 "applies_to": "Wilo Stratos GIGA2.0 pumps fitted with the plug-in CIF module Modbus RTU (module firmware 1.00-99.99); registers needing a newer module are marked.",
 "summary": "The Wilo Stratos GIGA2.0 gets Modbus RTU through Wilo's plug-in CIF module. A master switches the pump on/off with the pump command word, selects the control mode and writes a relative duty point in 0.5 % steps; a bus command timer can fall back to preset values when communication stops. Read-only data covers head, flow, power, energy, speed, temperatures and status/error words. This map keeps only the points Wilo marks as supported on the Stratos GIGA2.0.",
 "transport": [
  "RTU"
 ],
 "defaults": {
  "unit_id": null,
  "baud": null,
  "parity": null,
  "data_bits": 8,
  "stop_bits": null,
  "tcp_port": null
 },
 "addressing": {
  "convention": "0-based",
  "note": "Wilo states that all register addresses are raw addresses as sent on the bus; its example frame 01 04 02 BC 00 01 reads input register 700 (0x02BC). Masters that count registers from 1 must add 1."
 },
 "default_word_order": "ABCD",
 "firmware": "CIF module Modbus RTU 1.00-99.99 (module versions per register as noted)",
 "source": {
  "title": "WILO Modbus RTU",
  "doc_number": "wilo194406",
  "revision_date": null,
  "url": "https://cms.media.wilo.com/cdndoc/wilo194406/11516106/wilo194406.html",
  "pages": "HTML sections 6.1.4 (data types and 32-bit order), 6.1.5 (error values), 6.2.6 (raw addressing note), 6.2.7.3 (holding registers), 6.2.7.4 (input registers), 8.2.3-8.2.4 (baud and frame codes), 8.3 (example frame)"
 },
 "notes": [
  "Source is Wilo's public HTML functional description for the CIF module Modbus RTU, which marks every register and every enumeration/bit value with the pump families that support it. Only registers, values and bits marked for Stratos GIGA2.0 are kept here; values and bits not listed are not supported on this pump. Facts are re-keyed and the document is linked, not re-hosted.",
  "32-bit values (REAL = FLOAT32, UDINT = UINT32) are stored with the most significant 16 bits at the base address (ABCD), as stated in section 6.1.4.",
  "Scale: engineering value = raw x scale from Wilo's list (e.g. pressure x 10 = cm H2O, operation time x 10 = h, flow x 0.1 = m3/h, duty point x 0.5 = %, temperatures x 0.1 = K).",
  "Temperatures are in kelvin with scale 0.1 (raw 2932 = 293.2 K, about 20 °C).",
  "Error values: an unavailable reading returns the largest positive value of its data type (65535 for UINT, 32767 for INT).",
  "Flow (input register 2): Wilo lists it twice with the same address, type and scale; up to module 6.00 its error value is 9999, from 6.01 it is 65535.",
  "Module-version requirements from the list are noted in descriptions ('Module 3.01+' etc.); registers without a note exist from module version 1.00.",
  "Left out: identification registers (700-750: BCD software revisions, vendor ID, UUID, article number), system time (502), energy-meter start timestamps (306/310), the double-pump total runtime (9) and 'pressure max-pres-value' (212, ambiguous between live and maximum pressure)."
 ],
 "registers": [
  {
   "table": "input_register",
   "address": 1,
   "documented": "1",
   "name": "pressure",
   "description": "Actual pressure (head) at the pump.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 10,
   "scale_factor_ref": null,
   "units": "cm H₂O",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 2,
   "documented": "2",
   "name": "flow",
   "description": "Actual or calculated flow. Error value 9999 up to module 6.00, 65535 from 6.01.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "scale_factor_ref": null,
   "units": "m³/h",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 3,
   "documented": "3",
   "name": "energyConsumption",
   "description": "Energy consumption counter.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "kWh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 4,
   "documented": "4",
   "name": "powerInput",
   "description": "Electrical power input.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "W",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 5,
   "documented": "5",
   "name": "operationTime",
   "description": "Operating hours counter.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 10,
   "scale_factor_ref": null,
   "units": "h",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 7,
   "documented": "7",
   "name": "speed",
   "description": "Motor speed.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "1/min",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 8,
   "documented": "8",
   "name": "temperatureFluid@Device",
   "description": "Fluid temperature measured at the pump, in kelvin.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "scale_factor_ref": null,
   "units": "K",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 10,
   "documented": "10",
   "name": "controlFunction",
   "description": "Active control mode.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": {
    "1": "Gen_Spd",
    "3": "Gen_PHdConst",
    "4": "Gen_PHdVar",
    "9": "Gen_T",
    "10": "Gen_TDiff",
    "15": "INVALID",
    "16": "HeatRadiator_PHd",
    "17": "HeatRadiator_DA",
    "18": "HeatRadiator_T",
    "19": "HeatFloor_PHd",
    "20": "HeatFloor_DA",
    "21": "HeatFloor_T",
    "22": "HeatCeiling_PHd",
    "23": "HeatCeiling_DA",
    "24": "HeatCeiling_T",
    "25": "HeatFan_PHd",
    "26": "HeatFan_DA",
    "27": "HeatFan_T",
    "28": "HeatB._T",
    "29": "HeatB._TDiff",
    "30": "HeatB._Acc.Flow",
    "31": "HeatE._T",
    "32": "HeatE._TDiff",
    "33": "HeatE._Acc.Flow",
    "34": "Heat_PHdConst",
    "35": "Heat_PHdVar",
    "36": "Heat_PHdExt",
    "37": "Heat_DA",
    "38": "Heat_VolFlow",
    "39": "Heat_Acc.Flow",
    "40": "Heat_T",
    "41": "Heat_TDiff",
    "42": "Heat_Spd",
    "43": "CoolCeiling_PHd",
    "44": "CoolCeiling_DA",
    "45": "CoolCeiling_T",
    "46": "CoolFloor_PHd",
    "47": "CoolFloor_DA",
    "48": "CoolFloor_T",
    "49": "CoolFan_PHd",
    "50": "CoolFan_DA",
    "51": "CoolFan_T",
    "52": "CoolB._T",
    "53": "CoolB._TDiff",
    "54": "CoolB._Acc.Flow",
    "55": "CoolE._T",
    "56": "CoolE._TDiff",
    "57": "CoolE._Acc.Flow",
    "58": "Cool_PHdConst",
    "59": "Cool_PHdVar",
    "60": "Cool_PHdExt",
    "61": "Cool_DA",
    "62": "Cool_VolFlow",
    "63": "Cool_Acc.Flow",
    "64": "Cool_T",
    "65": "Cool_TDiff",
    "66": "Cool_Spd",
    "68": "SanW.Heat._TDiff",
    "69": "SanL.S._T",
    "70": "SanL.S._Acc.Flow",
    "71": "San_PHdConst",
    "72": "San_PHdVar",
    "73": "San_PHdExternal",
    "74": "San_VolFlow",
    "75": "San_Acc.Flow",
    "76": "San_T",
    "77": "San_TDiff",
    "78": "San_Spd",
    "79": "Gen_PHdExt",
    "80": "Gen_DA",
    "81": "Gen_VolFlow",
    "82": "Gen_Acc.Flow",
    "83": "ScndPHdConst",
    "84": "ScndPHdVar",
    "85": "ScndFlow",
    "86": "ScndSpd",
    "87": "HeatConcrete_PHd",
    "88": "HeatConcrete_DA",
    "90": "HeatConcrete_Flow",
    "91": "HeatBottle_Flow",
    "92": "HeatMan_MFA",
    "93": "HeatMan_Flow",
    "94": "HeatTank_MFA",
    "95": "HeatTank_Flow",
    "96": "HeatExchanger_Flow",
    "97": "HeatSource_TDiff",
    "98": "HeatSource_Flow",
    "99": "HeatDistrict_PHdConst",
    "100": "HeatDistrict_PHdVar",
    "101": "HeatDistrict_PHdExt",
    "102": "CoolConcrete_PHd",
    "103": "CoolConcrete_DA",
    "104": "CoolConcrete_TDiff",
    "105": "CoolConcrete_Flow",
    "106": "CoolBottle_Flow",
    "107": "CoolMan_MFA",
    "108": "CoolMan_Flow",
    "109": "CoolTank_MFA",
    "110": "CoolTank_Flow",
    "111": "CoolExchanger_Flow",
    "113": "CoolCondensor_Flow",
    "114": "CoolDistrict_PHdConst",
    "115": "CoolDistrict_PHdVar",
    "116": "CoolDistrict_PHdExt",
    "140": "Gen_UsrDfd"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 16,
   "documented": "16",
   "name": "Pump Module",
   "description": "Pump module flags.",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "0": "TRUE"
   },
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 17,
   "documented": "17",
   "name": "pumpTypePLR",
   "description": "Pump type code.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": {
    "254": "EXTENDED"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 18,
   "documented": "18",
   "name": "speed max-pres-value",
   "description": "Maximum speed.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "1/min",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 19,
   "documented": "19",
   "name": "speed min-pres-value",
   "description": "Minimum speed.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "1/min",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 20,
   "documented": "20",
   "name": "pressureMaxPHdConst",
   "description": "Max pressure setpoint in dp-c; scales % back to head.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 10,
   "scale_factor_ref": null,
   "units": "cm H₂O",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 21,
   "documented": "21",
   "name": "pressureMinPHdConst",
   "description": "Min pressure setpoint in dp-c.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 10,
   "scale_factor_ref": null,
   "units": "cm H₂O",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 22,
   "documented": "22",
   "name": "pressureMaxPHdVar",
   "description": "Max pressure setpoint in dp-v.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 10,
   "scale_factor_ref": null,
   "units": "cm H₂O",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 23,
   "documented": "23",
   "name": "pressureMinPHdVar",
   "description": "Min pressure setpoint in dp-v.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 10,
   "scale_factor_ref": null,
   "units": "cm H₂O",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 24,
   "documented": "24",
   "name": "flow max-pres-value",
   "description": "Maximum (calculated) flow.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "scale_factor_ref": null,
   "units": "m³/h",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 25,
   "documented": "25",
   "name": "flow min-pres-value",
   "description": "Minimum (calculated) flow.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "scale_factor_ref": null,
   "units": "m³/h",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 28,
   "documented": "28",
   "name": "powerInput max-pres-value",
   "description": "Maximum electrical input power.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "W",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 35,
   "documented": "35",
   "name": "Service Message",
   "description": "Legacy register.",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "0": "serviceRequired",
    "1": "FALSE",
    "2": "FALSE",
    "3": "FALSE"
   },
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 36,
   "documented": "36",
   "name": "Error Type",
   "description": "Legacy register; prefer I 940 for new work.",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "0": "moduleError",
    "1": "motorError",
    "3": "errorPresent",
    "4": "supplyVoltageError"
   },
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 37,
   "documented": "37",
   "name": "Error Message",
   "description": "Legacy detailed error flags.",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "0": "statusUndervoltage",
    "1": "overVoltage",
    "2": "phaseFault",
    "3": "idleRunning",
    "8": "motorOverheated",
    "9": "motorError",
    "10": "pumpBlocked",
    "11": "moduleOverheated",
    "12": "moduleWarning",
    "13": "moduleError",
    "14": "sensorMalfunction"
   },
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 38,
   "documented": "38",
   "name": "Pump Status",
   "description": "Legacy controller status flags.",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "0": "device/functionOn",
    "1": "FALSE",
    "2": "setpointDifference",
    "3": "overrideOff",
    "4": "pumpConfigurationDoublePump",
    "5": "localOperation",
    "6": "statusQ/HValuesInvalid",
    "7": "overrideMin",
    "8": "FALSE (module 5.00+)",
    "9": "FALSE (module 5.00+)",
    "10": "FALSE (module 5.00+)",
    "11": "FALSE (module 5.00+)",
    "12": "externalSetpoint (module 5.00+)",
    "14": "FALSE (module 5.00+)"
   },
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 39,
   "documented": "39",
   "name": "State Diagnostics",
   "description": "Legacy diagnostic flags.",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "0": "errorPresent",
    "1": "supplyVoltageError",
    "3": "lowRegulationLimit",
    "4": "highRegulationLimit",
    "6": "setpointOutOfRange",
    "8": "localOperation",
    "10": "device/functionOn"
   },
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 80,
   "documented": "80",
   "name": "Pump Module",
   "description": "Module flags of the partner pump (twin-head).",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "0": "TRUE"
   },
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 81,
   "documented": "81",
   "name": "pumpTypePLR",
   "description": "Pump type code of the partner pump.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": {
    "254": "EXTENDED"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 102,
   "documented": "102",
   "name": "Pump Status",
   "description": "Status flags of the partner pump (twin-head).",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "0": "device/functionOn",
    "1": "FALSE",
    "2": "setpointDifference",
    "3": "overrideOff",
    "4": "pumpConfigurationDoublePump",
    "5": "localOperation",
    "7": "overrideMin"
   },
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 200,
   "documented": "200",
   "name": "dutyPointRel",
   "description": "Setpoint the pump is actually using (200 = 100 %). Module 3.00+.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.5,
   "scale_factor_ref": null,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 202,
   "documented": "202",
   "name": "dutyPointRel maximum-output",
   "description": "Upper limit of the active setpoint. Module 3.00+.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.5,
   "scale_factor_ref": null,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 204,
   "documented": "204",
   "name": "dutyPointRel minimum-output",
   "description": "Lower limit; lower writes are limited to it. Module 3.00+.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.5,
   "scale_factor_ref": null,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 206,
   "documented": "206",
   "name": "dutyPoint100%Val",
   "description": "Engineering value at 100 % in the current mode; unit in I 208. Module 3.00+.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 208,
   "documented": "208",
   "name": "dutyPointRel units",
   "description": "Unit code for I 206. Module 3.00+.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": {
    "5": "V",
    "19": "kWh",
    "47": "W",
    "55": "bar",
    "62": "Cel",
    "63": "K",
    "73": "s",
    "80": "m3",
    "95": "{noUnit}",
    "104": "min-1",
    "135": "m3/h"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 210,
   "documented": "210",
   "name": "setpointSignalSource",
   "description": "Module 3.00+.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": {
    "1": "IF-Module",
    "6": "Internal",
    "7": "EXT 1",
    "8": "EXT 2",
    "9": "INVALID",
    "10": "EXT 3",
    "11": "EXT 4"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 211,
   "documented": "211",
   "name": "parameterSetSelector",
   "description": "Parameter set in use (module 3.01+).",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": {
    "1": "norm",
    "2": "aux",
    "3": "preset"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 222,
   "documented": "222",
   "name": "dutyPointRel maximum-output",
   "description": "Module 3.01+.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.5,
   "scale_factor_ref": null,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 224,
   "documented": "224",
   "name": "dutyPointRel minimum-output",
   "description": "Module 3.01+.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.5,
   "scale_factor_ref": null,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 226,
   "documented": "226",
   "name": "dutyPoint100%Val",
   "description": "Module 3.01+.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 228,
   "documented": "228",
   "name": "dutyPointRel units",
   "description": "Module 3.01+.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": {
    "5": "V",
    "19": "kWh",
    "47": "W",
    "55": "bar",
    "62": "Cel",
    "63": "K",
    "73": "s",
    "80": "m3",
    "95": "{noUnit}",
    "104": "min-1",
    "135": "m3/h"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 232,
   "documented": "232",
   "name": "dutyPointRel aux. maximum-output",
   "description": "Module 3.01+.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.5,
   "scale_factor_ref": null,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 234,
   "documented": "234",
   "name": "dutyPointRel aux. minimum-output",
   "description": "Module 3.01+.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.5,
   "scale_factor_ref": null,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 236,
   "documented": "236",
   "name": "dutyPoint100%Val aux.",
   "description": "Module 3.01+.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 238,
   "documented": "238",
   "name": "dutyPointRel aux. units",
   "description": "Module 3.01+.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": {
    "5": "V",
    "19": "kWh",
    "47": "W",
    "55": "bar",
    "62": "Cel",
    "63": "K",
    "73": "s",
    "80": "m3",
    "95": "{noUnit}",
    "104": "min-1",
    "135": "m3/h"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 242,
   "documented": "242",
   "name": "dutyPointRel preset maximum-output",
   "description": "Module 3.01+.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.5,
   "scale_factor_ref": null,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 244,
   "documented": "244",
   "name": "dutyPointRel preset minimum-output",
   "description": "Module 3.01+.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.5,
   "scale_factor_ref": null,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 246,
   "documented": "246",
   "name": "dutyPoint100%Val preset",
   "description": "Module 3.01+.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 248,
   "documented": "248",
   "name": "dutyPointRel preset units",
   "description": "Module 3.01+.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": {
    "5": "V",
    "19": "kWh",
    "47": "W",
    "55": "bar",
    "62": "Cel",
    "63": "K",
    "73": "s",
    "80": "m3",
    "95": "{noUnit}",
    "104": "min-1",
    "135": "m3/h"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 250,
   "documented": "250",
   "name": "dutyPointRel",
   "description": "Module 3.01+.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.5,
   "scale_factor_ref": null,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 252,
   "documented": "252",
   "name": "dutyPointRel maximum-output",
   "description": "Module 3.01+.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.5,
   "scale_factor_ref": null,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 254,
   "documented": "254",
   "name": "dutyPointRel minimum-output",
   "description": "Module 3.01+.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.5,
   "scale_factor_ref": null,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 256,
   "documented": "256",
   "name": "dutyPoint100%Val",
   "description": "Module 3.01+.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 258,
   "documented": "258",
   "name": "dutyPointRel units",
   "description": "Module 3.01+.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": {
    "5": "V",
    "19": "kWh",
    "47": "W",
    "55": "bar",
    "62": "Cel",
    "63": "K",
    "73": "s",
    "80": "m3",
    "95": "{noUnit}",
    "104": "min-1",
    "135": "m3/h"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 260,
   "documented": "260",
   "name": "controlFunction",
   "description": "Module 3.01+.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": {
    "1": "Gen_Spd",
    "3": "Gen_PHdConst",
    "4": "Gen_PHdVar",
    "9": "Gen_T",
    "10": "Gen_TDiff",
    "15": "INVALID",
    "16": "HeatRadiator_PHd",
    "17": "HeatRadiator_DA",
    "18": "HeatRadiator_T",
    "19": "HeatFloor_PHd",
    "20": "HeatFloor_DA",
    "21": "HeatFloor_T",
    "22": "HeatCeiling_PHd",
    "23": "HeatCeiling_DA",
    "24": "HeatCeiling_T",
    "25": "HeatFan_PHd",
    "26": "HeatFan_DA",
    "27": "HeatFan_T",
    "28": "HeatB._T",
    "29": "HeatB._TDiff",
    "30": "HeatB._Acc.Flow",
    "31": "HeatE._T",
    "32": "HeatE._TDiff",
    "33": "HeatE._Acc.Flow",
    "34": "Heat_PHdConst",
    "35": "Heat_PHdVar",
    "36": "Heat_PHdExt",
    "37": "Heat_DA",
    "38": "Heat_VolFlow",
    "39": "Heat_Acc.Flow",
    "40": "Heat_T",
    "41": "Heat_TDiff",
    "42": "Heat_Spd",
    "43": "CoolCeiling_PHd",
    "44": "CoolCeiling_DA",
    "45": "CoolCeiling_T",
    "46": "CoolFloor_PHd",
    "47": "CoolFloor_DA",
    "48": "CoolFloor_T",
    "49": "CoolFan_PHd",
    "50": "CoolFan_DA",
    "51": "CoolFan_T",
    "52": "CoolB._T",
    "53": "CoolB._TDiff",
    "54": "CoolB._Acc.Flow",
    "55": "CoolE._T",
    "56": "CoolE._TDiff",
    "57": "CoolE._Acc.Flow",
    "58": "Cool_PHdConst",
    "59": "Cool_PHdVar",
    "60": "Cool_PHdExt",
    "61": "Cool_DA",
    "62": "Cool_VolFlow",
    "63": "Cool_Acc.Flow",
    "64": "Cool_T",
    "65": "Cool_TDiff",
    "66": "Cool_Spd",
    "68": "SanW.Heat._TDiff",
    "69": "SanL.S._T",
    "70": "SanL.S._Acc.Flow",
    "71": "San_PHdConst",
    "72": "San_PHdVar",
    "73": "San_PHdExternal",
    "74": "San_VolFlow",
    "75": "San_Acc.Flow",
    "76": "San_T",
    "77": "San_TDiff",
    "78": "San_Spd",
    "79": "Gen_PHdExt",
    "80": "Gen_DA",
    "81": "Gen_VolFlow",
    "82": "Gen_Acc.Flow",
    "83": "ScndPHdConst",
    "84": "ScndPHdVar",
    "85": "ScndFlow",
    "86": "ScndSpd",
    "87": "HeatConcrete_PHd",
    "88": "HeatConcrete_DA",
    "90": "HeatConcrete_Flow",
    "91": "HeatBottle_Flow",
    "92": "HeatMan_MFA",
    "93": "HeatMan_Flow",
    "94": "HeatTank_MFA",
    "95": "HeatTank_Flow",
    "96": "HeatExchanger_Flow",
    "97": "HeatSource_TDiff",
    "98": "HeatSource_Flow",
    "99": "HeatDistrict_PHdConst",
    "100": "HeatDistrict_PHdVar",
    "101": "HeatDistrict_PHdExt",
    "102": "CoolConcrete_PHd",
    "103": "CoolConcrete_DA",
    "104": "CoolConcrete_TDiff",
    "105": "CoolConcrete_Flow",
    "106": "CoolBottle_Flow",
    "107": "CoolMan_MFA",
    "108": "CoolMan_Flow",
    "109": "CoolTank_MFA",
    "110": "CoolTank_Flow",
    "111": "CoolExchanger_Flow",
    "113": "CoolCondensor_Flow",
    "114": "CoolDistrict_PHdConst",
    "115": "CoolDistrict_PHdVar",
    "116": "CoolDistrict_PHdExt",
    "140": "Gen_UsrDfd"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 261,
   "documented": "261",
   "name": "Pump Command",
   "description": "Module 3.01+.",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "0": "device/functionOn (module 3.01+)"
   },
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 262,
   "documented": "262",
   "name": "setpointSignalSource",
   "description": "Module 3.01+.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": {
    "1": "IF-Module",
    "6": "Internal",
    "7": "EXT 1",
    "8": "EXT 2",
    "9": "INVALID",
    "10": "EXT 3",
    "11": "EXT 4"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 270,
   "documented": "270",
   "name": "flow limit. max",
   "description": "Module 3.02+.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "scale_factor_ref": null,
   "units": "m³/h",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 272,
   "documented": "272",
   "name": "flow limit. min",
   "description": "Module 3.02+.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "scale_factor_ref": null,
   "units": "m³/h",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 274,
   "documented": "274",
   "name": "flow limit. off",
   "description": "Module 3.02+.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "scale_factor_ref": null,
   "units": "m³/h",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 280,
   "documented": "280",
   "name": "flowZeroSetpointRed.Factor",
   "description": "Module 3.02+.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.5,
   "scale_factor_ref": null,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 281,
   "documented": "281",
   "name": "flowNominal4Ctrl.Fun.",
   "description": "Module 3.02+.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "scale_factor_ref": null,
   "units": "m³/h",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 282,
   "documented": "282",
   "name": "motorSpaceHeating",
   "description": "Module 6.10+.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": {
    "1": "FUN_INVALID",
    "2": "FUN_RESERVED",
    "3": "FUN_NOT_SUPP",
    "4": "FUN_NOT_AVAIL",
    "5": "FUN_DISABLE",
    "6": "FUN_ENABLE",
    "7": "FUN_ACTIVE"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 300,
   "documented": "300",
   "name": "powerHeating",
   "description": "Heating power in the measured circuit. Module 3.00+.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "scale_factor_ref": null,
   "units": "W",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 302,
   "documented": "302",
   "name": "powerRefrigeration",
   "description": "Cooling power in the measured circuit. Module 3.00+.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "scale_factor_ref": null,
   "units": "W",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 304,
   "documented": "304",
   "name": "energyHeatRrst.able",
   "description": "Resettable heating energy (reset may not be possible via bus). Module 3.00+.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "scale_factor_ref": null,
   "units": "kWh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 308,
   "documented": "308",
   "name": "energyRefrigRrst.able",
   "description": "Resettable cooling energy. Module 3.00+.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "scale_factor_ref": null,
   "units": "kWh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 312,
   "documented": "312",
   "name": "energyHeat.Total",
   "description": "Total heating energy, not resettable. Module 3.00+.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "scale_factor_ref": null,
   "units": "kWh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 314,
   "documented": "314",
   "name": "energyRefrig.Total",
   "description": "Total cooling energy, not resettable. Module 3.00+.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "scale_factor_ref": null,
   "units": "kWh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 316,
   "documented": "316",
   "name": "temperat.FluidFwd",
   "description": "Forward (supply) temperature in kelvin. Module 3.00+.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "scale_factor_ref": null,
   "units": "K",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 318,
   "documented": "318",
   "name": "temperat.FluidRet",
   "description": "Return temperature in kelvin. Module 3.00+.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "scale_factor_ref": null,
   "units": "K",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 320,
   "documented": "320",
   "name": "voltageInput",
   "description": "Mains input voltage. Module 3.00+.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "scale_factor_ref": null,
   "units": "V",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 324,
   "documented": "324",
   "name": "analogIn1MeasuredVal",
   "description": "Module 3.00+.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 326,
   "documented": "326",
   "name": "analogIn2MeasuredVal",
   "description": "Module 3.00+.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 328,
   "documented": "328",
   "name": "analogIn1MeasuredVal units",
   "description": "Module 3.02+.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": {
    "5": "V",
    "19": "kWh",
    "47": "W",
    "55": "bar",
    "62": "Cel",
    "63": "K",
    "73": "s",
    "80": "m3",
    "95": "{noUnit}",
    "104": "min-1",
    "135": "m3/h"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 329,
   "documented": "329",
   "name": "analogIn2MeasuredVal units",
   "description": "Module 3.02+.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": {
    "5": "V",
    "19": "kWh",
    "47": "W",
    "55": "bar",
    "62": "Cel",
    "63": "K",
    "73": "s",
    "80": "m3",
    "95": "{noUnit}",
    "104": "min-1",
    "135": "m3/h"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 330,
   "documented": "330",
   "name": "temperat.ReferenceT1",
   "description": "Module 3.02+.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "scale_factor_ref": null,
   "units": "K",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 332,
   "documented": "332",
   "name": "temperat.ReferenceT2",
   "description": "Module 3.02+.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "scale_factor_ref": null,
   "units": "K",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 334,
   "documented": "334",
   "name": "analogIn3MeasuredVal",
   "description": "Module 5.00+.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 336,
   "documented": "336",
   "name": "analogIn4MeasuredVal",
   "description": "Module 5.00+.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 338,
   "documented": "338",
   "name": "analogIn3MeasuredVal units",
   "description": "Module 5.00+.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": {
    "5": "V",
    "19": "kWh",
    "47": "W",
    "55": "bar",
    "62": "Cel",
    "63": "K",
    "73": "s",
    "80": "m3",
    "95": "{noUnit}",
    "104": "min-1",
    "135": "m3/h"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 339,
   "documented": "339",
   "name": "analogIn4MeasuredVal units",
   "description": "Module 5.00+.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": {
    "5": "V",
    "19": "kWh",
    "47": "W",
    "55": "bar",
    "62": "Cel",
    "63": "K",
    "73": "s",
    "80": "m3",
    "95": "{noUnit}",
    "104": "min-1",
    "135": "m3/h"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 340,
   "documented": "340",
   "name": "sensorSignal",
   "description": "Module 5.02+.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 400,
   "documented": "400",
   "name": "dutyPointRel",
   "description": "Duty point currently in use.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.5,
   "scale_factor_ref": null,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 402,
   "documented": "402",
   "name": "Pump Command active",
   "description": "Command currently in effect.",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "0": "device/functionOn",
    "1": "overrideMin",
    "2": "overrideMax",
    "3": "TRUE (module 3.00+)",
    "4": "overrideOff (module 3.00+)",
    "5": "overrideOn (module 3.00+)",
    "8": "autoNightMode (module 3.02+)"
   },
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 403,
   "documented": "403",
   "name": "Pump Command out",
   "description": "Module 3.02+.",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "8": "autoNightMode (module 3.02+)"
   },
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 404,
   "documented": "404",
   "name": "Operation Status",
   "description": "Main run / warning / error flags.",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "0": "ready4Operation",
    "1": "device/functionOn",
    "2": "serviceRequired",
    "3": "warningPresent",
    "4": "errorPresent",
    "5": "finalErrorPresent"
   },
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 500,
   "documented": "500",
   "name": "heartbeatCount",
   "description": "Counts pump-to-module heartbeats; resets on restart.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 504,
   "documented": "504",
   "name": "busCmd.TimerTimeRemain.",
   "description": "Seconds left before the bus command timer elapses (module 3.02+).",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "s",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 901,
   "documented": "901",
   "name": "userTroubleCode",
   "description": "Module 3.00+.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": {
    "0": "CODE_0",
    "401": "CODE_401",
    "402": "CODE_402",
    "403": "CODE_403",
    "404": "CODE_404",
    "405": "CODE_405",
    "406": "CODE_406",
    "407": "CODE_407",
    "408": "CODE_408",
    "409": "CODE_409",
    "410": "CODE_410",
    "420": "CODE_420",
    "421": "CODE_421",
    "449": "CODE_449",
    "550": "CODE_550",
    "551": "CODE_551",
    "552": "CODE_552",
    "553": "CODE_553",
    "554": "CODE_554",
    "556": "CODE_556",
    "558": "CODE_558",
    "560": "CODE_560",
    "561": "CODE_561",
    "562": "CODE_562",
    "563": "CODE_563",
    "564": "CODE_564",
    "565": "CODE_565",
    "566": "CODE_566",
    "569": "CODE_569",
    "570": "CODE_570",
    "571": "CODE_571",
    "573": "CODE_573",
    "574": "CODE_574",
    "577": "CODE_577",
    "578": "CODE_578",
    "579": "CODE_579",
    "582": "CODE_582",
    "583": "CODE_583",
    "584": "CODE_584",
    "586": "CODE_586",
    "588": "CODE_588",
    "589": "CODE_589",
    "590": "CODE_590",
    "591": "CODE_591",
    "592": "CODE_592",
    "593": "CODE_593",
    "594": "CODE_594",
    "595": "CODE_595",
    "596": "CODE_596",
    "597": "CODE_597",
    "601": "CODE_601",
    "602": "CODE_602",
    "603": "CODE_603",
    "604": "CODE_604",
    "606": "CODE_606",
    "607": "CODE_607",
    "609": "CODE_609",
    "610": "CODE_610",
    "611": "CODE_611",
    "614": "CODE_614",
    "615": "CODE_615",
    "618": "CODE_618",
    "619": "CODE_619",
    "621": "CODE_621",
    "641": "CODE_641",
    "642": "CODE_642",
    "643": "CODE_643",
    "644": "CODE_644",
    "646": "CODE_646",
    "647": "CODE_647",
    "649": "CODE_649",
    "650": "CODE_650",
    "651": "CODE_651",
    "655": "CODE_655",
    "656": "CODE_656",
    "657": "CODE_657",
    "658": "CODE_658",
    "888": "INVALID"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 940,
   "documented": "940",
   "name": "warning/errorMessage",
   "description": "Active Wilo warning/error code.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": {
    "0": "NO_ERROR",
    "3": "FLUID_TEMP_HI",
    "4": "MAINS_VOLT_LO",
    "5": "MAINS_VOLT_HI",
    "6": "MAINS_PHASE",
    "7": "PUMP_GENERATOR",
    "9": "PUMP_TURBINE",
    "10": "PUMP_BLOCKED",
    "11": "PUMP_DRY_RUN",
    "25": "MOT_OPEN_CIRC",
    "26": "MOT_TEMP_SENS",
    "30": "MOD_TEMP_HI",
    "33": "MOD_VOLT_DC_HI",
    "42": "SENS_IN1",
    "43": "SENS_IN2",
    "50": "COM_LOC_BIND",
    "51": "COM_MP",
    "52": "COM_MP_TIMEOUT",
    "54": "COM_REM_BIND",
    "72": "ELECT_POW",
    "77": "ELECT_SUPP_24_I",
    "89": "MOT_MOD_FAULT",
    "97": "SET_DATA_MISS",
    "100": "CTRL_BATT",
    "104": "CTRL_FAN_EXT",
    "119": "MCTL_TURBINE",
    "251": "EXTENDED_WARN",
    "252": "EXTENDED_ERR",
    "255": "INVALID"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 950,
   "documented": "950",
   "name": "warning/errorMessage",
   "description": "Second Wilo warning/error code register.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": {
    "0": "NO_ERROR",
    "3": "FLUID_TEMP_HI",
    "4": "MAINS_VOLT_LO",
    "5": "MAINS_VOLT_HI",
    "6": "MAINS_PHASE",
    "7": "PUMP_GENERATOR",
    "9": "PUMP_TURBINE",
    "10": "PUMP_BLOCKED",
    "11": "PUMP_DRY_RUN",
    "25": "MOT_OPEN_CIRC",
    "26": "MOT_TEMP_SENS",
    "30": "MOD_TEMP_HI",
    "33": "MOD_VOLT_DC_HI",
    "42": "SENS_IN1",
    "43": "SENS_IN2",
    "50": "COM_LOC_BIND",
    "51": "COM_MP",
    "52": "COM_MP_TIMEOUT",
    "54": "COM_REM_BIND",
    "72": "ELECT_POW",
    "77": "ELECT_SUPP_24_I",
    "89": "MOT_MOD_FAULT",
    "97": "SET_DATA_MISS",
    "100": "CTRL_BATT",
    "104": "CTRL_FAN_EXT",
    "119": "MCTL_TURBINE",
    "251": "EXTENDED_WARN",
    "252": "EXTENDED_ERR",
    "255": "INVALID"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1,
   "documented": "1",
   "name": "dutyPointRel",
   "description": "Setpoint in % of the active mode's 100 % value (200 = 100 %).",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.5,
   "scale_factor_ref": null,
   "units": "%",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 40,
   "documented": "40",
   "name": "Pump Command in",
   "description": "On/off and override command word.",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": {
    "0": "device/functionOn",
    "1": "overrideMin",
    "2": "overrideMax",
    "3": "TRUE",
    "4": "overrideOff (module 3.00+)",
    "5": "overrideOn (module 3.00+)"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 42,
   "documented": "42",
   "name": "controlFunction",
   "description": "Control mode; unsupported values are ignored.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "1": "Gen_Spd",
    "3": "Gen_PHdConst",
    "4": "Gen_PHdVar",
    "9": "Gen_T",
    "10": "Gen_TDiff",
    "15": "INVALID",
    "16": "HeatRadiator_PHd",
    "17": "HeatRadiator_DA",
    "18": "HeatRadiator_T",
    "19": "HeatFloor_PHd",
    "20": "HeatFloor_DA",
    "21": "HeatFloor_T",
    "22": "HeatCeiling_PHd",
    "23": "HeatCeiling_DA",
    "24": "HeatCeiling_T",
    "25": "HeatFan_PHd",
    "26": "HeatFan_DA",
    "27": "HeatFan_T",
    "28": "HeatB._T",
    "29": "HeatB._TDiff",
    "30": "HeatB._Acc.Flow",
    "31": "HeatE._T",
    "32": "HeatE._TDiff",
    "33": "HeatE._Acc.Flow",
    "34": "Heat_PHdConst",
    "35": "Heat_PHdVar",
    "36": "Heat_PHdExt",
    "37": "Heat_DA",
    "38": "Heat_VolFlow",
    "39": "Heat_Acc.Flow",
    "40": "Heat_T",
    "41": "Heat_TDiff",
    "42": "Heat_Spd",
    "43": "CoolCeiling_PHd",
    "44": "CoolCeiling_DA",
    "45": "CoolCeiling_T",
    "46": "CoolFloor_PHd",
    "47": "CoolFloor_DA",
    "48": "CoolFloor_T",
    "49": "CoolFan_PHd",
    "50": "CoolFan_DA",
    "51": "CoolFan_T",
    "52": "CoolB._T",
    "53": "CoolB._TDiff",
    "54": "CoolB._Acc.Flow",
    "55": "CoolE._T",
    "56": "CoolE._TDiff",
    "57": "CoolE._Acc.Flow",
    "58": "Cool_PHdConst",
    "59": "Cool_PHdVar",
    "60": "Cool_PHdExt",
    "61": "Cool_DA",
    "62": "Cool_VolFlow",
    "63": "Cool_Acc.Flow",
    "64": "Cool_T",
    "65": "Cool_TDiff",
    "66": "Cool_Spd",
    "68": "SanW.Heat._TDiff",
    "69": "SanL.S._T",
    "70": "SanL.S._Acc.Flow",
    "71": "San_PHdConst",
    "72": "San_PHdVar",
    "73": "San_PHdExternal",
    "74": "San_VolFlow",
    "75": "San_Acc.Flow",
    "76": "San_T",
    "77": "San_TDiff",
    "78": "San_Spd",
    "79": "Gen_PHdExt",
    "80": "Gen_DA",
    "81": "Gen_VolFlow",
    "82": "Gen_Acc.Flow",
    "83": "ScndPHdConst",
    "84": "ScndPHdVar",
    "85": "ScndFlow",
    "86": "ScndSpd",
    "87": "HeatConcrete_PHd",
    "88": "HeatConcrete_DA",
    "90": "HeatConcrete_Flow",
    "91": "HeatBottle_Flow",
    "92": "HeatMan_MFA",
    "93": "HeatMan_Flow",
    "94": "HeatTank_MFA",
    "95": "HeatTank_Flow",
    "96": "HeatExchanger_Flow",
    "97": "HeatSource_TDiff",
    "98": "HeatSource_Flow",
    "99": "HeatDistrict_PHdConst",
    "100": "HeatDistrict_PHdVar",
    "101": "HeatDistrict_PHdExt",
    "102": "CoolConcrete_PHd",
    "103": "CoolConcrete_DA",
    "104": "CoolConcrete_TDiff",
    "105": "CoolConcrete_Flow",
    "106": "CoolBottle_Flow",
    "107": "CoolMan_MFA",
    "108": "CoolMan_Flow",
    "109": "CoolTank_MFA",
    "110": "CoolTank_Flow",
    "111": "CoolExchanger_Flow",
    "113": "CoolCondensor_Flow",
    "114": "CoolDistrict_PHdConst",
    "115": "CoolDistrict_PHdVar",
    "116": "CoolDistrict_PHdExt",
    "140": "Gen_UsrDfd"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 300,
   "documented": "300",
   "name": "busCmd.Timer",
   "description": "Bus command timer / fallback state machine.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "1": "OFF",
    "2": "SET",
    "3": "ACTIVE",
    "4": "RESET",
    "5": "MANUAL",
    "6": "SET_PRESET",
    "7": "ACTIVE_PRESET",
    "8": "RESET_PRESET",
    "9": "MANUAL_PRESET",
    "10": "INVALID"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 302,
   "documented": "302",
   "name": "temperat.ReferenceT1",
   "description": "Module 3.00+.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "scale_factor_ref": null,
   "units": "K",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 304,
   "documented": "304",
   "name": "temperat.ReferenceT2",
   "description": "Module 3.00+.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "scale_factor_ref": null,
   "units": "K",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 306,
   "documented": "306",
   "name": "sensorSignal",
   "description": "Module 3.02+.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 400,
   "documented": "400",
   "name": "busCmd.TimerTimeout",
   "description": "Bus command timer timeout. Module 3.00+.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "s",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 401,
   "documented": "401",
   "name": "setpointSignalSource",
   "description": "Where the setpoint comes from; write 1 for bus control.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "1": "IF-Module",
    "6": "Internal",
    "7": "EXT 1",
    "8": "EXT 2",
    "9": "INVALID",
    "10": "EXT 3",
    "11": "EXT 4"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 402,
   "documented": "402",
   "name": "dutyPointRel preset",
   "description": "Fallback setpoint used by the bus command timer.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.5,
   "scale_factor_ref": null,
   "units": "%",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 403,
   "documented": "403",
   "name": "controlFunction preset",
   "description": "Fallback control mode.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "1": "Gen_Spd",
    "3": "Gen_PHdConst",
    "4": "Gen_PHdVar",
    "9": "Gen_T",
    "10": "Gen_TDiff",
    "15": "INVALID",
    "16": "HeatRadiator_PHd",
    "17": "HeatRadiator_DA",
    "18": "HeatRadiator_T",
    "19": "HeatFloor_PHd",
    "20": "HeatFloor_DA",
    "21": "HeatFloor_T",
    "22": "HeatCeiling_PHd",
    "23": "HeatCeiling_DA",
    "24": "HeatCeiling_T",
    "25": "HeatFan_PHd",
    "26": "HeatFan_DA",
    "27": "HeatFan_T",
    "28": "HeatB._T",
    "29": "HeatB._TDiff",
    "30": "HeatB._Acc.Flow",
    "31": "HeatE._T",
    "32": "HeatE._TDiff",
    "33": "HeatE._Acc.Flow",
    "34": "Heat_PHdConst",
    "35": "Heat_PHdVar",
    "36": "Heat_PHdExt",
    "37": "Heat_DA",
    "38": "Heat_VolFlow",
    "39": "Heat_Acc.Flow",
    "40": "Heat_T",
    "41": "Heat_TDiff",
    "42": "Heat_Spd",
    "43": "CoolCeiling_PHd",
    "44": "CoolCeiling_DA",
    "45": "CoolCeiling_T",
    "46": "CoolFloor_PHd",
    "47": "CoolFloor_DA",
    "48": "CoolFloor_T",
    "49": "CoolFan_PHd",
    "50": "CoolFan_DA",
    "51": "CoolFan_T",
    "52": "CoolB._T",
    "53": "CoolB._TDiff",
    "54": "CoolB._Acc.Flow",
    "55": "CoolE._T",
    "56": "CoolE._TDiff",
    "57": "CoolE._Acc.Flow",
    "58": "Cool_PHdConst",
    "59": "Cool_PHdVar",
    "60": "Cool_PHdExt",
    "61": "Cool_DA",
    "62": "Cool_VolFlow",
    "63": "Cool_Acc.Flow",
    "64": "Cool_T",
    "65": "Cool_TDiff",
    "66": "Cool_Spd",
    "68": "SanW.Heat._TDiff",
    "69": "SanL.S._T",
    "70": "SanL.S._Acc.Flow",
    "71": "San_PHdConst",
    "72": "San_PHdVar",
    "73": "San_PHdExternal",
    "74": "San_VolFlow",
    "75": "San_Acc.Flow",
    "76": "San_T",
    "77": "San_TDiff",
    "78": "San_Spd",
    "79": "Gen_PHdExt",
    "80": "Gen_DA",
    "81": "Gen_VolFlow",
    "82": "Gen_Acc.Flow",
    "83": "ScndPHdConst",
    "84": "ScndPHdVar",
    "85": "ScndFlow",
    "86": "ScndSpd",
    "87": "HeatConcrete_PHd",
    "88": "HeatConcrete_DA",
    "90": "HeatConcrete_Flow",
    "91": "HeatBottle_Flow",
    "92": "HeatMan_MFA",
    "93": "HeatMan_Flow",
    "94": "HeatTank_MFA",
    "95": "HeatTank_Flow",
    "96": "HeatExchanger_Flow",
    "97": "HeatSource_TDiff",
    "98": "HeatSource_Flow",
    "99": "HeatDistrict_PHdConst",
    "100": "HeatDistrict_PHdVar",
    "101": "HeatDistrict_PHdExt",
    "102": "CoolConcrete_PHd",
    "103": "CoolConcrete_DA",
    "104": "CoolConcrete_TDiff",
    "105": "CoolConcrete_Flow",
    "106": "CoolBottle_Flow",
    "107": "CoolMan_MFA",
    "108": "CoolMan_Flow",
    "109": "CoolTank_MFA",
    "110": "CoolTank_Flow",
    "111": "CoolExchanger_Flow",
    "113": "CoolCondensor_Flow",
    "114": "CoolDistrict_PHdConst",
    "115": "CoolDistrict_PHdVar",
    "116": "CoolDistrict_PHdExt",
    "140": "Gen_UsrDfd"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 404,
   "documented": "404",
   "name": "Pump Command preset",
   "description": "Fallback on/off command.",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": {
    "0": "device/functionOn preset"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 405,
   "documented": "405",
   "name": "setpointSignalSource preset",
   "description": "Fallback setpoint source.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "1": "IF-Module",
    "6": "Internal",
    "7": "EXT 1",
    "8": "EXT 2",
    "9": "INVALID",
    "10": "EXT 3",
    "11": "EXT 4"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 408,
   "documented": "408",
   "name": "pidKp",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 409,
   "documented": "409",
   "name": "pidTi",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "scale_factor_ref": null,
   "units": "s",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 410,
   "documented": "410",
   "name": "pidTd",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "scale_factor_ref": null,
   "units": "s",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 412,
   "documented": "412",
   "name": "dutyPointRel aux.",
   "description": "Module 3.01+.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.5,
   "scale_factor_ref": null,
   "units": "%",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 413,
   "documented": "413",
   "name": "controlFunction aux.",
   "description": "Module 3.01+.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "1": "Gen_Spd",
    "3": "Gen_PHdConst",
    "4": "Gen_PHdVar",
    "9": "Gen_T",
    "10": "Gen_TDiff",
    "15": "INVALID",
    "16": "HeatRadiator_PHd",
    "17": "HeatRadiator_DA",
    "18": "HeatRadiator_T",
    "19": "HeatFloor_PHd",
    "20": "HeatFloor_DA",
    "21": "HeatFloor_T",
    "22": "HeatCeiling_PHd",
    "23": "HeatCeiling_DA",
    "24": "HeatCeiling_T",
    "25": "HeatFan_PHd",
    "26": "HeatFan_DA",
    "27": "HeatFan_T",
    "28": "HeatB._T",
    "29": "HeatB._TDiff",
    "30": "HeatB._Acc.Flow",
    "31": "HeatE._T",
    "32": "HeatE._TDiff",
    "33": "HeatE._Acc.Flow",
    "34": "Heat_PHdConst",
    "35": "Heat_PHdVar",
    "36": "Heat_PHdExt",
    "37": "Heat_DA",
    "38": "Heat_VolFlow",
    "39": "Heat_Acc.Flow",
    "40": "Heat_T",
    "41": "Heat_TDiff",
    "42": "Heat_Spd",
    "43": "CoolCeiling_PHd",
    "44": "CoolCeiling_DA",
    "45": "CoolCeiling_T",
    "46": "CoolFloor_PHd",
    "47": "CoolFloor_DA",
    "48": "CoolFloor_T",
    "49": "CoolFan_PHd",
    "50": "CoolFan_DA",
    "51": "CoolFan_T",
    "52": "CoolB._T",
    "53": "CoolB._TDiff",
    "54": "CoolB._Acc.Flow",
    "55": "CoolE._T",
    "56": "CoolE._TDiff",
    "57": "CoolE._Acc.Flow",
    "58": "Cool_PHdConst",
    "59": "Cool_PHdVar",
    "60": "Cool_PHdExt",
    "61": "Cool_DA",
    "62": "Cool_VolFlow",
    "63": "Cool_Acc.Flow",
    "64": "Cool_T",
    "65": "Cool_TDiff",
    "66": "Cool_Spd",
    "68": "SanW.Heat._TDiff",
    "69": "SanL.S._T",
    "70": "SanL.S._Acc.Flow",
    "71": "San_PHdConst",
    "72": "San_PHdVar",
    "73": "San_PHdExternal",
    "74": "San_VolFlow",
    "75": "San_Acc.Flow",
    "76": "San_T",
    "77": "San_TDiff",
    "78": "San_Spd",
    "79": "Gen_PHdExt",
    "80": "Gen_DA",
    "81": "Gen_VolFlow",
    "82": "Gen_Acc.Flow",
    "83": "ScndPHdConst",
    "84": "ScndPHdVar",
    "85": "ScndFlow",
    "86": "ScndSpd",
    "87": "HeatConcrete_PHd",
    "88": "HeatConcrete_DA",
    "90": "HeatConcrete_Flow",
    "91": "HeatBottle_Flow",
    "92": "HeatMan_MFA",
    "93": "HeatMan_Flow",
    "94": "HeatTank_MFA",
    "95": "HeatTank_Flow",
    "96": "HeatExchanger_Flow",
    "97": "HeatSource_TDiff",
    "98": "HeatSource_Flow",
    "99": "HeatDistrict_PHdConst",
    "100": "HeatDistrict_PHdVar",
    "101": "HeatDistrict_PHdExt",
    "102": "CoolConcrete_PHd",
    "103": "CoolConcrete_DA",
    "104": "CoolConcrete_TDiff",
    "105": "CoolConcrete_Flow",
    "106": "CoolBottle_Flow",
    "107": "CoolMan_MFA",
    "108": "CoolMan_Flow",
    "109": "CoolTank_MFA",
    "110": "CoolTank_Flow",
    "111": "CoolExchanger_Flow",
    "113": "CoolCondensor_Flow",
    "114": "CoolDistrict_PHdConst",
    "115": "CoolDistrict_PHdVar",
    "116": "CoolDistrict_PHdExt",
    "140": "Gen_UsrDfd"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 414,
   "documented": "414",
   "name": "Pump Command aux.",
   "description": "Module 3.01+.",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": {
    "0": "device/functionOn aux. (module 3.01+)"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 415,
   "documented": "415",
   "name": "setpointSignalSource aux.",
   "description": "Module 3.01+.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "1": "IF-Module",
    "6": "Internal",
    "7": "EXT 1",
    "8": "EXT 2",
    "9": "INVALID",
    "10": "EXT 3",
    "11": "EXT 4"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 416,
   "documented": "416",
   "name": "parameterSetSelector",
   "description": "Which parameter set drives the pump (module 3.01+).",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "1": "norm",
    "2": "aux",
    "3": "preset"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 420,
   "documented": "420",
   "name": "flow limit. max",
   "description": "Module 3.02+.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "scale_factor_ref": null,
   "units": "m³/h",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 422,
   "documented": "422",
   "name": "flow limit. min",
   "description": "Module 3.02+.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "scale_factor_ref": null,
   "units": "m³/h",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 424,
   "documented": "424",
   "name": "flow limit. off",
   "description": "Module 3.02+.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "scale_factor_ref": null,
   "units": "m³/h",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 426,
   "documented": "426",
   "name": "flowZeroSetpointRed.Factor",
   "description": "Module 3.02+.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.5,
   "scale_factor_ref": null,
   "units": "%",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 427,
   "documented": "427",
   "name": "flowNominal4Ctrl.Fun.",
   "description": "Module 3.02+.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "scale_factor_ref": null,
   "units": "m³/h",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  }
 ],
 "integration": {
  "summary": "Set bus address, baud (parameter A) and frame (parameter C) in the pump menu, then write the control mode (H 42), the duty point (H 1) and the pump command (H 40). Poll status (I 404 if present), error code (I 940) and the measured values in the I 1-I 10 block.",
  "minimum_registers": [
   {
    "table": "holding_register",
    "address": 40,
    "why": "On/off command (bit 3 = 1 when writing, if listed)"
   },
   {
    "table": "holding_register",
    "address": 42,
    "why": "Control mode"
   },
   {
    "table": "holding_register",
    "address": 1,
    "why": "Setpoint (duty point, 0.5 % steps)"
   },
   {
    "table": "input_register",
    "address": 404,
    "why": "Operation status flags"
   },
   {
    "table": "input_register",
    "address": 940,
    "why": "Active warning/error code"
   },
   {
    "table": "input_register",
    "address": 1,
    "why": "Actual pressure"
   },
   {
    "table": "input_register",
    "address": 2,
    "why": "Flow"
   },
   {
    "table": "input_register",
    "address": 4,
    "why": "Power input"
   }
  ],
  "enable": "Plug in the CIF module Modbus RTU and set the bus address (menu <5.2.3.0>), baud rate (parameter A, <5.2.4.0>: 5 = 9600, 6 = 19200, 7 = 38400 ...) and frame (parameter C, <5.2.5.0>: 2 = 8N1, 3 = 8N2, 6 = 8E1, 10 = 8O1). OFF as bus address disables the interface.",
  "watchdog": "The bus command timer (H 300, timeout in H 400 where supported) can switch the pump to the preset command, mode and duty point (H 402-405) when the master stops refreshing it.",
  "quirks": [
   "Register numbers are raw wire addresses; do not subtract 1.",
   "Duty points are in 0.5 % steps (200 = 100 %).",
   "Unsupported control-mode values are ignored by the pump."
  ],
  "setup": [
   "Where a setpointSignalSource register is listed, select IF-Module (value 1) as the setpoint source if the duty point should come from the bus.",
   "Terminate the RS-485 line at both ends."
  ],
  "gotchas": [
   "Temperatures are in kelvin.",
   "Last write wins between the bus, the pump display and other remote controls."
  ]
 },
 "page": "https://easymodbus.com/modbus-register-maps/wilo/stratos-giga2-0-cif-modbus",
 "address_note": "address = 0-based Modbus wire (PDU) address; documented = as printed in the source.",
 "note": "Re-typed from the manufacturer's public documentation (see source) and verified against it. Registers vary by firmware and options; verify against the live device before writing."
}