 "manufacturer": "Vaisala",
 "manufacturer_slug": "vaisala",
 "model": "Origo10 transmitters for HVAC (Origo10A, Modbus RTU)",
 "model_slug": "origo10",
 "short_model": "Origo10",
 "aliases": [
  "Origo10",
  "Origo10A",
  "Origo 10",
  "Vaisala Origo10 duct transmitter",
  "Vaisala Origo10 wall transmitter"
 ],
 "equipment_type": "Sensor (HVAC humidity, temperature and CO2 transmitter)",
 "applies_to": "Origo10A duct and wall transmitters ordered with the Modbus RTU output (user guide M213293EN-B). Origo10L has no Modbus.",
 "summary": "Origo10 is Vaisala's modular HVAC transmitter: a duct or wall housing that takes up to two probes (XMP10 humidity/temperature, CO2, temperature) and up to three plug-in modules such as the DIO10 relay/binary-input module. The Origo10A version offers Modbus RTU (or BACnet MS/TP) on RS-485. Each probe or module gets its own 4096-register block; this map lists probe A in full, the main probe B readings, module 1 relay/input, transmitter status, serial settings and test registers.",
 "transport": [
  "RTU"
 ],
 "defaults": {
  "unit_id": 240,
  "baud": 19200,
  "parity": "None",
  "data_bits": 8,
  "stop_bits": 1,
  "tcp_port": null
 },
 "addressing": {
  "convention": "1-based",
  "note": "Registers are numbered in decimal from 1 and the guide also prints the 0-based hex PDU address; register 1 is address 0x0000. Subdevice blocks: register = base + X * 4096, with X = 0 probe A, 1 probe B, 2-4 modules 1-3 (hex address 0xX000 style)."
 },
 "default_word_order": "CDAB",
 "firmware": null,
 "source": {
  "title": "Origo10 User Guide",
  "doc_number": "M213293EN-B",
  "revision_date": "2026-05",
  "url": "https://docs.vaisala.com/r/M213293EN-B/en-US",
  "pages": "Appendix A Modbus reference, pp. 125-134 (Tables 34-46)"
 },
 "notes": [
  "All registers are holding registers: read with function 03, write with function 16.",
  "32-bit floats and 32-bit integers/bitfields put the least significant word at the listed register (CDAB), as the guide states for both formats.",
  "Only probe A is listed in full. Probe B uses the same layout plus 4096 (e.g. RH at register 4353), and modules 1-3 add 8192, 12288 and 16384. Registers for parameters the fitted probe cannot measure are unavailable.",
  "Left out: the 16-bit integer copies of the measurements (897-910 + X*4096). The guide prints a 'scale factor' column (10, and 0.01 for CO2 ppm) but never says whether to multiply or divide the raw value by it, so the floats are listed instead. 0x8000 in an integer register means not available.",
  "Left out: most non-metric floats except RH, T, dew point and enthalpy, the remaining measurement-status registers (same bit layout), and the long identification strings (vendor URL, product name, manufacturing data).",
  "Modbus is only available on Origo10A transmitters. The protocol can be changed to BACnet MS/TP in Insight."
 ],
 "registers": [
  {
   "table": "holding_register",
   "address": 0,
   "documented": "1",
   "name": "Probe A product code",
   "description": "32-character text.",
   "data_type": "STRING",
   "length": 16,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 16,
   "documented": "17",
   "name": "Probe A serial number",
   "description": "",
   "data_type": "STRING",
   "length": 16,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 32,
   "documented": "33",
   "name": "Probe A version",
   "description": "",
   "data_type": "STRING",
   "length": 16,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 48,
   "documented": "49",
   "name": "Probe A status code",
   "description": "",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "0": "Failure active",
    "1": "Error active",
    "2": "Warning active",
    "3": "Information active",
    "4": "Calibration mode active"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 256,
   "documented": "257",
   "name": "Probe A relative humidity",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 1,
   "units": "%RH",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 258,
   "documented": "259",
   "name": "Probe A temperature",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 1,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 260,
   "documented": "261",
   "name": "Probe A dew point temperature",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 1,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 262,
   "documented": "263",
   "name": "Probe A dew/frost point temperature",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 1,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 264,
   "documented": "265",
   "name": "Probe A absolute humidity",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 1,
   "units": "g/m3",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 266,
   "documented": "267",
   "name": "Probe A mixing ratio",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 1,
   "units": "g/kg",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 268,
   "documented": "269",
   "name": "Probe A wet-bulb temperature",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 1,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 270,
   "documented": "271",
   "name": "Probe A water vapor pressure",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 1,
   "units": "hPa",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 272,
   "documented": "273",
   "name": "Probe A water vapor saturation pressure",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 1,
   "units": "hPa",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 274,
   "documented": "275",
   "name": "Probe A enthalpy",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 1,
   "units": "kJ/kg",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 276,
   "documented": "277",
   "name": "Probe A CO2 concentration (ppm)",
   "description": "With a CO2 probe connected.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 1,
   "units": "ppm",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 278,
   "documented": "279",
   "name": "Probe A CO2 concentration (%)",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 1,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 512,
   "documented": "513",
   "name": "Probe A relative humidity (non-metric block)",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 1,
   "units": "%RH",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 514,
   "documented": "515",
   "name": "Probe A temperature (non-metric block)",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 1,
   "units": "°F",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 516,
   "documented": "517",
   "name": "Probe A dew point temperature (non-metric block)",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 1,
   "units": "°F",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 530,
   "documented": "531",
   "name": "Probe A enthalpy (non-metric block)",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 1,
   "units": "BTU/lb",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 768,
   "documented": "769",
   "name": "Probe A RH measurement status",
   "description": "0 = status OK.",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "0": "Measurement not available",
    "1": "Measurement not reliable",
    "2": "Under range",
    "3": "Over range",
    "4": "Noisy",
    "5": "Value locked",
    "6": "Calibration expired",
    "7": "Sensor failure",
    "8": "Measurement not ready"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 769,
   "documented": "770",
   "name": "Probe A T measurement status",
   "description": "",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "0": "Measurement not available",
    "1": "Measurement not reliable",
    "2": "Under range",
    "3": "Over range",
    "4": "Noisy",
    "5": "Value locked",
    "6": "Calibration expired",
    "7": "Sensor failure",
    "8": "Measurement not ready"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 778,
   "documented": "779",
   "name": "Probe A CO2 ppm measurement status",
   "description": "",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "0": "Measurement not available",
    "1": "Measurement not reliable",
    "2": "Under range",
    "3": "Over range",
    "4": "Noisy",
    "5": "Value locked",
    "6": "Calibration expired",
    "7": "Sensor failure",
    "8": "Measurement not ready"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 4352,
   "documented": "4353",
   "name": "Probe B relative humidity",
   "description": "Same layout as probe A, offset by 4096.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 1,
   "units": "%RH",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 4354,
   "documented": "4355",
   "name": "Probe B temperature",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 1,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 4372,
   "documented": "4373",
   "name": "Probe B CO2 concentration (ppm)",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 1,
   "units": "ppm",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8242,
   "documented": "8243",
   "name": "Module 1 relay output control",
   "description": "DIO10 module in slot M1.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Inactive",
    "1": "Active",
    "2": "N/A"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8472,
   "documented": "8473",
   "name": "Module 1 binary input",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Loop open",
    "1": "Loop closed",
    "2": "N/A"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8474,
   "documented": "8475",
   "name": "Module 1 relay output",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Inactive",
    "1": "Active",
    "2": "N/A"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 49152,
   "documented": "49153",
   "name": "Transmitter status code low",
   "description": "",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "0": "Non-volatile memory read/write failure",
    "1": "Device settings corrupted",
    "2": "Factory settings corrupted",
    "4": "Probe current limit exceeded",
    "7": "Probe type not supported",
    "8": "Module type not supported",
    "11": "Probe missing",
    "12": "Module missing",
    "16": "Cannot read all measurement parameters",
    "17": "Analog output 1 out of range",
    "18": "Analog output 2 out of range",
    "19": "Analog output 3 out of range",
    "20": "Analog output 1 test mode active",
    "21": "Analog output 2 test mode active",
    "22": "Analog output 3 test mode active",
    "23": "Analog output 1 calibration active",
    "24": "Analog output 2 calibration active",
    "25": "Analog output 3 calibration active",
    "26": "Supply voltage out of range",
    "27": "Probe 1 not detected",
    "28": "Probe 2 not detected",
    "29": "Module 1 not detected",
    "30": "Module 2 not detected",
    "31": "Module 3 not detected"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 49154,
   "documented": "49155",
   "name": "Transmitter status code high",
   "description": "",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "0": "Restart to apply settings",
    "1": "Configuration locked",
    "2": "Configuration unlocked"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 49156,
   "documented": "49157",
   "name": "Firmware version",
   "description": "",
   "data_type": "STRING",
   "length": 16,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 49172,
   "documented": "49173",
   "name": "Security hash",
   "description": "",
   "data_type": "INT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 49174,
   "documented": "49175",
   "name": "Vendor name",
   "description": "",
   "data_type": "STRING",
   "length": 8,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 49206,
   "documented": "49207",
   "name": "Product code",
   "description": "",
   "data_type": "STRING",
   "length": 8,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 49262,
   "documented": "49263",
   "name": "Serial number",
   "description": "",
   "data_type": "STRING",
   "length": 4,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 49664,
   "documented": "49665",
   "name": "Restart device",
   "description": "Write 1 to restart.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 50949,
   "documented": "50950",
   "name": "Signed integer test",
   "description": "Always reads -12345.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 50950,
   "documented": "50951",
   "name": "Floating point test",
   "description": "Always reads -123.45.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 51201,
   "documented": "51202",
   "name": "Modbus address",
   "description": "1-247, default 240.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 51202,
   "documented": "51203",
   "name": "Bit rate",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "300",
    "1": "600",
    "2": "1200",
    "3": "2400",
    "4": "4800",
    "5": "9600",
    "6": "19200",
    "7": "38400",
    "8": "57600",
    "9": "76800",
    "10": "115200"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 51203,
   "documented": "51204",
   "name": "Parity, data, stop bits",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "None, 8, 1",
    "1": "None, 8, 2",
    "2": "Even, 8, 1",
    "3": "Even, 8, 2",
    "4": "Odd, 8, 1",
    "5": "Odd, 8, 2"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 51204,
   "documented": "51205",
   "name": "Response delay",
   "description": "0-1000 ms, default 20.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "ms",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  }
 ],
 "integration": {
  "summary": "Read registers 257-260 (wire 256-259) for probe A humidity and temperature as low-word-first floats, add 277 for CO2 if a CO2 probe is fitted, and watch the transmitter status code at 49153.",
  "minimum_registers": [
   {
    "table": "holding_register",
    "address": 256,
    "why": "Probe A relative humidity"
   },
   {
    "table": "holding_register",
    "address": 258,
    "why": "Probe A temperature"
   },
   {
    "table": "holding_register",
    "address": 260,
    "why": "Dew point"
   },
   {
    "table": "holding_register",
    "address": 276,
    "why": "CO2 ppm (CO2 probe)"
   },
   {
    "table": "holding_register",
    "address": 48,
    "why": "Probe A status"
   },
   {
    "table": "holding_register",
    "address": 49152,
    "why": "Transmitter error/warning bits"
   }
  ],
  "enable": "Order Origo10A with the Modbus RTU output option. Serial settings and the Modbus address can be changed in Vaisala Insight PC software over the USB-C service port or through registers 51202-51205.",
  "watchdog": null,
  "quirks": [
   "Floats are low word first (CDAB); choose a word-swapped float format in masters that default to high word first.",
   "Read or write each 32-bit value in one transaction.",
   "Register blocks are per subdevice: add 4096 for probe B and 8192/12288/16384 for modules 1-3."
  ],
  "setup": [
   "Defaults: address 240, 19200 baud, no parity, 8 data bits, 1 stop bit, response delay 20 ms.",
   "Up to 24 transmitters on one RS-485 line, each with a unique address.",
   "Use the RS-485 termination jumper on the component board at the line ends."
  ],
  "gotchas": [
   "Origo10L transmitters are analog only.",
   "Read the test registers 50950-50952 first to confirm addressing and float format."
  ]
 },
 "page": "https://easymodbus.com/modbus-register-maps/vaisala/origo10",
 "address_note": "address = 0-based Modbus wire (PDU) address; documented = as printed in the source.",
 "note": "Re-typed from the manufacturer's public documentation (see source) and verified against it. Registers vary by firmware and options; verify against the live device before writing."
}