 "manufacturer": "Wilo",
 "manufacturer_slug": "wilo",
 "model": "Wilo-Control EC-WP switchgear (ModBus RTU)",
 "model_slug": "control-ec-wp",
 "short_model": "Control EC-WP",
 "aliases": [
  "Control EC-WP",
  "Wilo Control EC WP",
  "EC-WP"
 ],
 "equipment_type": "Pump controller (switchgear)",
 "applies_to": "Wilo-Control EC-WP for one or two fixed-speed pumps, hardware HW2, software SW102x (instructions Ed.01/2024-08, 2552567).",
 "summary": "The Wilo-Control EC-WP is a switchgear for level- or pressure-dependent control of up to two fixed-speed pumps (float switch, electrodes, pressure switch or sensor). It has an RS485 ModBus RTU slave port. The holding registers cover pump enable, per-pump modes, pressure actual value and setpoints, general and float-switch status and the alarm history.",
 "transport": [
  "RTU"
 ],
 "defaults": {
  "unit_id": 10,
  "baud": 19200,
  "parity": "Even",
  "data_bits": null,
  "stop_bits": 1,
  "tcp_port": null
 },
 "addressing": {
  "convention": "Modicon",
  "note": "The parameter table prints each holding register as 4xxxx with the protocol address in brackets, e.g. 40026 (25). The bracketed number goes on the wire."
 },
 "default_word_order": null,
 "firmware": "SW102x",
 "source": {
  "title": "Wilo-Control EC-WP Installation and operating instructions",
  "doc_number": "2552567 Ed.01/2024-08",
  "revision_date": "2024-08",
  "url": "https://cms.media.wilo.com/dcianimpfinder/wilo718556/9646785/Resources/pdf/6110468747__en.pdf",
  "pages": "ModBus connection 6.5.14 (p. 19); Menu 2 ModBus settings 8.3.5 (p. 50); data types 13.4 and parameter overview 13.5 (pp. 63-64)"
 },
 "notes": [
  "The same parameter table is published as an HTML appendix page: https://cms.media.wilo.com/dcianimpfinder/wilo718556/9646785/en-GB/2228099211.html.",
  "BOOL registers are listed as UINT16 with 0/1; the manual treats any value above zero as true. ENUM registers are UINT16.",
  "Left out: Fault status 40139-40140 (BITMAP32 over two registers, bits 0-20) because the manual does not say which register holds the low bits.",
  "The data-type table describes BITMAP32 with the same 16-bit wording as BITMAP; this is a source wording issue.",
  "The scaling column prints 0.1 for 'Fault number alarm history'; it is copied as printed."
 ],
 "registers": [
  {
   "table": "holding_register",
   "address": 0,
   "documented": "40001 (0)",
   "name": "Communication profile version",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.001,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1,
   "documented": "40002 (1)",
   "name": "Wink service",
   "description": "Boolean; makes the switchgear identify itself.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "False / off",
    "1": "True / on"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2,
   "documented": "40003 (2)",
   "name": "Type of switchgear",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "8": "EC"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 13,
   "documented": "40014 (13)",
   "name": "BusCommandTimer",
   "description": "Bus command timer state.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "-",
    "1": "Off",
    "2": "Set",
    "3": "Active",
    "4": "Reset",
    "5": "Manual"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 14,
   "documented": "40015 (14)",
   "name": "Drives on/off",
   "description": "Boolean; enables or disables the pumps.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "False / off",
    "1": "True / on"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 24,
   "documented": "40025 (24)",
   "name": "Control mode",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "p-c (constant pressure)",
    "10": "Filling",
    "11": "Draining"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 25,
   "documented": "40026 (25)",
   "name": "Actual value",
   "description": "Measured pressure.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "bar",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 26,
   "documented": "40027 (26)",
   "name": "Current setpoint",
   "description": "Setpoint now in force.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "bar",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 40,
   "documented": "40041 (40)",
   "name": "Pump mode 1",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Off",
    "1": "Manual",
    "2": "Auto"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 41,
   "documented": "40042 (41)",
   "name": "Pump mode 2",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Off",
    "1": "Manual",
    "2": "Auto"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 61,
   "documented": "40062 (61)",
   "name": "General status",
   "description": "",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "0": "SBM (run signal)",
    "1": "SSM (collective fault)",
    "8": "EBM pump 1",
    "9": "EBM pump 2"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 67,
   "documented": "40068 (67)",
   "name": "Setpoint 1",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "bar",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 73,
   "documented": "40074 (73)",
   "name": "Application",
   "description": "Configured application; the table lists the element 2nd WP only.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 140,
   "documented": "40141 (140)",
   "name": "Acknowledge",
   "description": "Boolean fault acknowledge flag.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "False / off",
    "1": "True / on"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 141,
   "documented": "40142 (141)",
   "name": "Alarm history index",
   "description": "Selects the alarm history entry to read.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 142,
   "documented": "40143 (142)",
   "name": "Fault number alarm history",
   "description": "Fault number of the selected history entry.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 197,
   "documented": "40198 (197)",
   "name": "Status of float switch",
   "description": "",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "0": "Dry running",
    "1": "Pumps off",
    "2": "Pump 1 on",
    "3": "Pump 2 on",
    "4": "High water",
    "5": "Dry run 2",
    "6": "Pump 1 off",
    "7": "Pump 2 off"
   },
   "offset": 0
  }
 ],
 "integration": {
  "summary": "Turn ModBus on in Menu 2.01, wire RS485 and poll unit 10 at 19200 baud, even parity. Read the actual pressure (40026), general status (40062) and float-switch status (40198); enable the pumps with Drives on/off (40015).",
  "minimum_registers": [
   {
    "table": "holding_register",
    "address": 25,
    "why": "Actual pressure"
   },
   {
    "table": "holding_register",
    "address": 26,
    "why": "Current setpoint"
   },
   {
    "table": "holding_register",
    "address": 61,
    "why": "Run and fault signals"
   },
   {
    "table": "holding_register",
    "address": 14,
    "why": "Pumps on/off"
   },
   {
    "table": "holding_register",
    "address": 67,
    "why": "Pressure setpoint"
   },
   {
    "table": "holding_register",
    "address": 197,
    "why": "Float switch status"
   }
  ],
  "enable": "Menu 2.01 switches the ModBus RTU interface on (factory setting on). Baud in 2.02, address in 2.03, parity in 2.04, stop bits in 2.05.",
  "watchdog": null,
  "quirks": [
   "Pressure values are INT16/UINT16 in 0.1 bar.",
   "Factory address is 10, not 1."
  ],
  "setup": [
   "RS485 interface on the terminal strip; see the terminal diagram on the cover.",
   "Baud rate 9600, 19200 (default), 38400 or 76800; parity none, even (default) or odd; 1 (default) or 2 stop bits.",
   "The switchgear is terminated at the factory; remove jumper J2 if it is not at the end of the bus. Fit J3 and J4 if the bus needs polarisation."
  ],
  "gotchas": [
   "A 'Fault status' block (40139-40140) exists but is not in this map; read General status (40062) for the collective fault bit."
  ]
 },
 "page": "https://easymodbus.com/modbus-register-maps/wilo/control-ec-wp",
 "address_note": "address = 0-based Modbus wire (PDU) address; documented = as printed in the source.",
 "note": "Re-typed from the manufacturer's public documentation (see source) and verified against it. Registers vary by firmware and options; verify against the live device before writing."
}