefficient A",
   "description": "-100000...0.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 778,
   "documented": "779",
   "name": "Oil coefficient B",
   "description": "-100...100.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 794,
   "documented": "795",
   "name": "Measurement filtering factor",
   "description": "0.00001-1.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1536,
   "documented": "1537",
   "name": "Modbus address",
   "description": "1-247.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1537,
   "documented": "1538",
   "name": "Bit rate",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "5": "9600",
    "6": "19200"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1538,
   "documented": "1539",
   "name": "Parity, data, stop bits",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "N81",
    "1": "N82",
    "2": "E81",
    "3": "E82",
    "4": "O81",
    "5": "O82"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1539,
   "documented": "1540",
   "name": "Response delay",
   "description": "0-1020 ms.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "ms",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1540,
   "documented": "1541",
   "name": "Interface mode",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "6": "Modbus"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1541,
   "documented": "1542",
   "name": "Restart device",
   "description": "Write 1 to restart.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "W",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 7680,
   "documented": "7681",
   "name": "Restore settings",
   "description": "Write 1 to restore factory settings.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "W",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 7936,
   "documented": "7937",
   "name": "Signed integer test",
   "description": "Always reads -12345.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 7937,
   "documented": "7938",
   "name": "Floating point test",
   "description": "Always reads -123.45.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 7939,
   "documented": "7940",
   "name": "Text string test",
   "description": "Reads the text \"-123.45\".",
   "data_type": "STRING",
   "length": 4,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  }
 ],
 "integration": {
  "summary": "Read holding registers 3-4 and 29-42 for temperature, water activity, ppm and relative saturation (CDAB floats). Set the oil type first so ppm is meaningful.",
  "minimum_registers": [
   {
    "table": "holding_register",
    "address": 34,
    "why": "Water content ppm"
   },
   {
    "table": "holding_register",
    "address": 28,
    "why": "Water activity"
   },
   {
    "table": "holding_register",
    "address": 2,
    "why": "Oil temperature"
   },
   {
    "table": "holding_register",
    "address": 512,
    "why": "Error status"
   },
   {
    "table": "holding_register",
    "address": 770,
    "why": "Oil type"
   }
  ],
  "enable": "Order the transmitter with the Modbus configuration option, or set the serial mode to MODBUS with the SMODE serial command (applied at the next power-up).",
  "watchdog": null,
  "quirks": [
   "Floats are low word first (CDAB); pick \"word-swapped\" float in masters that default to high word first.",
   "Read or write each 32-bit value in one transaction."
  ],
  "setup": [
   "Defaults: address 240, 19200 baud, no parity, 8 data bits; stop bits are 1 or 2 depending on the ordered configuration (check register 1539).",
   "Change Modbus serial settings with Insight, the Indigo80 or registers 1537-1540; give each device on a shared bus a unique address (1-247)."
  ],
  "gotchas": [
   "Use the test registers (7937 on) to confirm float format and addressing before trusting readings."
  ]
 },
 "page": "https://easymodbus.com/modbus-register-maps/vaisala/mmt143",
 "address_note": "address = 0-based Modbus wire (PDU) address; documented = as printed in the source.",
 "note": "Re-typed from the manufacturer's public documentation (see source) and verified against it. Registers vary by firmware and options; verify against the live device before writing."
}