 "manufacturer": "Vasco",
 "manufacturer_slug": "vasco",
 "model": "SAB RVU ventilation unit controller (D150 Compact, Energy Plus)",
 "model_slug": "sab-rvu",
 "short_model": "Vasco SAB RVU",
 "aliases": [
  "D150 Compact",
  "Energy Plus ENY-P1",
  "ENY-P2",
  "ENY-P3",
  "ENY-P4",
  "ESP170V",
  "ESP270",
  "ESP360",
  "ESP460"
 ],
 "equipment_type": "Air handler (residential heat recovery ventilation)",
 "applies_to": "Vasco SAB RVU controller boards (models 0x52xx residential and 0x53xx Energy Plus) with protocol release 0x0006, manual 90.01.06.53.",
 "summary": "The SAB RVU board in Vasco D150 Compact and Energy Plus heat recovery units speaks Modbus RTU on its RS485 port (connector M19), using holding registers only. The map covers identification, the live machine state (temperatures, fan speeds, pressures, CO2, RH, alarms, run hours), the main parameters and the command block for on/off, mode, speed and external RH/CO2 values.",
 "transport": [
  "RTU"
 ],
 "defaults": {
  "unit_id": null,
  "baud": 9600,
  "parity": "None",
  "data_bits": 8,
  "stop_bits": 1,
  "tcp_port": null
 },
 "addressing": {
  "convention": "hex 0-based",
  "note": "The manual prints hexadecimal register addresses and the first block starts at 0x0000 (serial number), which only fits addresses sent as printed. Use the hex value directly: 0x0110 = register 272 on the wire."
 },
 "default_word_order": "ABCD",
 "firmware": "Protocol release 0x0006",
 "source": {
  "title": "SAB RVU Ventilation Unit - Manual Modbus Protocol (D150 Compact, Energy Plus ENY-P1/2/3/4)",
  "doc_number": "90.01.06.53",
  "revision_date": null,
  "url": "https://vasco.eu/files/downloads/manuel-modbus-protocol-energy-plus/90.01.06.53-Handleiding-Modbus-registers-SAB-RVU.pdf",
  "pages": "p. 2 serial settings, data types and word order, pp. 3-4 block 0-1, pp. 5-6 block 2, p. 6-7 block 3"
 },
 "notes": [
  "32-bit values use two registers with the most significant 16 bits first (data type table), so the hours counter is ABCD.",
  "Left out: the four float registers Rho 1-4 (0x0115-0x011B), because the type table states the word order only for 32-bit integers; the four weekly timer programs (blocks 4-7, 0x0400-0x0737) and block 8 time/date.",
  "Byte-type registers (0x0108-0x010A) carry their 8 bits in the most significant byte of the register.",
  "Out-of-range parameter writes are accepted but clipped to the allowed range."
 ],
 "registers": [
  {
   "table": "holding_register",
   "address": 0,
   "documented": "0x0000",
   "name": "Serial Number",
   "description": "Machine ID for customer use, 20 characters.",
   "data_type": "STRING",
   "length": 10,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 10,
   "documented": "0x000A",
   "name": "Controller model",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "20992": "0x5200 ESP170V",
    "20993": "0x5201 ESP270",
    "20994": "0x5202 ESP360",
    "20995": "0x5203 ESP460",
    "20996": "0x5204 ESP170H",
    "20997": "0x5205 ESP180",
    "20998": "0x5206 ESP280",
    "20999": "0x5207 ESP370",
    "21248": "0x5300 ENYP1",
    "21249": "0x5301 ENYP2",
    "21250": "0x5302 ENYP3",
    "21251": "0x5303 ENYP4"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 11,
   "documented": "0x000B",
   "name": "Firmware Release",
   "description": "High byte major, low byte minor release.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 12,
   "documented": "0x000C",
   "name": "Protocol Release",
   "description": "The tables apply when this reads 0x0006.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 13,
   "documented": "0x000D",
   "name": "T-EP Firmware Release",
   "description": "High byte major, low byte minor release.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 256,
   "documented": "0x0100",
   "name": "Temperature probe T1",
   "description": "Part of the Sig16[4] block at 0x0100.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 257,
   "documented": "0x0101",
   "name": "Temperature probe T2",
   "description": "Part of the Sig16[4] block at 0x0100.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 258,
   "documented": "0x0102",
   "name": "Temperature probe T3",
   "description": "Part of the Sig16[4] block at 0x0100.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 259,
   "documented": "0x0103",
   "name": "Temperature probe T4",
   "description": "Part of the Sig16[4] block at 0x0100.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 260,
   "documented": "0x0104",
   "name": "Dips Configuration",
   "description": "1 = DIP on.",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "0": "Inverted configuration",
    "1": "Pre-heating present",
    "2": "Pre-heating with water (0 = heat exchanger)",
    "3": "Post treatment on",
    "4": "Post treatment also in summer",
    "5": "RL5 = IAQ (0 = fault signalling)",
    "6": "Pre treatment",
    "7": "IN3 boiler pressure booster",
    "8": "Post treatment external heat exchanger",
    "9": "0x53xx controllers: post treatment on T2 (0 = on T3)"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 261,
   "documented": "0x0105",
   "name": "Machine state and mode",
   "description": "Bits 9-10 mode (0 holiday, 1 auto, 2 program, 3 manual); bit 11 winter; bits 12-15 program.",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "0": "Remote OFF active",
    "1": "Bypass active",
    "2": "Electric pre-heater active",
    "3": "Water pre-heating active",
    "4": "Boost active",
    "5": "Defrost cycle active",
    "7": "Party mode on",
    "8": "Unit on",
    "11": "Season winter (0 = summer)"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 262,
   "documented": "0x0106",
   "name": "Humidity setpoint",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "%RH",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 263,
   "documented": "0x0107",
   "name": "Filter counter",
   "description": "Counts in 15-minute steps.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 264,
   "documented": "0x0108",
   "name": "Digital output",
   "description": "8-bit value in the high byte; bit 2 damper clockwise, bit 3 counter-clockwise.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 265,
   "documented": "0x0109",
   "name": "Relay state",
   "description": "8-bit value in the high byte; bits 0-4 IAQ/fault, preheat, postheat, fans, postcool/postheat2.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 266,
   "documented": "0x010A",
   "name": "Digital Inputs",
   "description": "8-bit value in the high byte; bits 1-4 = inputs C1-C4 active.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 267,
   "documented": "0x010B",
   "name": "Fan1 Speed",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "rpm",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 268,
   "documented": "0x010C",
   "name": "Fan2 Speed",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "rpm",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 269,
   "documented": "0x010D",
   "name": "Duty Cycle Fan 1",
   "description": "PWM drive.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 270,
   "documented": "0x010E",
   "name": "Duty Cycle Fan 2",
   "description": "PWM drive.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 271,
   "documented": "0x010F",
   "name": "Duty Cycle El. Preheater",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 272,
   "documented": "0x0110",
   "name": "Alarms",
   "description": "1 = active.",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "0": "T1 probe failure",
    "1": "T2 probe failure",
    "2": "T3 probe failure",
    "3": "T4 probe failure",
    "4": "Timekeeper failure",
    "5": "Frost alarm",
    "6": "Frost alarm (T2 probe)",
    "7": "Fireplace alarm",
    "8": "Pressure transducer failure",
    "9": "Filter alarm",
    "10": "Fans failure",
    "11": "RH or CO2 sensor failure",
    "12": "Fan thermal input alarm",
    "14": "Pre-heating alarm",
    "15": "Pre-frost alarm (T2)"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 273,
   "documented": "0x0111",
   "name": "Diff Pressure Sensor 1",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "Pa",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 274,
   "documented": "0x0112",
   "name": "Diff Pressure Sensor 2",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "Pa",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 275,
   "documented": "0x0113",
   "name": "CO2 reading",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "ppm",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 276,
   "documented": "0x0114",
   "name": "RH reading",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "%RH",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 285,
   "documented": "0x011D",
   "name": "Cspeed 1",
   "description": "Speed coefficient 1, multiplied by 0x4000.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 286,
   "documented": "0x011E",
   "name": "Cspeed 2",
   "description": "Speed coefficient 2, multiplied by 0x4000.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 287,
   "documented": "0x0111F",
   "name": "Options/info",
   "description": "Printed as 0x0111F, between 0x011E and 0x0120.",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "1": "RPM too high detected",
    "8": "IAQ used",
    "9": "Post treatment used",
    "10": "Heat exchanger used",
    "11": "Boiler boost mode used",
    "12": "CO2 sensor present",
    "13": "Differential pressure sensor present",
    "14": "RH sensor present",
    "15": "Reverse mounting"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 288,
   "documented": "0x0120",
   "name": "Hours of operation",
   "description": "Fans-on hour counter.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "h",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 290,
   "documented": "0x0122",
   "name": "FreeCooling/FreeHeating",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "None",
    "1": "Free cooling",
    "2": "Free heating"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 512,
   "documented": "0x0200",
   "name": "Parameters Flags",
   "description": "",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": {
    "1": "Stop mode fans on (0 = fans off)",
    "2": "Flush mode on",
    "3": "Modbus speed 38400 (0 = 9600)",
    "4": "High RH management on"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 513,
   "documented": "0x0201",
   "name": "Temp probe 1 offset",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "°C",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 514,
   "documented": "0x0202",
   "name": "Temp probe 2 offset",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "°C",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 515,
   "documented": "0x0203",
   "name": "Temp probe 3 offset",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "°C",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 516,
   "documented": "0x0204",
   "name": "Temp probe 4 offset",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "°C",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 517,
   "documented": "0x0205",
   "name": "Fan min voltage",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "V",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 518,
   "documented": "0x0206",
   "name": "Fan max voltage",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "V",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 519,
   "documented": "0x0207",
   "name": "Fan1 Nominal V drive",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "V",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 520,
   "documented": "0x0208",
   "name": "Fan2 Nominal V drive",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "V",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 521,
   "documented": "0x0209",
   "name": "Fan min speed",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "rpm",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 522,
   "documented": "0x020A",
   "name": "Fan max speed",
   "description": "Range 1000-4000 rpm.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "rpm",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 523,
   "documented": "0x020B",
   "name": "Fan1 nominal speed",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "rpm",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 524,
   "documented": "0x020C",
   "name": "Fan2 nominal speed",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "rpm",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 525,
   "documented": "0x020D",
   "name": "Fan1 installation speed",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "rpm",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 526,
   "documented": "0x020E",
   "name": "K coefficient 1",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 527,
   "documented": "0x020F",
   "name": "K coefficient 2",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 528,
   "documented": "0x0210",
   "name": "Air flow 1",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "m³/h",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 529,
   "documented": "0x0211",
   "name": "Air flow 2",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "m³/h",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 530,
   "documented": "0x0212",
   "name": "Manual Speed (parameter)",
   "description": "0-3 = speed 1-4; writing it switches to manual speed mode.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 531,
   "documented": "0x0213",
   "name": "Speed 1 %",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "%",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 532,
   "documented": "0x0214",
   "name": "Speed 2 %",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "%",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 533,
   "documented": "0x0215",
   "name": "Speed 3 %",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "%",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 534,
   "documented": "0x0216",
   "name": "Speed 4 %",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "%",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 535,
   "documented": "0x0217",
   "name": "Boost Speed %",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "%",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 536,
   "documented": "0x0218",
   "name": "Summer T Setpoint",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "°C",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 537,
   "documented": "0x0219",
   "name": "Winter T setpoint",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "°C",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 538,
   "documented": "0x021A",
   "name": "Air coefficients recalc. interval",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "min",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 539,
   "documented": "0x021B",
   "name": "Temp for free cooling",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "°C",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 540,
   "documented": "0x021C",
   "name": "Temp for free heating",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "°C",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 541,
   "documented": "0x021D",
   "name": "Fan2 unbalance %",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "%",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 542,
   "documented": "0x021E",
   "name": "Humidity samples for setpoint",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 543,
   "documented": "0x021F",
   "name": "Boost time",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "min",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 544,
   "documented": "0x0220",
   "name": "P constant for humidity regulator",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 545,
   "documented": "0x0221",
   "name": "Filter life",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "days",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 546,
   "documented": "0x0222",
   "name": "CO2 ppm min",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "ppm",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 547,
   "documented": "0x0223",
   "name": "CO2 ppm nom",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "ppm",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 548,
   "documented": "0x0224",
   "name": "CO2 ppm max",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "ppm",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 549,
   "documented": "0x0225",
   "name": "CO2 ppm prop constant",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 550,
   "documented": "0x0226",
   "name": "Blocked functions",
   "description": "1 = function blocked on the user panel.",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": {
    "0": "Manual mode not allowed",
    "1": "Party mode not allowed",
    "2": "Holiday mode not allowed",
    "3": "Auto mode not allowed",
    "4": "Weekly program mode not allowed",
    "5": "Time/day change not allowed",
    "6": "Off command not allowed"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 551,
   "documented": "0x0227",
   "name": "CO2 Sensor PPM Range",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "ppm",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 552,
   "documented": "0x0228",
   "name": "Boiler boost time",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "min",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 553,
   "documented": "0x0229",
   "name": "RH Low value",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "%RH",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 554,
   "documented": "0x022A",
   "name": "RH Standard value",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "%RH",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 555,
   "documented": "0x022B",
   "name": "RH Hi value",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "%RH",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 556,
   "documented": "0x022C",
   "name": "Fan Speed with RH Low",
   "description": "0-3 = speed 1-4.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 557,
   "documented": "0x022D",
   "name": "Heater K Coefficient",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 558,
   "documented": "0x022E",
   "name": "Heater Power limit mode",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Limit on RPM",
    "1": "None"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 559,
   "documented": "0x022F",
   "name": "Heater PID, P Coefficient",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 560,
   "documented": "0x0230",
   "name": "Heater PID, I Coefficient",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 561,
   "documented": "0x0231",
   "name": "Heater PID, D Coefficient",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 562,
   "documented": "0x0232",
   "name": "T4 value for Heater ON",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "°C",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 768,
   "documented": "0x0300",
   "name": "ON-OFF Command",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Off",
    "1": "On"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 769,
   "documented": "0x0301",
   "name": "Mode Command Manual",
   "description": "Write 1 for manual mode.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 770,
   "documented": "0x0302",
   "name": "Mode Command Holiday",
   "description": "Write 1 for holiday mode.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 771,
   "documented": "0x0303",
   "name": "Mode Command Party",
   "description": "Write 1 for party mode.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 772,
   "documented": "0x0304",
   "name": "Mode Command Auto",
   "description": "Write 1 for auto mode.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 773,
   "documented": "0x0305",
   "name": "Mode Command Program",
   "description": "Write 1 for program mode.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 774,
   "documented": "0x0306",
   "name": "Timer prog selection",
   "description": "0-7 = programs P1-P8.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 775,
   "documented": "0x0307",
   "name": "Mode Selection",
   "description": "Single-register mode select.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Holiday",
    "1": "Auto",
    "2": "Program",
    "3": "Manual",
    "4": "Party"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 776,
   "documented": "0x0308",
   "name": "Parameter reset",
   "description": "Write 0x005A (90) to restore factory parameters; reads 0.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 777,
   "documented": "0x0309",
   "name": "Manual speed",
   "description": "0-3 = speed 1-4.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 778,
   "documented": "0x030A",
   "name": "External RH Value",
   "description": "0xFFFF on read = not yet valid.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "%RH",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 779,
   "documented": "0x030B",
   "name": "External CO2 Value",
   "description": "0xFFFF on read = not yet valid.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "ppm",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 783,
   "documented": "0x030F",
   "name": "Set Holiday mode days",
   "description": "Write N (1-60) for N holiday days; reads days left.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "days",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 784,
   "documented": "0x0310",
   "name": "Reset Filter Counter",
   "description": "Write 1 to reset.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  }
 ],
 "integration": {
  "summary": "Read 0x0100-0x0114 for temperatures, state, fan speeds, alarms, CO2 and RH. Switch with 0x0300, pick the mode with 0x0307 and the manual speed with 0x0309; a BMS humidity or CO2 sensor can be fed through 0x030A/0x030B.",
  "minimum_registers": [
   {
    "table": "holding_register",
    "address": 256,
    "why": "T1 temperature"
   },
   {
    "table": "holding_register",
    "address": 261,
    "why": "Machine state and mode"
   },
   {
    "table": "holding_register",
    "address": 272,
    "why": "Alarms"
   },
   {
    "table": "holding_register",
    "address": 267,
    "why": "Fan 1 speed"
   },
   {
    "table": "holding_register",
    "address": 768,
    "why": "On/off command"
   },
   {
    "table": "holding_register",
    "address": 775,
    "why": "Mode selection"
   },
   {
    "table": "holding_register",
    "address": 777,
    "why": "Manual speed"
   },
   {
    "table": "holding_register",
    "address": 784,
    "why": "Filter counter reset"
   }
  ],
  "enable": "Set the Modbus address (1-60) on the ADDRESS DIP switches (DIP 2); on residential 0x52xx controllers DIP 1 switch 10 selects 9600 (off) or 38400 baud (on).",
  "watchdog": null,
  "quirks": [
   "Only holding registers (FC 03, 06, 16) are supported.",
   "A multi-register write is refused unless every register in the range is writable.",
   "Writing the Manual Speed parameter (0x0212) switches the unit to manual speed mode."
  ],
  "setup": [
   "RS485 on connector M19, 8 data bits, no parity, 1 stop bit."
  ],
  "gotchas": [
   "The Options/info register is printed as '0x0111F' in the manual; it is the register between 0x011E and 0x0120."
  ]
 },
 "page": "https://easymodbus.com/modbus-register-maps/vasco/sab-rvu",
 "address_note": "address = 0-based Modbus wire (PDU) address; documented = as printed in the source.",
 "note": "Re-typed from the manufacturer's public documentation (see source) and verified against it. Registers vary by firmware and options; verify against the live device before writing."
}