 "manufacturer": "Walchem",
 "manufacturer_slug": "walchem",
 "model": "W600 water treatment controller (Modbus/TCP)",
 "model_slug": "w600",
 "short_model": "W600",
 "aliases": [
  "W600 series"
 ],
 "equipment_type": "Water treatment controller (Sensor / controller)",
 "applies_to": "Walchem W600 controllers (software 3.01 and up) with the Modbus/TCP feature, per Modbus manual 180676.K. W900, Intuition-6 and Intuition-9 use the same type maps but different block start addresses.",
 "summary": "Walchem W-series and Intuition controllers run cooling tower, boiler and process water treatment. With the Modbus/TCP feature enabled they act as a Modbus TCP server on port 502. Data is laid out in 36-address blocks per object (system, network, each sensor input, digital input, relay); this map covers the system and network blocks and the key values of each I/O block, with 32-bit floats and integers sent low word first.",
 "transport": [
  "TCP"
 ],
 "defaults": {
  "unit_id": 1,
  "baud": null,
  "parity": null,
  "data_bits": null,
  "stop_bits": null,
  "tcp_port": 502
 },
 "addressing": {
  "convention": "1-based",
  "note": "Section 5.1 says the published addresses are 1-based while the packet is 0-based, so subtract 1 on the wire. Each object's address = its block start (xNNNN in the I/O channel map) + the index in its type-specific map; e.g. firmware version is block x0037 + index 2 = 30039/40039, wire address 38. The 'x' prefix stands for the table digit: the same address can be read as a holding register (FC3) or input register (FC4)."
 },
 "default_word_order": "CDAB",
 "firmware": "Controller software 3.01 and higher",
 "source": {
  "title": "Modbus Manual - Intuition-9 / Intuition-6 / W900 / W600",
  "doc_number": "180676.K",
  "revision_date": "2026-06",
  "url": "https://www.walchem.com/Literature/Controllers/Intuition/180676_W600_W900_Intuition_Modbus_Manual.pdf",
  "pages": "pp. 9-11 (encoding, addressing), pp. 12-17 (I/O channel maps), pp. 20-22, 25, 36-37 (type-specific maps), pp. 81-86 (status codes, alarm bitfields)"
 },
 "notes": [
  "32-bit integers and floats are sent least significant word first (CDAB) by default. The Remote Communications menu has an 'inverse' data format that swaps to high word first (ABCD); if values look wrong, check that setting.",
  "All 32-bit integers are unsigned; times are Unix seconds since 1970-01-01.",
  "Every address can be read as a holding register (FC3) or input register (FC4); this map lists them as holding registers. Booleans (the bold rows in the manual) can also be read as coils/discrete inputs at the same number.",
  "Sensor blocks use the general sensor map (all sensor types except Digital Sensor and Analog Input Flowmeter, which have their own maps). The full block is listed for the first sensor only; for the others only primary value, status and alarm bitfield are listed - the same indices apply to every sensor block.",
  "Digital input blocks are shown for the DI State type. Flow meter, counter, flow monitor and remote Modbus DI types use different maps (section 5.3.4).",
  "Relay entries use the indices common to every relay control mode (time on, total time, state, reset, HOA, status, alarm bitfield). Mode-specific set points live at other indices in section 5.3.6. Pulse relay maps (section 5.3.7) differ and are not included.",
  "Status register codes 37 and above are not listed in the values here; see section 5.4. Alarm bit 5 meanings vary by sensor or DI type.",
  "Analog outputs, virtual inputs and fields marked as W900/Intuition-9 only are left out.",
  "Block start addresses are from the W600 I/O channel map (p. 12): sensors 1-1..2-3 at x0577/x0613/x0649/x0865/x0901/x0937, digital inputs 1-6 at x0289..x0469, relays 1-6 at x8929..x9109."
 ],
 "registers": [
  {
   "table": "holding_register",
   "address": 36,
   "documented": "x0037",
   "name": "Controller time",
   "description": "Unix time (seconds since 1970).",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 1,
   "units": "s",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 38,
   "documented": "x0039",
   "name": "Controller firmware version",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 40,
   "documented": "x0041",
   "name": "Date of last data log",
   "description": "Unix time.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 1,
   "units": "s",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 42,
   "documented": "x0043",
   "name": "Controller processor temperature",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 1,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 44,
   "documented": "x0045",
   "name": "Network card temperature",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 1,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 48,
   "documented": "x0049",
   "name": "I/O card 1 temperature",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 1,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 50,
   "documented": "x0051",
   "name": "I/O card 2 temperature",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 1,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 62,
   "documented": "x0063",
   "name": "Battery power",
   "description": "Clock battery voltage.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 1,
   "units": "V",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 64,
   "documented": "x0065",
   "name": "+3.3 V supply",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 1,
   "units": "V",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 66,
   "documented": "x0067",
   "name": "+5 V supply",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 1,
   "units": "V",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 71,
   "documented": "x0072",
   "name": "System alarm bitfield",
   "description": "8 alarm flags in the low byte.",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "0": "Temperature alarm",
    "1": "Battery low",
    "2": "Invalid setting",
    "3": "Software version (add-on card needs update)",
    "4": "Board failure",
    "5": "Internal voltage out of range"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 144,
   "documented": "x0145",
   "name": "Fluent last data time",
   "description": "Unix time.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 1,
   "units": "s",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 146,
   "documented": "x0147",
   "name": "Fluent last configuration time",
   "description": "Unix time.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 1,
   "units": "s",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 148,
   "documented": "x0149",
   "name": "Fluent refresh rate",
   "description": "1-1440 minutes.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 1,
   "units": "min",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 150,
   "documented": "x0151",
   "name": "Fluent LiveConnect status",
   "description": "Status code.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Error",
    "1": "None",
    "2": "Sensor: Auto Cal",
    "3": "Sensor: User Cal",
    "4": "DI State: Open",
    "5": "DI State: Closed",
    "6": "DI Interlock: Active",
    "7": "DI Interlock: Inactive",
    "8": "Relay: On",
    "9": "Relay: Off",
    "11": "Output Interlocked",
    "12": "Output Forced On",
    "13": "Output Timeout",
    "14": "Output Input Error",
    "15": "Output Error",
    "16": "Output Hold",
    "17": "Output HOA: Auto On",
    "18": "Output HOA: Auto Off",
    "19": "Output HOA: Hand",
    "20": "Output HOA: Off",
    "21": "Output Deadband",
    "22": "Relay Timeout",
    "23": "Relay OK",
    "24": "Daily Max Timeout",
    "25": "Biocide: Prebleed",
    "26": "Biocide: Hold",
    "27": "Biocide: Add",
    "28": "Time Proportional: Off",
    "29": "Bleed & Feed: Bleeding",
    "30": "Bleed & Feed: Timeout",
    "31": "Intermittent Sampling: Wait",
    "32": "Intermittent Sampling: Sample",
    "33": "Intermittent Sampling: Hold",
    "34": "Intermittent Sampling: Bleed",
    "35": "Probe Wash: On",
    "36": "Probe Wash: Hold"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 151,
   "documented": "x0152",
   "name": "Web server status",
   "description": "Status code (93-95 = web server modes).",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Error",
    "1": "None",
    "2": "Sensor: Auto Cal",
    "3": "Sensor: User Cal",
    "4": "DI State: Open",
    "5": "DI State: Closed",
    "6": "DI Interlock: Active",
    "7": "DI Interlock: Inactive",
    "8": "Relay: On",
    "9": "Relay: Off",
    "11": "Output Interlocked",
    "12": "Output Forced On",
    "13": "Output Timeout",
    "14": "Output Input Error",
    "15": "Output Error",
    "16": "Output Hold",
    "17": "Output HOA: Auto On",
    "18": "Output HOA: Auto Off",
    "19": "Output HOA: Hand",
    "20": "Output HOA: Off",
    "21": "Output Deadband",
    "22": "Relay Timeout",
    "23": "Relay OK",
    "24": "Daily Max Timeout",
    "25": "Biocide: Prebleed",
    "26": "Biocide: Hold",
    "27": "Biocide: Add",
    "28": "Time Proportional: Off",
    "29": "Bleed & Feed: Bleeding",
    "30": "Bleed & Feed: Timeout",
    "31": "Intermittent Sampling: Wait",
    "32": "Intermittent Sampling: Sample",
    "33": "Intermittent Sampling: Hold",
    "34": "Intermittent Sampling: Bleed",
    "35": "Probe Wash: On",
    "36": "Probe Wash: Hold"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 179,
   "documented": "x0180",
   "name": "Network alarm bitfield",
   "description": "",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "0": "Web server failure",
    "1": "Fluent data comm",
    "2": "Fluent LiveConnect",
    "3": "WiFi error"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 288,
   "documented": "x0289",
   "name": "Digital input 1 last reset date",
   "description": "Unix time (DI State type).",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 1,
   "units": "s",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 290,
   "documented": "x0291",
   "name": "Digital input 1 total time",
   "description": "Accumulated time (DI State type).",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 1,
   "units": "s",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 292,
   "documented": "x0293",
   "name": "Digital input 1 cycle time",
   "description": "DI State type.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 1,
   "units": "s",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 320,
   "documented": "x0321",
   "name": "Digital input 1 reset total time",
   "description": "Write 1 to reset (DI State type).",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 321,
   "documented": "x0322",
   "name": "Digital input 1 state",
   "description": "DI State type.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Open",
    "1": "Closed"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 322,
   "documented": "x0323",
   "name": "Digital input 1 interlock state",
   "description": "DI State type.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Inactive",
    "1": "Active interlock"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 323,
   "documented": "x0324",
   "name": "Digital input 1 alarm bitfield",
   "description": "",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "0": "DI state alarm",
    "1": "Total",
    "2": "Total range",
    "3": "Input failure",
    "4": "Flow verify / Modbus alarm (type-specific)",
    "5": "Low flow",
    "6": "High flow"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 357,
   "documented": "x0358",
   "name": "Digital input 2 state",
   "description": "DI State type.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Open",
    "1": "Closed"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 359,
   "documented": "x0360",
   "name": "Digital input 2 alarm bitfield",
   "description": "",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "0": "DI state alarm",
    "1": "Total",
    "2": "Total range",
    "3": "Input failure",
    "4": "Flow verify / Modbus alarm (type-specific)",
    "5": "Low flow",
    "6": "High flow"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 393,
   "documented": "x0394",
   "name": "Digital input 3 state",
   "description": "DI State type.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Open",
    "1": "Closed"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 395,
   "documented": "x0396",
   "name": "Digital input 3 alarm bitfield",
   "description": "",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "0": "DI state alarm",
    "1": "Total",
    "2": "Total range",
    "3": "Input failure",
    "4": "Flow verify / Modbus alarm (type-specific)",
    "5": "Low flow",
    "6": "High flow"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 429,
   "documented": "x0430",
   "name": "Digital input 4 state",
   "description": "DI State type.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Open",
    "1": "Closed"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 431,
   "documented": "x0432",
   "name": "Digital input 4 alarm bitfield",
   "description": "",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "0": "DI state alarm",
    "1": "Total",
    "2": "Total range",
    "3": "Input failure",
    "4": "Flow verify / Modbus alarm (type-specific)",
    "5": "Low flow",
    "6": "High flow"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 465,
   "documented": "x0466",
   "name": "Digital input 5 state",
   "description": "DI State type.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Open",
    "1": "Closed"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 467,
   "documented": "x0468",
   "name": "Digital input 5 alarm bitfield",
   "description": "",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "0": "DI state alarm",
    "1": "Total",
    "2": "Total range",
    "3": "Input failure",
    "4": "Flow verify / Modbus alarm (type-specific)",
    "5": "Low flow",
    "6": "High flow"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 501,
   "documented": "x0502",
   "name": "Digital input 6 state",
   "description": "DI State type.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Open",
    "1": "Closed"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 503,
   "documented": "x0504",
   "name": "Digital input 6 alarm bitfield",
   "description": "",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "0": "DI state alarm",
    "1": "Total",
    "2": "Total range",
    "3": "Input failure",
    "4": "Flow verify / Modbus alarm (type-specific)",
    "5": "Low flow",
    "6": "High flow"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 576,
   "documented": "x0577",
   "name": "Sensor 1-1 primary value",
   "description": "Measured value in the sensor's configured units.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 578,
   "documented": "x0579",
   "name": "Sensor 1-1 primary raw value",
   "description": "Raw signal: uS/cm, mV, mA or ohm depending on sensor type.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 580,
   "documented": "x0581",
   "name": "Sensor 1-1 last calibration date",
   "description": "Unix time.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 1,
   "units": "s",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 586,
   "documented": "x0587",
   "name": "Sensor 1-1 deadband",
   "description": "Alarm deadband in sensor units.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 588,
   "documented": "x0589",
   "name": "Sensor 1-1 smoothing factor",
   "description": "0-90 %.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 1,
   "units": "%",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 590,
   "documented": "x0591",
   "name": "Sensor 1-1 LoLo alarm setpoint",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 592,
   "documented": "x0593",
   "name": "Sensor 1-1 Low alarm setpoint",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 594,
   "documented": "x0595",
   "name": "Sensor 1-1 High alarm setpoint",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 596,
   "documented": "x0597",
   "name": "Sensor 1-1 HiHi alarm setpoint",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 604,
   "documented": "x0605",
   "name": "Sensor 1-1 Low alarm",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Inactive",
    "1": "Alarm active"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 605,
   "documented": "x0606",
   "name": "Sensor 1-1 High alarm",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Inactive",
    "1": "Alarm active"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 606,
   "documented": "x0607",
   "name": "Sensor 1-1 LoLo alarm",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Inactive",
    "1": "Alarm active"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 607,
   "documented": "x0608",
   "name": "Sensor 1-1 HiHi alarm",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Inactive",
    "1": "Alarm active"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 608,
   "documented": "x0609",
   "name": "Sensor 1-1 calibration required",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Inactive",
    "1": "Alarm active"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 609,
   "documented": "x0610",
   "name": "Sensor 1-1 input failure",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Inactive",
    "1": "Alarm active"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 610,
   "documented": "x0611",
   "name": "Sensor 1-1 status",
   "description": "Status code.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Error",
    "1": "None",
    "2": "Sensor: Auto Cal",
    "3": "Sensor: User Cal",
    "4": "DI State: Open",
    "5": "DI State: Closed",
    "6": "DI Interlock: Active",
    "7": "DI Interlock: Inactive",
    "8": "Relay: On",
    "9": "Relay: Off",
    "11": "Output Interlocked",
    "12": "Output Forced On",
    "13": "Output Timeout",
    "14": "Output Input Error",
    "15": "Output Error",
    "16": "Output Hold",
    "17": "Output HOA: Auto On",
    "18": "Output HOA: Auto Off",
    "19": "Output HOA: Hand",
    "20": "Output HOA: Off",
    "21": "Output Deadband",
    "22": "Relay Timeout",
    "23": "Relay OK",
    "24": "Daily Max Timeout",
    "25": "Biocide: Prebleed",
    "26": "Biocide: Hold",
    "27": "Biocide: Add",
    "28": "Time Proportional: Off",
    "29": "Bleed & Feed: Bleeding",
    "30": "Bleed & Feed: Timeout",
    "31": "Intermittent Sampling: Wait",
    "32": "Intermittent Sampling: Sample",
    "33": "Intermittent Sampling: Hold",
    "34": "Intermittent Sampling: Bleed",
    "35": "Probe Wash: On",
    "36": "Probe Wash: Hold"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 611,
   "documented": "x0612",
   "name": "Sensor 1-1 alarm bitfield",
   "description": "",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "0": "Low",
    "1": "High",
    "2": "Low Low",
    "3": "High High",
    "4": "Type-specific (replace electrode / total / PV2 low)",
    "5": "PV2 high (digital sensors only)",
    "6": "Input failure",
    "7": "Calibration required"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 612,
   "documented": "x0613",
   "name": "Sensor 1-2 primary value",
   "description": "Measured value in the sensor's configured units.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 646,
   "documented": "x0647",
   "name": "Sensor 1-2 status",
   "description": "Status code.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Error",
    "1": "None",
    "2": "Sensor: Auto Cal",
    "3": "Sensor: User Cal",
    "4": "DI State: Open",
    "5": "DI State: Closed",
    "6": "DI Interlock: Active",
    "7": "DI Interlock: Inactive",
    "8": "Relay: On",
    "9": "Relay: Off",
    "11": "Output Interlocked",
    "12": "Output Forced On",
    "13": "Output Timeout",
    "14": "Output Input Error",
    "15": "Output Error",
    "16": "Output Hold",
    "17": "Output HOA: Auto On",
    "18": "Output HOA: Auto Off",
    "19": "Output HOA: Hand",
    "20": "Output HOA: Off",
    "21": "Output Deadband",
    "22": "Relay Timeout",
    "23": "Relay OK",
    "24": "Daily Max Timeout",
    "25": "Biocide: Prebleed",
    "26": "Biocide: Hold",
    "27": "Biocide: Add",
    "28": "Time Proportional: Off",
    "29": "Bleed & Feed: Bleeding",
    "30": "Bleed & Feed: Timeout",
    "31": "Intermittent Sampling: Wait",
    "32": "Intermittent Sampling: Sample",
    "33": "Intermittent Sampling: Hold",
    "34": "Intermittent Sampling: Bleed",
    "35": "Probe Wash: On",
    "36": "Probe Wash: Hold"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 647,
   "documented": "x0648",
   "name": "Sensor 1-2 alarm bitfield",
   "description": "",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "0": "Low",
    "1": "High",
    "2": "Low Low",
    "3": "High High",
    "4": "Type-specific (replace electrode / total / PV2 low)",
    "5": "PV2 high (digital sensors only)",
    "6": "Input failure",
    "7": "Calibration required"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 648,
   "documented": "x0649",
   "name": "Sensor 1-3 primary value",
   "description": "Measured value in the sensor's configured units.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 682,
   "documented": "x0683",
   "name": "Sensor 1-3 status",
   "description": "Status code.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Error",
    "1": "None",
    "2": "Sensor: Auto Cal",
    "3": "Sensor: User Cal",
    "4": "DI State: Open",
    "5": "DI State: Closed",
    "6": "DI Interlock: Active",
    "7": "DI Interlock: Inactive",
    "8": "Relay: On",
    "9": "Relay: Off",
    "11": "Output Interlocked",
    "12": "Output Forced On",
    "13": "Output Timeout",
    "14": "Output Input Error",
    "15": "Output Error",
    "16": "Output Hold",
    "17": "Output HOA: Auto On",
    "18": "Output HOA: Auto Off",
    "19": "Output HOA: Hand",
    "20": "Output HOA: Off",
    "21": "Output Deadband",
    "22": "Relay Timeout",
    "23": "Relay OK",
    "24": "Daily Max Timeout",
    "25": "Biocide: Prebleed",
    "26": "Biocide: Hold",
    "27": "Biocide: Add",
    "28": "Time Proportional: Off",
    "29": "Bleed & Feed: Bleeding",
    "30": "Bleed & Feed: Timeout",
    "31": "Intermittent Sampling: Wait",
    "32": "Intermittent Sampling: Sample",
    "33": "Intermittent Sampling: Hold",
    "34": "Intermittent Sampling: Bleed",
    "35": "Probe Wash: On",
    "36": "Probe Wash: Hold"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 683,
   "documented": "x0684",
   "name": "Sensor 1-3 alarm bitfield",
   "description": "",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "0": "Low",
    "1": "High",
    "2": "Low Low",
    "3": "High High",
    "4": "Type-specific (replace electrode / total / PV2 low)",
    "5": "PV2 high (digital sensors only)",
    "6": "Input failure",
    "7": "Calibration required"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 864,
   "documented": "x0865",
   "name": "Sensor 2-1 primary value",
   "description": "Measured value in the sensor's configured units.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 898,
   "documented": "x0899",
   "name": "Sensor 2-1 status",
   "description": "Status code.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Error",
    "1": "None",
    "2": "Sensor: Auto Cal",
    "3": "Sensor: User Cal",
    "4": "DI State: Open",
    "5": "DI State: Closed",
    "6": "DI Interlock: Active",
    "7": "DI Interlock: Inactive",
    "8": "Relay: On",
    "9": "Relay: Off",
    "11": "Output Interlocked",
    "12": "Output Forced On",
    "13": "Output Timeout",
    "14": "Output Input Error",
    "15": "Output Error",
    "16": "Output Hold",
    "17": "Output HOA: Auto On",
    "18": "Output HOA: Auto Off",
    "19": "Output HOA: Hand",
    "20": "Output HOA: Off",
    "21": "Output Deadband",
    "22": "Relay Timeout",
    "23": "Relay OK",
    "24": "Daily Max Timeout",
    "25": "Biocide: Prebleed",
    "26": "Biocide: Hold",
    "27": "Biocide: Add",
    "28": "Time Proportional: Off",
    "29": "Bleed & Feed: Bleeding",
    "30": "Bleed & Feed: Timeout",
    "31": "Intermittent Sampling: Wait",
    "32": "Intermittent Sampling: Sample",
    "33": "Intermittent Sampling: Hold",
    "34": "Intermittent Sampling: Bleed",
    "35": "Probe Wash: On",
    "36": "Probe Wash: Hold"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 899,
   "documented": "x0900",
   "name": "Sensor 2-1 alarm bitfield",
   "description": "",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "0": "Low",
    "1": "High",
    "2": "Low Low",
    "3": "High High",
    "4": "Type-specific (replace electrode / total / PV2 low)",
    "5": "PV2 high (digital sensors only)",
    "6": "Input failure",
    "7": "Calibration required"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 900,
   "documented": "x0901",
   "name": "Sensor 2-2 primary value",
   "description": "Measured value in the sensor's configured units.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 934,
   "documented": "x0935",
   "name": "Sensor 2-2 status",
   "description": "Status code.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Error",
    "1": "None",
    "2": "Sensor: Auto Cal",
    "3": "Sensor: User Cal",
    "4": "DI State: Open",
    "5": "DI State: Closed",
    "6": "DI Interlock: Active",
    "7": "DI Interlock: Inactive",
    "8": "Relay: On",
    "9": "Relay: Off",
    "11": "Output Interlocked",
    "12": "Output Forced On",
    "13": "Output Timeout",
    "14": "Output Input Error",
    "15": "Output Error",
    "16": "Output Hold",
    "17": "Output HOA: Auto On",
    "18": "Output HOA: Auto Off",
    "19": "Output HOA: Hand",
    "20": "Output HOA: Off",
    "21": "Output Deadband",
    "22": "Relay Timeout",
    "23": "Relay OK",
    "24": "Daily Max Timeout",
    "25": "Biocide: Prebleed",
    "26": "Biocide: Hold",
    "27": "Biocide: Add",
    "28": "Time Proportional: Off",
    "29": "Bleed & Feed: Bleeding",
    "30": "Bleed & Feed: Timeout",
    "31": "Intermittent Sampling: Wait",
    "32": "Intermittent Sampling: Sample",
    "33": "Intermittent Sampling: Hold",
    "34": "Intermittent Sampling: Bleed",
    "35": "Probe Wash: On",
    "36": "Probe Wash: Hold"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 935,
   "documented": "x0936",
   "name": "Sensor 2-2 alarm bitfield",
   "description": "",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "0": "Low",
    "1": "High",
    "2": "Low Low",
    "3": "High High",
    "4": "Type-specific (replace electrode / total / PV2 low)",
    "5": "PV2 high (digital sensors only)",
    "6": "Input failure",
    "7": "Calibration required"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 936,
   "documented": "x0937",
   "name": "Sensor 2-3 primary value",
   "description": "Measured value in the sensor's configured units.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 970,
   "documented": "x0971",
   "name": "Sensor 2-3 status",
   "description": "Status code.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Error",
    "1": "None",
    "2": "Sensor: Auto Cal",
    "3": "Sensor: User Cal",
    "4": "DI State: Open",
    "5": "DI State: Closed",
    "6": "DI Interlock: Active",
    "7": "DI Interlock: Inactive",
    "8": "Relay: On",
    "9": "Relay: Off",
    "11": "Output Interlocked",
    "12": "Output Forced On",
    "13": "Output Timeout",
    "14": "Output Input Error",
    "15": "Output Error",
    "16": "Output Hold",
    "17": "Output HOA: Auto On",
    "18": "Output HOA: Auto Off",
    "19": "Output HOA: Hand",
    "20": "Output HOA: Off",
    "21": "Output Deadband",
    "22": "Relay Timeout",
    "23": "Relay OK",
    "24": "Daily Max Timeout",
    "25": "Biocide: Prebleed",
    "26": "Biocide: Hold",
    "27": "Biocide: Add",
    "28": "Time Proportional: Off",
    "29": "Bleed & Feed: Bleeding",
    "30": "Bleed & Feed: Timeout",
    "31": "Intermittent Sampling: Wait",
    "32": "Intermittent Sampling: Sample",
    "33": "Intermittent Sampling: Hold",
    "34": "Intermittent Sampling: Bleed",
    "35": "Probe Wash: On",
    "36": "Probe Wash: Hold"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 971,
   "documented": "x0972",
   "name": "Sensor 2-3 alarm bitfield",
   "description": "",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "0": "Low",
    "1": "High",
    "2": "Low Low",
    "3": "High High",
    "4": "Type-specific (replace electrode / total / PV2 low)",
    "5": "PV2 high (digital sensors only)",
    "6": "Input failure",
    "7": "Calibration required"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8928,
   "documented": "x8929",
   "name": "Relay 1 time on",
   "description": "Current on time.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 1,
   "units": "s",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8930,
   "documented": "x8931",
   "name": "Relay 1 total time",
   "description": "Accumulated on time.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 1,
   "units": "s",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8959,
   "documented": "x8960",
   "name": "Relay 1 state",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Off",
    "1": "On"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8960,
   "documented": "x8961",
   "name": "Relay 1 reset time total",
   "description": "Write 1 to reset.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8961,
   "documented": "x8962",
   "name": "Relay 1 HOA setting",
   "description": "Hand / Off / Auto.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Hand",
    "1": "Off",
    "2": "Auto"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8962,
   "documented": "x8963",
   "name": "Relay 1 status",
   "description": "Status code.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Error",
    "1": "None",
    "2": "Sensor: Auto Cal",
    "3": "Sensor: User Cal",
    "4": "DI State: Open",
    "5": "DI State: Closed",
    "6": "DI Interlock: Active",
    "7": "DI Interlock: Inactive",
    "8": "Relay: On",
    "9": "Relay: Off",
    "11": "Output Interlocked",
    "12": "Output Forced On",
    "13": "Output Timeout",
    "14": "Output Input Error",
    "15": "Output Error",
    "16": "Output Hold",
    "17": "Output HOA: Auto On",
    "18": "Output HOA: Auto Off",
    "19": "Output HOA: Hand",
    "20": "Output HOA: Off",
    "21": "Output Deadband",
    "22": "Relay Timeout",
    "23": "Relay OK",
    "24": "Daily Max Timeout",
    "25": "Biocide: Prebleed",
    "26": "Biocide: Hold",
    "27": "Biocide: Add",
    "28": "Time Proportional: Off",
    "29": "Bleed & Feed: Bleeding",
    "30": "Bleed & Feed: Timeout",
    "31": "Intermittent Sampling: Wait",
    "32": "Intermittent Sampling: Sample",
    "33": "Intermittent Sampling: Hold",
    "34": "Intermittent Sampling: Bleed",
    "35": "Probe Wash: On",
    "36": "Probe Wash: Hold"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8963,
   "documented": "x8964",
   "name": "Relay 1 alarm bitfield",
   "description": "",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "0": "Output timeout",
    "1": "Relay event skipped / turnover limit",
    "2": "Control failure",
    "3": "State alarm",
    "4": "Daily max timeout"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8995,
   "documented": "x8996",
   "name": "Relay 2 state",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Off",
    "1": "On"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8997,
   "documented": "x8998",
   "name": "Relay 2 HOA setting",
   "description": "Hand / Off / Auto.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Hand",
    "1": "Off",
    "2": "Auto"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8998,
   "documented": "x8999",
   "name": "Relay 2 status",
   "description": "Status code.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Error",
    "1": "None",
    "2": "Sensor: Auto Cal",
    "3": "Sensor: User Cal",
    "4": "DI State: Open",
    "5": "DI State: Closed",
    "6": "DI Interlock: Active",
    "7": "DI Interlock: Inactive",
    "8": "Relay: On",
    "9": "Relay: Off",
    "11": "Output Interlocked",
    "12": "Output Forced On",
    "13": "Output Timeout",
    "14": "Output Input Error",
    "15": "Output Error",
    "16": "Output Hold",
    "17": "Output HOA: Auto On",
    "18": "Output HOA: Auto Off",
    "19": "Output HOA: Hand",
    "20": "Output HOA: Off",
    "21": "Output Deadband",
    "22": "Relay Timeout",
    "23": "Relay OK",
    "24": "Daily Max Timeout",
    "25": "Biocide: Prebleed",
    "26": "Biocide: Hold",
    "27": "Biocide: Add",
    "28": "Time Proportional: Off",
    "29": "Bleed & Feed: Bleeding",
    "30": "Bleed & Feed: Timeout",
    "31": "Intermittent Sampling: Wait",
    "32": "Intermittent Sampling: Sample",
    "33": "Intermittent Sampling: Hold",
    "34": "Intermittent Sampling: Bleed",
    "35": "Probe Wash: On",
    "36": "Probe Wash: Hold"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8999,
   "documented": "x9000",
   "name": "Relay 2 alarm bitfield",
   "description": "",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "0": "Output timeout",
    "1": "Relay event skipped / turnover limit",
    "2": "Control failure",
    "3": "State alarm",
    "4": "Daily max timeout"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 9031,
   "documented": "x9032",
   "name": "Relay 3 state",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Off",
    "1": "On"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 9033,
   "documented": "x9034",
   "name": "Relay 3 HOA setting",
   "description": "Hand / Off / Auto.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Hand",
    "1": "Off",
    "2": "Auto"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 9034,
   "documented": "x9035",
   "name": "Relay 3 status",
   "description": "Status code.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Error",
    "1": "None",
    "2": "Sensor: Auto Cal",
    "3": "Sensor: User Cal",
    "4": "DI State: Open",
    "5": "DI State: Closed",
    "6": "DI Interlock: Active",
    "7": "DI Interlock: Inactive",
    "8": "Relay: On",
    "9": "Relay: Off",
    "11": "Output Interlocked",
    "12": "Output Forced On",
    "13": "Output Timeout",
    "14": "Output Input Error",
    "15": "Output Error",
    "16": "Output Hold",
    "17": "Output HOA: Auto On",
    "18": "Output HOA: Auto Off",
    "19": "Output HOA: Hand",
    "20": "Output HOA: Off",
    "21": "Output Deadband",
    "22": "Relay Timeout",
    "23": "Relay OK",
    "24": "Daily Max Timeout",
    "25": "Biocide: Prebleed",
    "26": "Biocide: Hold",
    "27": "Biocide: Add",
    "28": "Time Proportional: Off",
    "29": "Bleed & Feed: Bleeding",
    "30": "Bleed & Feed: Timeout",
    "31": "Intermittent Sampling: Wait",
    "32": "Intermittent Sampling: Sample",
    "33": "Intermittent Sampling: Hold",
    "34": "Intermittent Sampling: Bleed",
    "35": "Probe Wash: On",
    "36": "Probe Wash: Hold"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 9035,
   "documented": "x9036",
   "name": "Relay 3 alarm bitfield",
   "description": "",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "0": "Output timeout",
    "1": "Relay event skipped / turnover limit",
    "2": "Control failure",
    "3": "State alarm",
    "4": "Daily max timeout"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 9067,
   "documented": "x9068",
   "name": "Relay 4 state",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Off",
    "1": "On"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 9069,
   "documented": "x9070",
   "name": "Relay 4 HOA setting",
   "description": "Hand / Off / Auto.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Hand",
    "1": "Off",
    "2": "Auto"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 9070,
   "documented": "x9071",
   "name": "Relay 4 status",
   "description": "Status code.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Error",
    "1": "None",
    "2": "Sensor: Auto Cal",
    "3": "Sensor: User Cal",
    "4": "DI State: Open",
    "5": "DI State: Closed",
    "6": "DI Interlock: Active",
    "7": "DI Interlock: Inactive",
    "8": "Relay: On",
    "9": "Relay: Off",
    "11": "Output Interlocked",
    "12": "Output Forced On",
    "13": "Output Timeout",
    "14": "Output Input Error",
    "15": "Output Error",
    "16": "Output Hold",
    "17": "Output HOA: Auto On",
    "18": "Output HOA: Auto Off",
    "19": "Output HOA: Hand",
    "20": "Output HOA: Off",
    "21": "Output Deadband",
    "22": "Relay Timeout",
    "23": "Relay OK",
    "24": "Daily Max Timeout",
    "25": "Biocide: Prebleed",
    "26": "Biocide: Hold",
    "27": "Biocide: Add",
    "28": "Time Proportional: Off",
    "29": "Bleed & Feed: Bleeding",
    "30": "Bleed & Feed: Timeout",
    "31": "Intermittent Sampling: Wait",
    "32": "Intermittent Sampling: Sample",
    "33": "Intermittent Sampling: Hold",
    "34": "Intermittent Sampling: Bleed",
    "35": "Probe Wash: On",
    "36": "Probe Wash: Hold"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 9071,
   "documented": "x9072",
   "name": "Relay 4 alarm bitfield",
   "description": "",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "0": "Output timeout",
    "1": "Relay event skipped / turnover limit",
    "2": "Control failure",
    "3": "State alarm",
    "4": "Daily max timeout"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 9103,
   "documented": "x9104",
   "name": "Relay 5 state",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Off",
    "1": "On"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 9105,
   "documented": "x9106",
   "name": "Relay 5 HOA setting",
   "description": "Hand / Off / Auto.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Hand",
    "1": "Off",
    "2": "Auto"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 9106,
   "documented": "x9107",
   "name": "Relay 5 status",
   "description": "Status code.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Error",
    "1": "None",
    "2": "Sensor: Auto Cal",
    "3": "Sensor: User Cal",
    "4": "DI State: Open",
    "5": "DI State: Closed",
    "6": "DI Interlock: Active",
    "7": "DI Interlock: Inactive",
    "8": "Relay: On",
    "9": "Relay: Off",
    "11": "Output Interlocked",
    "12": "Output Forced On",
    "13": "Output Timeout",
    "14": "Output Input Error",
    "15": "Output Error",
    "16": "Output Hold",
    "17": "Output HOA: Auto On",
    "18": "Output HOA: Auto Off",
    "19": "Output HOA: Hand",
    "20": "Output HOA: Off",
    "21": "Output Deadband",
    "22": "Relay Timeout",
    "23": "Relay OK",
    "24": "Daily Max Timeout",
    "25": "Biocide: Prebleed",
    "26": "Biocide: Hold",
    "27": "Biocide: Add",
    "28": "Time Proportional: Off",
    "29": "Bleed & Feed: Bleeding",
    "30": "Bleed & Feed: Timeout",
    "31": "Intermittent Sampling: Wait",
    "32": "Intermittent Sampling: Sample",
    "33": "Intermittent Sampling: Hold",
    "34": "Intermittent Sampling: Bleed",
    "35": "Probe Wash: On",
    "36": "Probe Wash: Hold"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 9107,
   "documented": "x9108",
   "name": "Relay 5 alarm bitfield",
   "description": "",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "0": "Output timeout",
    "1": "Relay event skipped / turnover limit",
    "2": "Control failure",
    "3": "State alarm",
    "4": "Daily max timeout"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 9139,
   "documented": "x9140",
   "name": "Relay 6 state",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Off",
    "1": "On"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 9141,
   "documented": "x9142",
   "name": "Relay 6 HOA setting",
   "description": "Hand / Off / Auto.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Hand",
    "1": "Off",
    "2": "Auto"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 9142,
   "documented": "x9143",
   "name": "Relay 6 status",
   "description": "Status code.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Error",
    "1": "None",
    "2": "Sensor: Auto Cal",
    "3": "Sensor: User Cal",
    "4": "DI State: Open",
    "5": "DI State: Closed",
    "6": "DI Interlock: Active",
    "7": "DI Interlock: Inactive",
    "8": "Relay: On",
    "9": "Relay: Off",
    "11": "Output Interlocked",
    "12": "Output Forced On",
    "13": "Output Timeout",
    "14": "Output Input Error",
    "15": "Output Error",
    "16": "Output Hold",
    "17": "Output HOA: Auto On",
    "18": "Output HOA: Auto Off",
    "19": "Output HOA: Hand",
    "20": "Output HOA: Off",
    "21": "Output Deadband",
    "22": "Relay Timeout",
    "23": "Relay OK",
    "24": "Daily Max Timeout",
    "25": "Biocide: Prebleed",
    "26": "Biocide: Hold",
    "27": "Biocide: Add",
    "28": "Time Proportional: Off",
    "29": "Bleed & Feed: Bleeding",
    "30": "Bleed & Feed: Timeout",
    "31": "Intermittent Sampling: Wait",
    "32": "Intermittent Sampling: Sample",
    "33": "Intermittent Sampling: Hold",
    "34": "Intermittent Sampling: Bleed",
    "35": "Probe Wash: On",
    "36": "Probe Wash: Hold"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 9143,
   "documented": "x9144",
   "name": "Relay 6 alarm bitfield",
   "description": "",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "0": "Output timeout",
    "1": "Relay event skipped / turnover limit",
    "2": "Control failure",
    "3": "State alarm",
    "4": "Daily max timeout"
   },
   "offset": 0
  }
 ],
 "integration": {
  "summary": "Enable Modbus/TCP in the controller's Remote Communications menu, connect to port 502 with any unit ID except 0, and read values as CDAB 32-bit pairs. Poll no faster than every 5 s.",
  "minimum_registers": [
   {
    "table": "holding_register",
    "address": 36,
    "why": "Controller time (proves comms)"
   },
   {
    "table": "holding_register",
    "address": 576,
    "why": "Sensor primary value"
   },
   {
    "table": "holding_register",
    "address": 610,
    "why": "Sensor status code"
   },
   {
    "table": "holding_register",
    "address": 611,
    "why": "Sensor alarm bitfield"
   },
   {
    "table": "holding_register",
    "address": 321,
    "why": "Digital input 1 state"
   },
   {
    "table": "holding_register",
    "address": 8959,
    "why": "Relay 1 state"
   },
   {
    "table": "holding_register",
    "address": 8961,
    "why": "Relay 1 HOA setting"
   },
   {
    "table": "holding_register",
    "address": 71,
    "why": "System alarm bitfield"
   }
  ],
  "enable": "Modbus/TCP is a feature of the controller; enable it and set the port and data format (normal or inverse word order) in the Remote Communications menu. A 'Verbose Logging' option there logs every message for commissioning and turns itself off at restart.",
  "watchdog": null,
  "quirks": [
   "Addresses are 1-based: subtract 1 for the wire address.",
   "Floats and 32-bit integers are low word first (CDAB) unless 'inverse' format is selected.",
   "Unit ID 0 is treated as broadcast: the request is processed but no reply is sent.",
   "FC1/FC2 and FC3/FC4 are interchangeable on reads."
  ],
  "setup": [
   "Network address, port (default 502) and data format are set on the controller's communications menus.",
   "Read up to 125 registers per request."
  ],
  "gotchas": [
   "Polling faster than once every 5 seconds is unsupported.",
   "Block start addresses depend on the controller model and on which I/O cards are fitted; confirm the I/O channel map for your unit.",
   "Modbus RTU is not supported; serial masters need a TCP gateway."
  ]
 },
 "page": "https://easymodbus.com/modbus-register-maps/walchem/w600",
 "address_note": "address = 0-based Modbus wire (PDU) address; documented = as printed in the source.",
 "note": "Re-typed from the manufacturer's public documentation (see source) and verified against it. Registers vary by firmware and options; verify against the live device before writing."
}