 "manufacturer": "Vaisala",
 "manufacturer_slug": "vaisala",
 "model": "XMP10 humidity and temperature probe (Modbus RTU)",
 "model_slug": "xmp10",
 "short_model": "XMP10",
 "aliases": [
  "XMP10",
  "HUMICAP XMP10",
  "Vaisala XMP10"
 ],
 "equipment_type": "Sensor (humidity and temperature probe)",
 "applies_to": "XMP10 probes ordered with (or switched to) Modbus RTU output, user guide M213279EN-A.",
 "summary": "XMP10 is a small Vaisala HUMICAP humidity and temperature probe that works stand-alone or as the sensing part of a transmitter such as Origo10. With the Modbus option it talks Modbus RTU on RS-485 and can be daisy-chained. This map covers humidity, temperature and the calculated humidity values as floats and scaled integers, error and status registers, filtering, serial settings and the test registers.",
 "transport": [
  "RTU"
 ],
 "defaults": {
  "unit_id": 240,
  "baud": 19200,
  "parity": "None",
  "data_bits": 8,
  "stop_bits": 2,
  "tcp_port": null
 },
 "addressing": {
  "convention": "1-based",
  "note": "The guide numbers registers in decimal from 1 and also prints the 0-based hex address used in the request. Register 1 is address 0x0000 on the wire; the guide's example frame reads relative humidity at address 0x0000."
 },
 "default_word_order": "CDAB",
 "firmware": null,
 "source": {
  "title": "XMP10 User Guide",
  "doc_number": "M213279EN-A",
  "revision_date": "2026-04",
  "url": "https://docs.vaisala.com/r/M213279EN-A/en-US",
  "pages": "Appendix A Modbus reference, pp. 80-88 (Tables 17-25, example frames A.6)"
 },
 "notes": [
  "All registers are holding registers: read with function 03, write with function 16.",
  "32-bit floats and 32-bit integers put the least significant word at the listed register (CDAB), as the guide states; its example response for RH shows the low word first.",
  "Integer registers are printed with units such as '%RH * 10', so divide the raw value by 10 (scale 0.1). 0x8000 (32768) means the value is not available; 0x7FFF and 0x8001 mean at or beyond the 16-bit range.",
  "Register 513 reads 0 when an error is active and 1 when there is none, exactly as printed.",
  "Error codes 1024, 16384 and 32768 (calibration expiry and invalid communication settings) are visible only in Insight or Indigo80, so they are not listed as Modbus bits.",
  "The text-string test register (7940) is left out because the guide does not give its register length in a way that fixes the read size.",
  "Bit rate and parity changes take effect after a restart (register 1542). Incompatible settings can lock out Modbus; Insight can override them."
 ],
 "registers": [
  {
   "table": "holding_register",
   "address": 0,
   "documented": "1",
   "name": "Relative humidity",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 1,
   "units": "%RH",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2,
   "documented": "3",
   "name": "Temperature",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 1,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8,
   "documented": "9",
   "name": "Dew/frost point temperature",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 1,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 14,
   "documented": "15",
   "name": "Absolute humidity",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 1,
   "units": "g/m3",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 16,
   "documented": "17",
   "name": "Mixing ratio",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 1,
   "units": "g/kg",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 18,
   "documented": "19",
   "name": "Wet-bulb temperature",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 1,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 26,
   "documented": "27",
   "name": "Enthalpy",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 1,
   "units": "kJ/kg",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 256,
   "documented": "257",
   "name": "Relative humidity (integer)",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "%RH",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 257,
   "documented": "258",
   "name": "Temperature (integer)",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 260,
   "documented": "261",
   "name": "Dew/frost point temperature (integer)",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 263,
   "documented": "264",
   "name": "Absolute humidity (integer)",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "g/m3",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 264,
   "documented": "265",
   "name": "Mixing ratio (integer)",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "g/kg",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 265,
   "documented": "266",
   "name": "Wet-bulb temperature (integer)",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 269,
   "documented": "270",
   "name": "Enthalpy (integer)",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "kJ/kg",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 512,
   "documented": "513",
   "name": "Error status",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "One or more errors active",
    "1": "No errors"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 515,
   "documented": "516",
   "name": "Error code",
   "description": "Sum of active error codes (see bits).",
   "data_type": "INT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "0": "Temperature measurement error",
    "1": "Humidity measurement error",
    "2": "Humidity sensor failure",
    "3": "Capacitance reference error",
    "4": "Ambient temperature out of range",
    "5": "Firmware checksum mismatch",
    "6": "Device settings corrupted",
    "7": "Additional configuration settings corrupted",
    "8": "Sensor coefficients corrupted",
    "9": "Main configuration settings corrupted",
    "11": "Supply voltage out of range",
    "13": "Non-volatile memory read/write failure"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 517,
   "documented": "518",
   "name": "Security hash",
   "description": "Changes whenever settings or adjustments change.",
   "data_type": "INT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 784,
   "documented": "785",
   "name": "Measurement filtering factor",
   "description": "0.001 = maximum filtering, 1.000 = no filtering.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1536,
   "documented": "1537",
   "name": "Modbus address",
   "description": "1-247.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1537,
   "documented": "1538",
   "name": "Bit rate",
   "description": "Takes effect after restart.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "5": "9600",
    "6": "19200",
    "7": "38400",
    "8": "57600"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1538,
   "documented": "1539",
   "name": "Parity, data, stop bits",
   "description": "Takes effect after restart.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "None, 8, 1",
    "1": "None, 8, 2",
    "2": "Even, 8, 1",
    "3": "Even, 8, 2",
    "4": "Odd, 8, 1",
    "5": "Odd, 8, 2"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1539,
   "documented": "1540",
   "name": "Response delay",
   "description": "0-1020 ms in 4 ms steps.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "ms",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1540,
   "documented": "1541",
   "name": "Protocol",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "6": "Modbus RTU"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1541,
   "documented": "1542",
   "name": "Restart device",
   "description": "Write 1 to restart.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "W",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 7936,
   "documented": "7937",
   "name": "Signed integer test",
   "description": "Always reads -12345.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 7937,
   "documented": "7938",
   "name": "Floating point test",
   "description": "Always reads -123.45.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  }
 ],
 "integration": {
  "summary": "Read holding registers 1-4 (wire 0-3) for RH and temperature as low-word-first floats, or 257-258 as integers divided by 10. Check register 513 and the error code at 516 for faults.",
  "minimum_registers": [
   {
    "table": "holding_register",
    "address": 0,
    "why": "Relative humidity"
   },
   {
    "table": "holding_register",
    "address": 2,
    "why": "Temperature"
   },
   {
    "table": "holding_register",
    "address": 8,
    "why": "Dew/frost point"
   },
   {
    "table": "holding_register",
    "address": 26,
    "why": "Enthalpy"
   },
   {
    "table": "holding_register",
    "address": 512,
    "why": "Error status"
   },
   {
    "table": "holding_register",
    "address": 515,
    "why": "Error code"
   }
  ],
  "enable": "Order the probe with Modbus RTU output (output code M), or from the serial command interface give smode modbus and then reset or power cycle the probe. Serial setting changes also need a power cycle before they apply.",
  "watchdog": null,
  "quirks": [
   "Floats are low word first (CDAB); choose a word-swapped float format in masters that default to high word first.",
   "Read or write each 32-bit value in one transaction."
  ],
  "setup": [
   "Defaults: address 240, 19200 baud, no parity, 8 data bits, 2 stop bits, response delay 0.",
   "Up to 32 probes per RS-485 line at 19200 bps or lower; give each a unique address with Insight.",
   "Terminate the last device when the line is over 100 m.",
   "Allow up to 2 s after power-up before the first request."
  ],
  "gotchas": [
   "Read the test registers 7937-7939 first to confirm addressing and float format; a wrong float setting can still give plausible-looking numbers."
  ]
 },
 "page": "https://easymodbus.com/modbus-register-maps/vaisala/xmp10",
 "address_note": "address = 0-based Modbus wire (PDU) address; documented = as printed in the source.",
 "note": "Re-typed from the manufacturer's public documentation (see source) and verified against it. Registers vary by firmware and options; verify against the live device before writing."
}