 "manufacturer": "Woodward",
 "manufacturer_slug": "woodward",
 "model": "easYgen-1000 Series genset controller (Modbus RTU)",
 "model_slug": "easygen-1000",
 "short_model": "easYgen-1000",
 "aliases": [
  "easYgen-1000",
  "easYgen1000",
  "easYgen-1000 Series"
 ],
 "equipment_type": "Generator controller",
 "applies_to": "easYgen-1000 series software version 2.1xxx, transmission telegram protocol 4003, per interface manual 37393B.",
 "summary": "The easYgen-1000 is Woodward's genset controller for single units and AMF duty. On RS-485 it is a Modbus RTU slave: the visualization telegram (protocol 4003) is block-read from Modicon 450001, and control word 1 at parameter 503 starts, stops and acknowledges the set. This map covers generator and mains voltages, currents and frequency, energy and hours counters, status and alarm words, a few J1939 engine values and the remote-control word.",
 "transport": [
  "RTU"
 ],
 "defaults": {
  "unit_id": null,
  "baud": null,
  "parity": null,
  "data_bits": null,
  "stop_bits": null,
  "tcp_port": null
 },
 "addressing": {
  "convention": "Modicon",
  "note": "The manual uses Modicon numbers. Telegram word No. n is Modicon 450000 + n; the manual says 450001 may become bus address 50000, so word n is wire address 49999 + n. Parameters use Modicon 40000 + (parameter ID + 1), so control word 1 (parameter 503) is 40504 = wire address 503."
 },
 "default_word_order": "ABCD",
 "firmware": "2.1xxx",
 "source": {
  "title": "easYgen-1000 Series Interfaces - Interface Description, Software Version 2.1xxx",
  "doc_number": "37393B",
  "revision_date": "2008-07-02",
  "url": "https://www.woodward.com/products/publication-asset/37393",
  "pages": "pp. 10-11 (telegrams), pp. 13-19 (Modbus RTU slave, addressing, parameters, exceptions), pp. 41-52 (transmission telegram), p. 53 (remote control telegram)"
 },
 "notes": [
  "32-bit values are listed as a High word row followed by a Low word row, so the high word sits at the lower address (ABCD).",
  "The telegram prints units and resolution but no signed/unsigned type. Voltages, currents, frequency, energy and hours cannot be negative, so the unsigned type here reads them correctly either way.",
  "Left out: generator and mains real power, reactive power and power factor (words 10, 13, 50, 53, 56, 59, 61-65), because the telegram does not say whether they are signed and they can go negative; analog inputs T1/T2 (no scaling given); hours/days until maintenance; the system state bits 0-5 of word 34, whose labels sit between two bit rows; diagnostic (DM1/DM2) SPN/FMT words and most J1939 engine values.",
  "Words 112-168 come from an engine ECU over J1939 and only hold data when one is connected and configured.",
  "Parameters (configuration range 40001-450000) are read or written one at a time with a length that matches the parameter data type; the full parameter list is in configuration manual 37391, not this document."
 ],
 "registers": [
  {
   "table": "holding_register",
   "address": 503,
   "documented": "503 (40504)",
   "name": "Control word 1",
   "description": "Remote start / stop / acknowledge; act on a 0-to-1 transition.",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": {
    "0": "Remote start (rising edge)",
    "1": "Remote stop (rising edge)",
    "2": "Must be 0",
    "3": "Must be 0",
    "4": "Remote acknowledge (rising edge, send twice)"
   }
  },
  {
   "table": "holding_register",
   "address": 50000,
   "documented": "No. 1 (450001)",
   "name": "Protocol number",
   "description": "Reads 4003 for the easYgen-1000 series.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 50001,
   "documented": "No. 2 (450002)",
   "name": "Generator voltage L1-L2",
   "description": "",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 0.1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "V",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 50003,
   "documented": "No. 4 (450004)",
   "name": "Generator frequency",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "Hz",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 50004,
   "documented": "No. 5 (450005)",
   "name": "Generator voltage L1-N",
   "description": "",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 0.1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "V",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 50006,
   "documented": "No. 7 (450007)",
   "name": "Mains frequency",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "Hz",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 50007,
   "documented": "No. 8 (450008)",
   "name": "Generator voltage L2-L3",
   "description": "",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 0.1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "V",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 50010,
   "documented": "No. 11 (450011)",
   "name": "Generator voltage L2-N",
   "description": "",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 0.1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "V",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 50013,
   "documented": "No. 14 (450014)",
   "name": "Generator voltage L3-L1",
   "description": "",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 0.1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "V",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 50015,
   "documented": "No. 16 (450016)",
   "name": "Engine speed (pickup)",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "rpm",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 50016,
   "documented": "No. 17 (450017)",
   "name": "Generator voltage L3-N",
   "description": "",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 0.1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "V",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 50018,
   "documented": "No. 19 (450019)",
   "name": "Battery voltage",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "V",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 50019,
   "documented": "No. 20 (450020)",
   "name": "Mains voltage L1-L2",
   "description": "",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 0.1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "V",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 50022,
   "documented": "No. 23 (450023)",
   "name": "Mains voltage L1-N",
   "description": "",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 0.1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "V",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 50025,
   "documented": "No. 26 (450026)",
   "name": "Mains voltage L2-L3",
   "description": "",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 0.1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "V",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 50027,
   "documented": "No. 28 (450028)",
   "name": "Discrete input state",
   "description": "Physical input state; NO/NC setting is ignored.",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "15": "Discrete input D1",
    "14": "Discrete input D2",
    "13": "Discrete input D3",
    "12": "Discrete input D4",
    "11": "Discrete input D5",
    "10": "Discrete input D6",
    "9": "Discrete input D7",
    "8": "Discrete input D8"
   }
  },
  {
   "table": "holding_register",
   "address": 50028,
   "documented": "No. 29 (450029)",
   "name": "Mains voltage L2-N",
   "description": "",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 0.1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "V",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 50030,
   "documented": "No. 31 (450031)",
   "name": "Relay state",
   "description": "",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "15": "Relay R1",
    "14": "Relay R2",
    "13": "Relay R3",
    "12": "Relay R4",
    "11": "Relay R5",
    "10": "Relay R6",
    "9": "Relay R7",
    "8": "Relay R8",
    "7": "Relay R9",
    "6": "Relay R10",
    "5": "Relay R11"
   }
  },
  {
   "table": "holding_register",
   "address": 50031,
   "documented": "No. 32 (450032)",
   "name": "Mains voltage L3-L1",
   "description": "",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 0.1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "V",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 50033,
   "documented": "No. 34 (450034)",
   "name": "System state (operating mode)",
   "description": "",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "8": "Operating mode STOP",
    "7": "Operating mode MANUAL",
    "6": "Operating mode AUTOMATIC"
   }
  },
  {
   "table": "holding_register",
   "address": 50034,
   "documented": "No. 35 (450035)",
   "name": "Mains voltage L3-N",
   "description": "",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 0.1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "V",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 50036,
   "documented": "No. 37 (450037)",
   "name": "Alarm class",
   "description": "",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "0": "Alarm class A",
    "1": "Alarm class B",
    "2": "Alarm class C",
    "3": "Alarm class D",
    "4": "Alarm class E",
    "5": "Alarm class F"
   }
  },
  {
   "table": "holding_register",
   "address": 50037,
   "documented": "No. 38 (450038)",
   "name": "Generator current L1",
   "description": "",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "mA",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 50039,
   "documented": "No. 40 (450040)",
   "name": "Discrete inputs with alarm class",
   "description": "Bit set when the input is configured as an alarm input and active.",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "15": "Discrete input D1",
    "14": "Discrete input D2",
    "13": "Discrete input D3",
    "12": "Discrete input D4",
    "11": "Discrete input D5",
    "10": "Discrete input D6",
    "9": "Discrete input D7",
    "8": "Discrete input D8"
   }
  },
  {
   "table": "holding_register",
   "address": 50040,
   "documented": "No. 41 (450041)",
   "name": "Generator current L2",
   "description": "",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "mA",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 50042,
   "documented": "No. 43 (450043)",
   "name": "Alarms 1",
   "description": "",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "15": "Overspeed limit 1",
    "14": "Overspeed limit 2",
    "13": "Underspeed limit 1",
    "12": "Underspeed limit 2",
    "11": "Unintended stop",
    "10": "Speed detection alarm",
    "9": "Stop failure",
    "8": "GCB close failure",
    "7": "GCB open failure",
    "6": "MCB close failure",
    "5": "MCB open failure",
    "3": "Start failure",
    "2": "Maintenance days expired",
    "1": "Maintenance hours expired"
   }
  },
  {
   "table": "holding_register",
   "address": 50043,
   "documented": "No. 44 (450044)",
   "name": "Generator current L3",
   "description": "",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "mA",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 50045,
   "documented": "No. 46 (450046)",
   "name": "Generator alarms 1",
   "description": "",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "15": "Overfrequency limit 1",
    "14": "Overfrequency limit 2",
    "13": "Underfrequency limit 1",
    "12": "Underfrequency limit 2",
    "11": "Overvoltage limit 1",
    "10": "Overvoltage limit 2",
    "9": "Undervoltage limit 1",
    "8": "Undervoltage limit 2",
    "7": "Overcurrent limit 1",
    "6": "Overcurrent limit 2",
    "5": "Overcurrent limit 3",
    "4": "Reverse/reduced power limit 1",
    "3": "Reverse/reduced power limit 2",
    "2": "Overload limit 1",
    "1": "Overload limit 2"
   }
  },
  {
   "table": "holding_register",
   "address": 50046,
   "documented": "No. 47 (450047)",
   "name": "Mains current L1",
   "description": "",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "mA",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 50048,
   "documented": "No. 49 (450049)",
   "name": "Mains alarms",
   "description": "",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "6": "Mains overfrequency (emergency power)",
    "5": "Mains underfrequency (emergency power)",
    "4": "Mains overvoltage (emergency power)",
    "3": "Mains undervoltage (emergency power)",
    "2": "Mains phase rotation wrong",
    "1": "Mains load limit 1 (LogicsManager)",
    "0": "Mains load limit 2 (LogicsManager)"
   }
  },
  {
   "table": "holding_register",
   "address": 50051,
   "documented": "No. 52 (450052)",
   "name": "Analog input wire break",
   "description": "",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "2": "Wire break analog input T2",
    "1": "Wire break analog input T1"
   }
  },
  {
   "table": "holding_register",
   "address": 50054,
   "documented": "No. 55 (450055)",
   "name": "Analog inputs and battery monitoring",
   "description": "",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "7": "Analog input T2 limit 2",
    "6": "Analog input T2 limit 1",
    "5": "Analog input T1 limit 2",
    "4": "Analog input T1 limit 1",
    "3": "Battery overvoltage limit 2",
    "2": "Battery undervoltage limit 2",
    "1": "Battery overvoltage limit 1",
    "0": "Battery undervoltage limit 1"
   }
  },
  {
   "table": "holding_register",
   "address": 50057,
   "documented": "No. 58 (450058)",
   "name": "System state",
   "description": "",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "15": "Turning (gas engine)",
    "14": "Ignition on (gas engine)",
    "13": "Dead bus start GCB",
    "12": "Dead bus start MCB",
    "11": "Starter / fuel solenoid (diesel) or gas valve (gas)",
    "10": "Start pause",
    "9": "Engine post-run",
    "8": "Engine will be stopped",
    "7": "Preglow (diesel)",
    "6": "Crank protection",
    "5": "Emergency power (AMF) / critical mode",
    "4": "Post-run auxiliary services",
    "3": "Mains settling",
    "2": "Pre-run auxiliary services",
    "1": "Emergency power operation (AMF)",
    "0": "Critical mode (sprinkler) operation"
   }
  },
  {
   "table": "holding_register",
   "address": 50066,
   "documented": "No. 67 (450067)",
   "name": "Generator alarms 2",
   "description": "",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "15": "Load imbalance limit 1",
    "14": "Load imbalance limit 2",
    "13": "Voltage asymmetry",
    "12": "Ground fault limit 1",
    "11": "Ground fault limit 2",
    "10": "Generator phase rotation wrong",
    "9": "Generator load limit 1",
    "8": "Generator load limit 2",
    "7": "Inverse-time overcurrent"
   }
  },
  {
   "table": "holding_register",
   "address": 50067,
   "documented": "No. 68 (450068)",
   "name": "Real energy",
   "description": "",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 0.01,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "MWh",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 50069,
   "documented": "No. 70 (450070)",
   "name": "LogicsManager flags",
   "description": "",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "15": "Flag 1 true",
    "14": "Flag 2 true",
    "13": "Flag 3 true",
    "12": "Flag 4 true",
    "11": "Flag 5 true",
    "10": "Flag 6 true",
    "9": "Flag 7 true",
    "8": "Flag 8 true"
   }
  },
  {
   "table": "holding_register",
   "address": 50070,
   "documented": "No. 71 (450071)",
   "name": "Reactive energy",
   "description": "",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 0.01,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "Mvarh",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 50073,
   "documented": "No. 74 (450074)",
   "name": "Generator ground current",
   "description": "",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "mA",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 50075,
   "documented": "No. 76 (450076)",
   "name": "External discrete inputs with alarm class",
   "description": "",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "15": "External input DEx16",
    "14": "External input DEx15",
    "13": "External input DEx14",
    "12": "External input DEx13",
    "11": "External input DEx12",
    "10": "External input DEx11",
    "9": "External input DEx10",
    "8": "External input DEx09",
    "7": "External input DEx08",
    "6": "External input DEx07",
    "5": "External input DEx06",
    "4": "External input DEx05",
    "3": "External input DEx04",
    "2": "External input DEx03",
    "1": "External input DEx02",
    "0": "External input DEx01"
   }
  },
  {
   "table": "holding_register",
   "address": 50078,
   "documented": "No. 79 (450079)",
   "name": "External relay outputs",
   "description": "",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "15": "External relay REx16",
    "14": "External relay REx15",
    "13": "External relay REx14",
    "12": "External relay REx13",
    "11": "External relay REx12",
    "10": "External relay REx11",
    "9": "External relay REx10",
    "8": "External relay REx09",
    "7": "External relay REx08",
    "6": "External relay REx07",
    "5": "External relay REx06",
    "4": "External relay REx05",
    "3": "External relay REx04",
    "2": "External relay REx03",
    "1": "External relay REx02",
    "0": "External relay REx01"
   }
  },
  {
   "table": "holding_register",
   "address": 50079,
   "documented": "No. 80 (450080)",
   "name": "External discrete inputs",
   "description": "",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "15": "External input DEx16",
    "14": "External input DEx15",
    "13": "External input DEx14",
    "12": "External input DEx13",
    "11": "External input DEx12",
    "10": "External input DEx11",
    "9": "External input DEx10",
    "8": "External input DEx09",
    "7": "External input DEx08",
    "6": "External input DEx07",
    "5": "External input DEx06",
    "4": "External input DEx05",
    "3": "External input DEx04",
    "2": "External input DEx03",
    "1": "External input DEx02",
    "0": "External input DEx01"
   }
  },
  {
   "table": "holding_register",
   "address": 50111,
   "documented": "No. 112 (450112)",
   "name": "J1939 engine speed (SPN 190)",
   "description": "From the engine ECU over J1939.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 0.1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "rpm",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 50114,
   "documented": "No. 115 (450115)",
   "name": "J1939 total engine hours (SPN 247)",
   "description": "From the engine ECU over J1939.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "h",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 50119,
   "documented": "No. 120 (450120)",
   "name": "J1939 engine oil pressure (SPN 100)",
   "description": "From the engine ECU over J1939.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "kPa",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 50169,
   "documented": "No. 170 (450170)",
   "name": "Hours of operation",
   "description": "",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "h",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 50172,
   "documented": "No. 173 (450173)",
   "name": "ECU lamp alarms (Alarm 2)",
   "description": "",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "0": "Amber warning lamp from ECU (J1939)",
    "1": "Red stop lamp from ECU (J1939)"
   }
  },
  {
   "table": "holding_register",
   "address": 50173,
   "documented": "No. 174 (450174)",
   "name": "Number of starts",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 50177,
   "documented": "No. 178 (450178)",
   "name": "Hours of operation (1/100 h)",
   "description": "",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 0.01,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "h",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 50180,
   "documented": "No. 181 (450181)",
   "name": "Free adjustable hours counter",
   "description": "",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 0.01,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "h",
   "access": "R",
   "values": null,
   "bits": null
  }
 ],
 "integration": {
  "summary": "Block-read up to 128 holding registers from wire address 50000 (Modicon 450001) for measurements, status and alarms. To start or stop the set, write 0 and then the start (bit 0) or stop (bit 1) bit to parameter 503; acknowledge with two rising edges of bit 4.",
  "minimum_registers": [
   {
    "table": "holding_register",
    "address": 50000,
    "why": "Protocol number (4003) to confirm the map"
   },
   {
    "table": "holding_register",
    "address": 50001,
    "why": "Generator voltage L1-L2"
   },
   {
    "table": "holding_register",
    "address": 50003,
    "why": "Generator frequency"
   },
   {
    "table": "holding_register",
    "address": 50037,
    "why": "Generator current L1"
   },
   {
    "table": "holding_register",
    "address": 50033,
    "why": "Operating mode STOP/MANUAL/AUTO"
   },
   {
    "table": "holding_register",
    "address": 50057,
    "why": "System state"
   },
   {
    "table": "holding_register",
    "address": 50036,
    "why": "Active alarm classes"
   },
   {
    "table": "holding_register",
    "address": 503,
    "why": "Remote start / stop / acknowledge"
   }
  ],
  "enable": "Select the Modbus protocol on the serial interface and set the Modbus slave ID (0-255) and reply delay (0-1000 ms) in the controller. For remote start/stop the LogicsManager must use command variable 04.13; see application manual 37394. Parameter writes need the code level 2 password for that interface (parameter 10401 for serial interface 1).",
  "watchdog": "Interface watchdogs exist but are disabled by default; they are described in the device manual, not in this document.",
  "quirks": [
   "Start, stop and acknowledge react only to a rising edge: write 0 first, then the bit.",
   "Acknowledge must be sent twice: the first edge silences the horn, the second clears faults that are gone.",
   "Some PLCs and tools offset addresses by one; the manual notes 450001 may become bus address 50000."
  ],
  "setup": [
   "RS-485 half or full duplex is supported. Set the baud rate, parity and stop bits in the controller's serial interface menu to match the master."
  ],
  "gotchas": [
   "Writing control word 1 can start or stop the engine; make sure the site is safe first.",
   "Bits 2 and 3 of control word 1 must always be 0."
  ]
 },
 "page": "https://easymodbus.com/modbus-register-maps/woodward/easygen-1000",
 "address_note": "address = 0-based Modbus wire (PDU) address; documented = as printed in the source.",
 "note": "Re-typed from the manufacturer's public documentation (see source) and verified against it. Registers vary by firmware and options; verify against the live device before writing."
}