 "manufacturer": "Watlow",
 "manufacturer_slug": "watlow",
 "model": "EZ-ZONE PM PID / limit / integrated controller (Modbus RTU)",
 "model_slug": "ez-zone-pm",
 "short_model": "EZ-ZONE PM",
 "aliases": [
  "EZ-ZONE PM",
  "EZ-ZONE PM Limit",
  "EZ-ZONE PM Integrated"
 ],
 "equipment_type": "Thermostat / temperature controller",
 "applies_to": "Watlow EZ-ZONE PM panel-mount controllers (PID, limit and integrated models) with Modbus RTU, per communications manual 0600-0056-0000 Rev. B (Nov 2007).",
 "summary": "The EZ-ZONE PM is Watlow's panel-mount PID and limit controller family. With the Modbus RTU option every parameter has a fixed register: floats take two registers and enumerated settings use Watlow's numeric codes (for example 106 = Yes). This map covers the operations values an integrator needs: input process values and errors, loop set points, control mode, PID terms, output power, autotune, event and limit states, alarm 1 set points and status, and the basic communications settings. The full parameter list is in the manual.",
 "transport": [
  "RTU"
 ],
 "defaults": {
  "unit_id": 1,
  "baud": null,
  "parity": "None",
  "data_bits": 8,
  "stop_bits": 1,
  "tcp_port": null
 },
 "addressing": {
  "convention": "0-based",
  "note": "The manual lists 'relative' Modbus registers (less the 40,001 offset) and sends them unchanged: the worked read of analog input 1 sends 360 as hex 01 68. In a Modicon-style tool, 360 is 40361."
 },
 "default_word_order": "CDAB",
 "firmware": null,
 "source": {
  "title": "EZ-ZONE PM Controller Communications Manual",
  "doc_number": "0600-0056-0000 Rev. B",
  "revision_date": "2007-11",
  "url": "https://www.instrumart.com/assets/ezzone-pm_communicationsmanual.pdf",
  "pages": "pp. 11-13 (32-bit read example and frame), pp. 56-61 (operations page), p. 85 (communications menu)",
  "unofficial": true
 },
 "notes": [
  "Watlow does not appear to host this communications manual publicly; the copy linked is a distributor (Instrumart) copy of the unaltered Watlow manual, Rev. B from 2007.",
  "Floats are IEEE 754 in two registers with the low word first by default (CDAB): register 360 holds the low word and 361 the high word, as the manual's example shows. The order can be changed to high-low in the Communications menu; this map assumes the default.",
  "Integers are unsigned 16-bit. Enumerated parameters use Watlow codes, e.g. 59 = No, 106 = Yes, 62 = Off.",
  "Temperatures follow the display units chosen for the communications port (°F by default).",
  "Only a subset is listed (operations-page values, alarm 1 and comms basics); alarms 2-4 follow the same pattern at other registers given in the manual, as do setup and profile parameters.",
  "Left out: the word-order and non-volatile-save registers, which the manual prints with the same address (2494); the baud-rate register, whose value codes are not printed. The manual gives the default serial format as 9,600 baud in its footnotes but lists 38,400 as the baud-rate default, so the default baud is left blank."
 ],
 "registers": [
  {
   "table": "holding_register",
   "address": 360,
   "documented": "360",
   "name": "Analog input 1 process value",
   "description": "In the display units set for this channel (°F default).",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 362,
   "documented": "362",
   "name": "Analog input 1 error status",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": {
    "61": "None",
    "65": "Open",
    "127": "Shorted",
    "140": "Measurement error",
    "139": "Bad calibration data",
    "9": "Ambient error",
    "141": "RTD lead resistance error"
   },
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 382,
   "documented": "382",
   "name": "Analog input 1 calibration offset",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 440,
   "documented": "440",
   "name": "Analog input 2 process value",
   "description": "Marked for integrated (Int.) models only.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 442,
   "documented": "442",
   "name": "Analog input 2 error status",
   "description": "Marked for integrated (Int.) models only.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": {
    "61": "None",
    "65": "Open",
    "127": "Shorted",
    "140": "Measurement error",
    "139": "Bad calibration data",
    "9": "Ambient error",
    "141": "RTD lead resistance error"
   },
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 446,
   "documented": "446",
   "name": "Ambient temperature, input 2",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 462,
   "documented": "462",
   "name": "Analog input 2 calibration offset",
   "description": "Marked for integrated (Int.) models only.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 690,
   "documented": "690",
   "name": "Limit state",
   "description": "Limit models.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": {
    "62": "Off",
    "61": "None",
    "51": "Limit high",
    "52": "Limit low",
    "28": "Error"
   },
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 1328,
   "documented": "1328",
   "name": "Event 1 status",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": {
    "41": "Inactive",
    "5": "Active"
   },
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 1348,
   "documented": "1348",
   "name": "Event 2 status",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": {
    "41": "Inactive",
    "5": "Active"
   },
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 1368,
   "documented": "1368",
   "name": "EZ key status",
   "description": "The manual describes it as the status of event 3.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": {
    "41": "Inactive",
    "5": "Active"
   },
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 1480,
   "documented": "1480",
   "name": "Alarm 1 high set point",
   "description": "Process value or deviation, per alarm type.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 1482,
   "documented": "1482",
   "name": "Alarm 1 low set point",
   "description": "Process value or deviation, per alarm type.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 1498,
   "documented": "1498",
   "name": "Alarm 1 latched status",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": {
    "59": "No",
    "106": "Yes"
   },
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 1500,
   "documented": "1500",
   "name": "Alarm 1 silenced status",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": {
    "59": "No",
    "106": "Yes"
   },
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 1502,
   "documented": "1502",
   "name": "Alarm 1 clearable status",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": {
    "59": "No",
    "106": "Yes"
   },
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 1504,
   "documented": "1504",
   "name": "Alarm 1 clear request",
   "description": "Write 0 to clear the alarm state.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "W",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 1506,
   "documented": "1506",
   "name": "Alarm 1 silence request",
   "description": "Write 0 to this request register.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "W",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 1516,
   "documented": "1516",
   "name": "Alarm 1 working process value",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 1518,
   "documented": "1518",
   "name": "Alarm 1 working set point",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 1880,
   "documented": "1880",
   "name": "Control mode",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "62": "Off",
    "10": "Auto (closed loop)",
    "54": "Manual (open loop)"
   },
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 1890,
   "documented": "1890",
   "name": "Heat proportional band",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 1892,
   "documented": "1892",
   "name": "Cool proportional band",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 1894,
   "documented": "1894",
   "name": "Time integral",
   "description": "0-9999 s per repeat.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "s",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 1896,
   "documented": "1896",
   "name": "Time derivative",
   "description": "0-9999 s.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "s",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 1898,
   "documented": "1898",
   "name": "Dead band",
   "description": "-1000 to 1000.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 1900,
   "documented": "1900",
   "name": "Heat hysteresis",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 1902,
   "documented": "1902",
   "name": "Cool hysteresis",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 1908,
   "documented": "1908",
   "name": "Control loop output power",
   "description": "-100 to 100 %.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 1918,
   "documented": "1918",
   "name": "Autotune set point",
   "description": "50-200 % of the current set point.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "%",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 1920,
   "documented": "1920",
   "name": "Autotune request",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "59": "No",
    "106": "Yes"
   },
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 1928,
   "documented": "1928",
   "name": "Loop error status",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": {
    "61": "None",
    "1274": "Open loop",
    "1278": "Reversed loop"
   },
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 1930,
   "documented": "1930",
   "name": "Loop error clear",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "204": "Ignore",
    "129": "Clear"
   },
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 2160,
   "documented": "2160",
   "name": "Closed loop set point",
   "description": "Default 75.0.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 2162,
   "documented": "2162",
   "name": "Open loop set point",
   "description": "Fixed output power in manual mode.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "%",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 2176,
   "documented": "2176",
   "name": "Idle set point",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 2178,
   "documented": "2178",
   "name": "Bumpless set point",
   "description": "Set point that applies if a bumpless transfer occurs.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 2190,
   "documented": "2190",
   "name": "Ramp active set point",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 2198,
   "documented": "2198",
   "name": "Ramp target set point",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 2200,
   "documented": "2200",
   "name": "Remote enable",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "59": "No",
    "106": "Yes"
   },
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 2202,
   "documented": "2202",
   "name": "Remote set point type",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "10": "Auto (closed loop)",
    "54": "Manual (open loop)"
   },
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 2482,
   "documented": "2482",
   "name": "Comms 1 Modbus address",
   "description": "1-247, default 1.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 2486,
   "documented": "2486",
   "name": "Comms 1 Modbus parity",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "61": "None",
    "191": "Even",
    "192": "Odd"
   },
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 2490,
   "documented": "2490",
   "name": "Comms 1 temperature units",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "30": "°F",
    "15": "°C"
   },
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 2592,
   "documented": "2592",
   "name": "Comms 1 protocol",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "1286": "Standard Bus",
    "1057": "Modbus RTU"
   },
   "bits": null
  }
 ],
 "integration": {
  "summary": "Read the process value as a low-word-first float at 360-361 and the closed-loop set point at 2160-2161; write the set point with function 16. Control mode is at 1880 and output power at 1908.",
  "minimum_registers": [
   {
    "table": "holding_register",
    "address": 360,
    "why": "Analog input 1 process value"
   },
   {
    "table": "holding_register",
    "address": 362,
    "why": "Input 1 error status"
   },
   {
    "table": "holding_register",
    "address": 2160,
    "why": "Closed loop set point"
   },
   {
    "table": "holding_register",
    "address": 1880,
    "why": "Control mode"
   },
   {
    "table": "holding_register",
    "address": 1908,
    "why": "Output power"
   },
   {
    "table": "holding_register",
    "address": 1928,
    "why": "Loop error status"
   }
  ],
  "enable": "Set Protocol to Modbus RTU and set the Modbus address, baud rate and parity in the Communications menu of the Setup Page on the front panel.",
  "watchdog": null,
  "quirks": [
   "Floats are low word first by default (CDAB).",
   "Watlow uses numeric codes for enumerations (106 = Yes, 59 = No).",
   "Temperature unit for the comms channel is set separately (2490)."
  ],
  "setup": [
   "Defaults per the manual footnote: 8 data bits, no parity, 1 stop bit; Modbus address 1 (range 1-247)."
  ],
  "gotchas": [
   "Settings written over the network are not saved to EEPROM by default; the Nonvolatile Memory Save parameter changes this. The EEPROM is rated for about 1,000,000 writes, so avoid continuous writes in a loop.",
   "Some parameters exist only on some model configurations (PID, limit, integrated)."
  ]
 },
 "page": "https://easymodbus.com/modbus-register-maps/watlow/ez-zone-pm",
 "address_note": "address = 0-based Modbus wire (PDU) address; documented = as printed in the source.",
 "note": "Re-typed from the manufacturer's public documentation (see source) and verified against it. Registers vary by firmware and options; verify against the live device before writing."
}