Variable frequency drive · Modbus register map

Yaskawa A1000 AC drive (MEMOBUS/Modbus RTU) Modbus register map

Updated 24 October 2026

Short answer

Yaskawa's high-performance vector drive with a built-in RS-422/RS-485 MEMOBUS/Modbus RTU port on terminal block TB5. Commands are written to hex registers 0001H-001FH, status, fault and alarm words and key monitors are read from 0020H upwards, and every parameter has its own hex register in the parameter list. This map covers the command block, status/fault/alarm words, the main monitors with fixed units, fault and alarm codes, and the b1/H5 setup parameters.

This page lists 66 Modbus registers for the Yaskawa A1000 AC drive (MEMOBUS/Modbus RTU) — 13 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Yaskawa’s own free documentation (linked below) and checked against it.

Manufacturer
Yaskawa
Model
A1000 AC drive (MEMOBUS/Modbus RTU)
Equipment type
Variable frequency drive
Registers
66 (13 writable)
Transport
Modbus RTU
Default unit ID
31
Default serial
9600 baud, 8N1
Documented addressing
hexadecimal, 0-based
Firmware
Drive software up to PRG 1021-1024 (per the manual's revision history)
Also known as
CIMR-AU, CIMR-AUA, A1000 High Performance Vector Control Drive
Source document
YASKAWA AC Drive-A1000 High Performance Vector Control Drive Technical Manual · SIEP C710616 41H · rev. 2022-03
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: Yaskawa A1000 AC drive (MEMOBUS/Modbus RTU)

Integration in brief

Set H5-01..H5-03 at the keypad and power-cycle, set b1-01 = 2 and b1-02 = 2 so the frequency reference and Run command come from Modbus, then write 0001H (run bits) and 0002H (frequency reference) together with function 10H and poll 0020H-002CH for status, faults and alarms.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
HR 1Operation commands / multi-function inputsBITMAP16Run/stop, direction, fault resetRead/write
HR 2Frequency referenceUINT16Frequency reference (o1-03 units)Read/write
HR 32Drive Status 1BITMAP16Drive Status 1: run/ready/faultRead
HR 33Fault Contents 1BITMAP16Fault Contents 1Read
HR 36Output frequencyUINT16Output frequencyRead
HR 44Drive Status 2BITMAP16Drive Status 2 incl. comm timeout bitRead
HR 49DC bus voltageUINT16DC bus voltageRead
HR 128U2-01 Current FaultUINT16U2-01 current fault codeRead

Enable Modbus control & writes

Set H5-01 slave address (default 1F hex = 31, range 0-FF hex), H5-02 speed (default 3 = 9600 bps) and H5-03 parity (default 0 = none), then cycle power. For control set b1-01 = 2 and b1-02 = 2 (b1-15/b1-16 for external reference 2). H5-12 decides whether 0001H bits 0/1 mean FWD/REV run or Run + direction. Network inputs are ORed with terminals S1-S8.

Communication loss & watchdog

H5-05 = 1 (default) enables CE detection, H5-09 CE Detection Time (0.0-10.0 s, default 2.0 s) sets the timeout, and H5-04 selects the reaction: 0 ramp to stop, 1 coast, 2 fast stop, 3 alarm only and keep running (default). Drive Status 2 (002CH) bit F shows a communication timeout.

Byte order & addressing

Network setup

Watch out for

Yaskawa A1000 AC drive (MEMOBUS/Modbus RTU) Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

66 of 66 shown
Yaskawa A1000 AC drive (MEMOBUS/Modbus RTU) Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
HR1doc 0001HOperation commands / multi-function inputsRun, direction, external fault, fault reset and virtual inputs.BITMAP16Read/writebit 0 = H5-12=0: 1 = forward run / 0 = stop; H5-12=1: 1 = run / 0 = stop; bit 1 = H5-12=0: 1 = reverse run / 0 = stop; H5-12=1: 1 = reverse / 0 = forward; bit 2 = External fault EF0; bit 3 = Fault reset; bit 4 = Multi-function input 1 (ComRef when H1-01 = 40); bit 5 = Multi-function input 2 (ComCtrl when H1-02 = 41); bit 6 = Multi-function input 3; bit 7 = Multi-function input 4; bit 8 = Multi-function input 5; bit 9 = Multi-function input 6; bit 10 = Multi-function input 7; bit 11 = Multi-function input 8
HR2doc 0002HFrequency referenceUnits follow o1-03 (0 = 0.01 Hz).UINT16Read/write
HR3doc 0003HOutput voltage gain20-2000 (2.0-200.0%); 1000 at power-up.UINT16× 0.1%Read/write
HR4doc 0004HTorque reference / torque limitSigned; torque control only; enable with 000FH bit 2.INT16× 0.1%Read/write
HR5doc 0005HTorque compensationSigned; torque control only; enable with 000FH bit 3.INT16× 0.1%Read/write
HR6doc 0006HPID targetSigned; enable with 000FH bit 1.INT16× 0.01%Read/write
HR9doc 0009HMulti-function digital output settingDrive the digital outputs from the network.BITMAP16Read/writebit 0 = Contact output 1 (M1-M2); bit 1 = Contact output 2 (M3-M4); bit 2 = Contact output 3 (M5-M6); bit 6 = Enables the function in bit 7; bit 7 = Fault contact output MA/MB-MC
HR10doc 000AHPulse output terminal MP setting0-32000 Hz.UINT16HzRead/write
HR15doc 000FHControl selection settingEnables network PID, torque and broadcast inputs.BITMAP16Read/writebit 1 = PID setpoint input from MEMOBUS; bit 2 = Torque reference / limit from MEMOBUS; bit 3 = Torque compensation from MEMOBUS; bit 12 = Enable terminal S5 input for broadcast data; bit 13 = Enable terminal S6 input for broadcast data; bit 14 = Enable terminal S7 input for broadcast data; bit 15 = Enable terminal S8 input for broadcast data
HR32doc 0020HDrive Status 1BITMAP16Readbit 0 = During run; bit 1 = During reverse; bit 2 = Drive ready; bit 3 = Fault; bit 4 = Data setting error; bit 5 = Contact output 1 (M1-M2) on; bit 6 = Contact output 2 (M3-M4) on; bit 7 = Contact output 3 (M5-M6) on; bit 14 = ComRef enabled; bit 15 = ComCtrl enabled
HR33doc 0021HFault Contents 1Active fault groups.BITMAP16Readbit 0 = oC overcurrent, GF ground fault; bit 1 = ov overvoltage (Appendix C misprints it as 'Drive Overheat Warning'); bit 2 = oL2 drive overload; bit 3 = oH1 overheat 1, oH2 drive overheat warning; bit 4 = rr braking transistor, rH braking resistor overheat; bit 6 = FbL/FbH PID feedback loss; bit 7 = EF to EF8 external fault; bit 8 = CPFxx hardware fault (incl. oFx); bit 9 = oL1 motor overload, oL3/oL4 overtorque, UL3/UL4 undertorque; bit 10 = PGo, PGoH, oS, dEv; bit 11 = Uv main circuit undervoltage; bit 12 = Uv1, Uv2, Uv3 undervoltage; bit 13 = LF output / PF input phase loss; bit 14 = CE MEMOBUS / bUS option communication error; bit 15 = oPr external operator connection fault
HR34doc 0022HData Link StatusResult of the last parameter write.BITMAP16Readbit 0 = Writing data or switching motors; bit 3 = Upper or lower limit error; bit 4 = Data conformity error; bit 5 = Writing to EEPROM; bit 6 = 0 = write to EEPROM, 1 = RAM only (only when H5-17 = 1)
HR35doc 0023HFrequency reference (monitor)Units follow o1-03 (0 = 0.01 Hz).UINT16Read
HR36doc 0024HOutput frequencyUnits follow o1-03 (0 = 0.01 Hz).UINT16Read
HR41doc 0029HFault Contents 2BITMAP16Readbit 0 = SC output short circuit / IGBT fault; bit 1 = GF ground fault; bit 2 = PF input phase loss; bit 3 = LF output phase loss; bit 4 = rH braking resistor overheat; bit 6 = oH4 motor overheat 2 (PTC)
HR42doc 002AHAlarm Contents 1Active alarms (minor faults).BITMAP16Readbit 2 = EF forward/reverse run command input error; bit 3 = bb drive baseblock; bit 4 = oL3 overtorque 1; bit 5 = oH heatsink overheat; bit 6 = ov overvoltage (Appendix C misprints it as 'Drive Overheat Warning'); bit 7 = Uv undervoltage; bit 8 = FAn internal fan fault; bit 9 = CE MEMOBUS communication error; bit 10 = bUS option communication error; bit 11 = UL3/UL4 undertorque; bit 12 = oH3 motor overheat; bit 13 = FbL/FbH PID feedback loss; bit 15 = CALL serial transmission error
HR43doc 002BHInput terminal statusBITMAP16Readbit 0 = Terminal S1 closed; bit 1 = Terminal S2 closed; bit 2 = Terminal S3 closed; bit 3 = Terminal S4 closed; bit 4 = Terminal S5 closed; bit 5 = Terminal S6 closed; bit 6 = Terminal S7 closed; bit 7 = Terminal S8 closed
HR44doc 002CHDrive Status 2BITMAP16Readbit 0 = During run; bit 1 = Zero speed; bit 2 = Speed agree; bit 3 = User speed agree; bit 4 = Frequency detection 1; bit 5 = Frequency detection 2; bit 6 = Drive ready; bit 7 = During undervoltage; bit 8 = During baseblock; bit 9 = Frequency reference from operator keypad; bit 10 = Run command from operator keypad; bit 11 = Over/undertorque 1, 2; bit 12 = Frequency reference loss; bit 13 = During fault restart; bit 14 = Fault; bit 15 = Communication timeout
HR45doc 002DHOutput terminal statusBITMAP16Readbit 0 = Contact output 1 (M1-M2); bit 1 = Contact output 2 (M3-M4); bit 2 = Contact output 3 (M5-M6); bit 7 = Fault contact output MA/MB-MC
HR49doc 0031HDC bus voltageUINT16VRead
HR52doc 0034HProduct code 1Two ASCII characters; "A0" for A1000.UINT16Read
HR53doc 0035HProduct code 2Two ASCII characters: region code.UINT16Read
HR56doc 0038HPID feedbackUnsigned; 100% = maximum output frequency.UINT16× 0.1%Read
HR57doc 0039HPID inputSigned; 100% = maximum output frequency.INT16× 0.1%Read
HR58doc 003AHPID outputSigned; 100% = maximum output frequency.INT16× 0.1%Read
HR61doc 003DHCommunications error logHeld until the fault is reset.BITMAP16Readbit 0 = CRC error; bit 1 = Data length error; bit 3 = Parity error; bit 4 = Overrun error; bit 5 = Framing error; bit 6 = Timeout
HR64doc 0040HU1-01 Frequency ReferenceUnits follow o1-03 (0 = 0.01 Hz).UINT16Read
HR65doc 0041HU1-02 Output FrequencyUnits follow o1-03 (0 = 0.01 Hz).UINT16Read
HR66doc 0042HU1-03 Output Current8192 = 100% of drive rated output current.UINT16× 0.0122070312%Read
HR67doc 0043HU1-04 Control MethodControl method set in A1-02.UINT16Read0 = V/f Control; 1 = V/f Control with PG; 2 = Open Loop Vector Control; 3 = Closed Loop Vector Control; 5 = Open Loop Vector Control for PM; 6 = Advanced Open Loop Vector Control for PM; 7 = Closed Loop Vector Control for PM
HR69doc 0045HU1-06 Output Voltage ReferenceUINT16× 0.1VRead
HR70doc 0046HU1-07 DC Bus VoltageUINT16VRead
HR75doc 004BHU1-12 Drive StatusBITMAP16Readbit 0 = During run; bit 1 = During zero speed; bit 2 = During reverse run; bit 3 = During fault reset signal input; bit 4 = During speed agree; bit 5 = Drive ready; bit 6 = Alarm; bit 7 = Fault; bit 8 = During operation error (oPExx); bit 9 = During momentary power loss; bit 10 = Motor 2 selected; bit 14 = ComRef / NetRef status; bit 15 = ComCtrl / NetCtrl status
HR76doc 004CHU4-01 Cumulative Operation TimeReported in 10 h units over Modbus.UINT16× 10hRead
HR103doc 0067HU4-03 Cooling Fan Operation TimeReported in 10 h units over Modbus.UINT16× 10hRead
HR117doc 0075HU4-02 Number of Run CommandsCount of Run commands (wraps after 65535).UINT16Read
HR124doc 007CHU4-05 Capacitor MaintenancePercent of expected capacitor life used.UINT16%Read
HR126doc 007EHU4-04 Cooling Fan MaintenancePercent of expected fan life used.UINT16%Read
HR127doc 007FHAlarm codeCode of the active alarm (minor fault).UINT16Read1 = Undervoltage (Uv); 2 = DC Bus Overvoltage (ov) (printed in Table C.7 as 'Drive Overheat Warning (ov)'); 3 = Heatsink Overheat (oH); 4 = Drive Overheat Warning (oH2); 5 = Overtorque 1 (oL3); 6 = Overtorque 2 (oL4); 7 = Forward/Reverse Run Command Input Error (EF); 8 = Drive Baseblock (bb); 9 = External Fault 3, input terminal S3 (EF3); 10 = External Fault 4, input terminal S4 (EF4); 11 = External Fault 5, input terminal S5 (EF5); 12 = External Fault 6, input terminal S6 (EF6); 13 = External Fault 7, input terminal S7 (EF7); 14 = External Fault 8, input terminal S8 (EF8); 15 = Internal Fan Fault (FAn); 16 = Overspeed (oS); 17 = Speed Deviation (dEv); 18 = PG Disconnected (PGo); 20 = MEMOBUS/Modbus Communication Error (CE); 21 = Option Communication Error (bUS); 22 = Serial Communication Transmission Error (CALL); 23 = Motor Overload (oL1); 24 = Drive Overload (oL2); 26 = Option Card External Fault (EF0); 27 = Motor Switch command input during run (rUn); 29 = Serial Communication Transmission Error (CALL); 30 = Undertorque Detection 1 (UL3); 31 = Undertorque Detection 2 (UL4); 32 = MEMOBUS/Modbus Communication Test Mode Error (SE); 34 = Motor Overheat (oH3); 39 = PID Feedback Loss (FbL); 40 = PID Feedback Loss (FbH); 42 = Drive Disabled (dnE); 43 = PG Disconnected (PGo); 49 = MECHATROLINK Watchdog Timer Error (E5); 50 = Station Address Setting Error (AEr); 51 = MECHATROLINK Comm. Cycle Setting Error (CyC); 52 = High Current Alarm (HCA); 53 = Cooling Fan Maintenance Time (LT-1); 54 = Capacitor Maintenance Time (LT-2); 56 = SI-S EEPROM Error (EEP); 57 = External Fault (input terminal S1) (EF1); 58 = External Fault (input terminal S2) (EF2); 59 = Safe Disable Input (HbbF); 60 = Safe Disable Input (Hbb); 61 = Mechanical Weakening Detection 1 (oL5); 62 = Mechanical Weakening Detection 2 (UL5); 63 = PLC Alarm (PA1); 64 = PLC Alarm (PA2); 65 = Output Voltage Detection Fault (voF); 66 = IGBT Maintenance Time (90%) (TrPC); 67 = Soft Charge Bypass Relay Maintenance Time (LT-3); 68 = IGBT Maintenance Time (50%) (LT-4); 69 = Braking Transistor Overload (boL); 72 = Motor Overheat (NTC Input) (oH5); 73 = DriveWorksEZ Fault (dWAL); 77 = Thermistor Disconnect (THo)
HR128doc 0080HU2-01 Current FaultCode of the fault now active.UINT16Read2 = DC Bus Undervoltage (Uv1); 3 = Control Power Supply Voltage Fault (Uv2); 4 = Undervoltage 3 (Uv3); 5 = Output Short-Circuit or IGBT Fault (SC); 6 = Ground Fault (GF); 7 = Overcurrent (oC); 8 = Overvoltage (ov) (printed in Table C.6 as 'Drive Overheat Warning (ov)'); 9 = Heatsink Overheat (oH); 10 = Overheat 1 (oH1); 11 = Motor Overload (oL1); 12 = Drive Overload (oL2); 13 = Overtorque Detection 1 (oL3); 14 = Overtorque Detection 2 (oL4); 15 = Dynamic Braking Transistor (rr); 16 = Braking Resistor Overheat (rH); 17 = External Fault at Input Terminal S3 (EF3); 18 = External Fault at Input Terminal S4 (EF4); 19 = External Fault at Input Terminal S5 (EF5); 20 = External Fault at Input Terminal S6 (EF6); 21 = External Fault at Input Terminal S7 (EF7); 22 = External Fault at Input Terminal S8 (EF8); 23 = Internal Fan Fault (FAn); 24 = Overspeed (oS); 25 = Speed Deviation (dEv); 26 = PG Disconnect (PGo); 27 = Input Phase Loss (PF); 28 = Output Phase Loss (LF); 29 = Motor Overheat (PTC input) (oH3); 30 = Digital Operator Connection (oPr); 31 = EEPROM Write Error (Err); 32 = Motor Overheat (PTC input) (oH4); 33 = MEMOBUS/Modbus Communication Error (CE); 34 = Option Communication Error (bUS); 37 = Control Fault (CF); 38 = Zero-Servo Fault (SvE); 39 = Option External Fault (EF0); 40 = PID Feedback Loss (FbL); 41 = Undertorque Detection 1 (UL3); 42 = Undertorque Detection 2 (UL4); 43 = High Slip Braking Overload (oL7); 48 = Hardware Fault (including oFx); 50 = Z Pulse Fault (dv1); 51 = Z Pulse Noise Fault Detection (dv2); 52 = Inversion Detection (dv3); 53 = Inversion Prevention Detection (dv4); 54 = Output Current Imbalance (LF2); 55 = Pullout Detection (Sto); 56 = PG Hardware Fault (PGoH); 57 = MECHATROLINK Watchdog Timer Error (E5); 59 = Too Many Speed Search Restarts (SEr); 65 = PID Feedback Loss (FbH); 66 = External Fault 1, Input Terminal S1 (EF1); 67 = External Fault 2, Input Terminal S2 (EF2); 68 = Mechanical Weakening Detection 1 (oL5); 69 = Mechanical Weakening Detection 2 (UL5); 70 = Current Offset Fault (CoF); 71 = PLC Detection Error 1 (PE1); 72 = PLC Detection Error 2 (PE2); 73 = DriveWorksEZ Fault (dWFL); 74 = EEPROM Memory DriveWorksEZ Data Error (dWF1); 77 = Output Voltage Detection Fault (voF); 78 = Braking Resistor Transistor Fault (rF); 79 = Braking Transistor Overload Fault (boL); 80 = Motor Overheat (NTC Input) (oH5); 81 = LSo Fault (LSo); 82 = Node Setup Fault (nSE); 83 = Thermistor Disconnect (THo); 91 = Initial Polarity Estimation Timeout (dv7); 95 = Power Unit Output Phase Loss 3 (LF3); 96 = Current Unbalance (UnbC); 97 = Power Supply Module Undervoltage (Uv4); 131 = A/D Conversion Error (CPF02); 132 = PWM Data Fault (CPF03); 135 = EEPROM Memory Data Error (CPF06); 136 = Terminal Board Connection Error (CPF07); 137 = EEPROM Serial Communication Fault (CPF08); 140 = RAM Fault (CPF11); 141 = Flash Memory Circuit Exception (CPF12); 142 = Watchdog Circuit Exception (CPF13); 143 = Control Circuit Fault (CPF14); 145 = Clock Fault (CPF16); 146 = Timing Fault (CPF17); 147 = Control Circuit Fault (CPF18); 148 = Control Circuit Fault (CPF19); 149 = Hardware Fault at Power Up (CPF20); 150 = Hardware Fault at Communication Start Up (CPF21); 151 = A/D Conversion Fault (CPF22); 152 = PWM Feedback Fault (CPF23); 153 = Drive Unit Signal Fault (CPF24); 154 = Terminal Board is Not Properly Connected. (CPF25); 155 = ASIC BB Circuit Error (CPF26); 156 = ASIC PWM Setting Register Error (CPF27); 157 = ASIC PWM Pattern Error (CPF28); 158 = ASIC On-delay Error (CPF29); 159 = ASIC BBON Error (CPF30); 160 = ASIC Code Error (CPF31); 161 = ASIC Start-up Error (CPF32); 162 = Watch-dog Error (CPF33); 163 = ASIC Power/Clock Error (CPF34); 164 = External A/D Converter Error (CPF35); 169 = Control Circuit Error (CPF40); 170 = Control Circuit Error (CPF41); 171 = Control Circuit Error (CPF42); 172 = Control Circuit Error (CPF43); 173 = Control Circuit Error (CPF44); 174 = Control Circuit Error (CPF45); 257 = Option Compatibility Error (oFA00); 258 = Option Not Properly Connected (oFA01); 262 = A/D Conversion Error (oFA05); 263 = Option Response Error (oFA06); 273 = Option RAM Fault (oFA10); 274 = Option Operation Mode Fault (SLMOD) (oFA11); 275 = Drive Receive CRC Error (oFA12); 276 = Drive Receive Frame Error (oFA13); 277 = Drive Receive Abort Error (oFA14); 278 = Option Receive CRC Error (oFA15); 279 = Option Receive Frame Error (oFA16); 280 = Option Receive Abort Error (oFA17); 305 = Comm. ID Error (oFA30); 306 = Model Code Error (oFA31); 307 = Sumcheck Error (oFA32); 308 = Comm. Option Timeout Waiting for Response (oFA33); 309 = MEMOBUS Timeout (oFA34); 310 = Drive Timeout Waiting for Response (oFA35); 311 = CI Check Error (oFA36); 312 = Drive Timeout Waiting for Response (oFA37); 313 = Control Command Selection Error (oFA38); 314 = Drive Timeout Waiting for Response (oFA39); 315 = Control Response Selection 1 Error (oFA40); 316 = Drive Timeout Waiting for Response (oFA41); 317 = Control Response Selection 2 Error (oFA42); 318 = Drive Timeout Waiting for Response (oFA43); 513 = Option Compatibility Error (oFb00); 514 = Option Connection Error (oFb01); 515 = Same Type of Option Card Already Connected (oFb02); 518 = A/D Conversion Error (oFb05); 519 = Option Response Error (oFb06); 529 = Option RAM Fault (oFb10); 530 = Option Operation Mode Fault (SLMOD) (oFb11); 531 = Drive Receive CRC Error (oFb12); 532 = Drive Receive Frame Error (oFb13); 533 = Drive Receive Abort Error (oFb14); 534 = Option Receive CRC Error (oFb15); 535 = Option Receive Frame Error (oFb16); 536 = Option Receive Abort Error (oFb17); 561 = Comm. ID Error (oFb30); 562 = Model Code Error (oFb31); 563 = Sumcheck Error (oFb32); 564 = Comm. option Timeout Waiting for Response (oFb33); 565 = MEMOBUS Timeout (oFb34); 566 = Drive Timeout Waiting for Response (oFb35); 567 = CI Check Error (oFb36); 568 = Drive Timeout Waiting for Response (oFb37); 569 = Control Command Selection Error (oFb38); 570 = Drive Timeout Waiting for Response (oFb39); 571 = Control Response Selection 1 Error (oFb40); 572 = Drive Timeout Waiting for Response (oFb41); 573 = Control Response Selection 2 Error (oFb42); 574 = Drive Timeout Waiting for Response (oFb43); 769 = Option Compatibility Error (oFC00); 771 = Option Not Properly Connected (oFC01); 772 = Same Type of Option Card Already Connected (oFC02); 774 = A/D Conversion Error (oFC05); 775 = Option Response Error (oFC06); 785 = Option RAM Fault (oFC10); 786 = Option Operation Mode Fault (SLMOD) (oFC11); 787 = Drive Receive CRC Error (oFC12); 788 = Drive Receive Frame Error (oFC13); 789 = Drive Receive Abort Error (oFC14); 790 = Option Receive CRC Error (oFC15); 791 = Option Receive Frame Error (oFC16); 792 = Option Receive Abort Error (oFC17); 849 = Encoder Option AD Conversion Error (oFC50); 850 = Encoder Option Analog Circuit Error (oFC51); 851 = Encoder Communication Timeout (oFC52); 852 = Encoder Communication Data Error (oFC53); 853 = Encoder Error (oFC54); 854 = Resolver Error (oFC55)
HR129doc 0081HU2-02 Previous FaultPrevious fault; same codes as U2-01.UINT16Read
HR144doc 0090HU3-01 Most Recent FaultNewest fault history entry; same codes as U2-01.UINT16Read
HR152doc 0098HU4-01 Cumulative Operation Time (upper digits)U4-01 divided by 10 (12345 h reads 1234).UINT16× 10hRead
HR153doc 0099HU4-01 Cumulative Operation Time (last digit)Ones digit of U4-01 (12345 h reads 5).UINT16hRead
HR154doc 009AHU4-03 Cooling Fan Operation Time (upper digits)U4-03 divided by 10.UINT16× 10hRead
HR155doc 009BHU4-03 Cooling Fan Operation Time (last digit)Ones digit of U4-03.UINT16hRead
HR191doc 00BFHoPE error numberNumber of the active oPExx setting error.UINT16Read
HR192doc 00C0HFault Contents 3BITMAP16Readbit 1 = Uv1 DC bus undervoltage; bit 2 = Uv2 control power supply undervoltage; bit 3 = Uv3 soft-charge bypass circuit fault; bit 4 = SC output short circuit / IGBT fault; bit 5 = GF ground fault; bit 6 = oC overcurrent; bit 7 = ov overvoltage (Appendix C misprints it as 'Drive Overheat Warning'); bit 8 = oH heatsink overheat; bit 9 = oH1 overheat 1; bit 10 = oL1 motor overload; bit 11 = oL2 drive overload; bit 12 = oL3 overtorque 1; bit 13 = oL4 overtorque 2; bit 14 = rr braking transistor fault; bit 15 = rH braking resistor overheat
HR193doc 00C1HFault Contents 4BITMAP16Readbit 0 = EF3 external fault S3; bit 1 = EF4 external fault S4; bit 2 = EF5 external fault S5; bit 3 = EF6 external fault S6; bit 4 = EF7 external fault S7; bit 5 = EF8 external fault S8; bit 6 = FAn internal fan fault; bit 7 = oS overspeed; bit 8 = dEv excessive speed deviation; bit 9 = PGo PG disconnected; bit 10 = PF input phase loss; bit 11 = LF output phase loss; bit 12 = oH3 motor overheat (PTC); bit 13 = oPr external operator connection fault; bit 14 = Err EEPROM write error; bit 15 = oH4 motor overheat fault (PTC)
HR194doc 00C2HFault Contents 5BITMAP16Readbit 0 = CE MEMOBUS communication error; bit 1 = bUS option communication error; bit 4 = CF control fault; bit 5 = SvE zero servo fault; bit 6 = EF0 option external fault; bit 7 = FbL PID feedback loss; bit 8 = UL3 undertorque 1; bit 9 = UL4 undertorque 2; bit 10 = oL7 high slip braking overload; bit 15 = Hardware fault (incl. oFx)
HR384doc 0180Hb1-01 Frequency Reference Selection 1Set 2 for frequency reference over Modbus.UINT16Read/write0 = Digital operator; 1 = Analog input terminals; 2 = MEMOBUS/Modbus communications; 3 = Option PCB; 4 = Pulse input (terminal RP)
HR385doc 0181Hb1-02 Run Command Selection 1Set 2 for Run command over Modbus.UINT16Read/write0 = Digital operator; 1 = Digital input terminals; 2 = MEMOBUS/Modbus communications; 3 = Option PCB
HR1061doc 0425HH5-01 Drive Node Address0-FF hex; 0 = no response. Power cycle to apply.UINT16Read
HR1062doc 0426HH5-02 Communication Speed SelectionPower cycle to apply.UINT16Read0 = 1200 bps; 1 = 2400 bps; 2 = 4800 bps; 3 = 9600 bps; 4 = 19200 bps; 5 = 38400 bps; 6 = 57600 bps; 7 = 76800 bps; 8 = 115200 bps
HR1063doc 0427HH5-03 Communication Parity SelectionPower cycle to apply.UINT16Read0 = No parity; 1 = Even parity; 2 = Odd parity
HR1064doc 0428HH5-04 Stopping Method after Communication ErrorReaction to a CE fault.UINT16Read0 = Ramp to stop; 1 = Coast to stop; 2 = Fast stop; 3 = Alarm only
HR1065doc 0429HH5-05 Communication Fault Detection SelectionEnables CE detection.UINT16Read0 = Disabled; 1 = Enabled
HR1066doc 042AHH5-06 Drive Transmit Wait Time5-65 ms delay before the drive replies.UINT16msRead
HR1067doc 042BHH5-07 RTS Control Selection1 for RS-485 or multi-drop RS-422.UINT16Read0 = Disabled - RTS always on; 1 = Enabled - RTS on only while sending
HR1077doc 0435HH5-09 CE Detection Time0.0-10.0 s without messages before CE.UINT16× 0.1sRead
HR1078doc 0436HH5-10 Unit Selection for Register 0025HUnit of the output voltage monitor at 0025H.UINT16Read0 = 0.1 V units; 1 = 1 V units
HR1084doc 043CHH5-11 Communications Enter Function SelectionWhether parameter writes need the Enter command.UINT16Read0 = Changes apply only after an Enter command; 1 = Changes apply immediately; Enter (0900H) still needed to save to EEPROM
HR1085doc 043DHH5-12 Run Command Method SelectionMeaning of 0001H bits 0/1.UINT16Read0 = FWD/Stop, REV/Stop; 1 = Run/Stop, FWD/REV
HR2304doc 0900HEnter command (save to EEPROM)Write 0: apply parameter writes to RAM and EEPROM.UINT16Write
HR2320doc 0910HEnter command (RAM only)Write 0: apply parameter writes to RAM only.UINT16Write
HR4513doc 11A1HH5-17 Operation when Unable to Write into EEPROMPRG 1018 and later.UINT16Read0 = Cannot write into EEPROM; 1 = Write in RAM only

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the Yaskawa A1000 AC drive (MEMOBUS/Modbus RTU)

What Modbus registers does the Yaskawa A1000 AC drive (MEMOBUS/Modbus RTU) have?

This map lists 66 registers: 66 holding registers. 13 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the Yaskawa A1000 AC drive (MEMOBUS/Modbus RTU) Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers hexadecimal, 0-based. Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Register numbers are printed in hex and go into the request unchanged: the manual's read example asks for starting register 0020H by sending 00 20, and its write example starts at 0001H (00 01). Parameters use the hex address printed under each parameter in the parameter list (H5-01 (0425) -> 0425H, b1-01 (0180) -> 0180H).

What are the minimum Modbus registers to integrate the Yaskawa A1000 AC drive (MEMOBUS/Modbus RTU)?

Start with HR 1 Operation commands / multi-function inputs (Run/stop, direction, fault reset); HR 2 Frequency reference (Frequency reference (o1-03 units)); HR 32 Drive Status 1 (Drive Status 1: run/ready/fault); HR 33 Fault Contents 1 (Fault Contents 1); HR 36 Output frequency (Output frequency); HR 44 Drive Status 2 (Drive Status 2 incl. comm timeout bit); HR 49 DC bus voltage (DC bus voltage); HR 128 U2-01 Current Fault (U2-01 current fault code).

How do I enable Modbus control of the Yaskawa A1000 AC drive (MEMOBUS/Modbus RTU)?

Set H5-01 slave address (default 1F hex = 31, range 0-FF hex), H5-02 speed (default 3 = 9600 bps) and H5-03 parity (default 0 = none), then cycle power. For control set b1-01 = 2 and b1-02 = 2 (b1-15/b1-16 for external reference 2). H5-12 decides whether 0001H bits 0/1 mean FWD/REV run or Run + direction. Network inputs are ORed with terminals S1-S8.

What happens when the Yaskawa A1000 AC drive (MEMOBUS/Modbus RTU) loses Modbus communication?

H5-05 = 1 (default) enables CE detection, H5-09 CE Detection Time (0.0-10.0 s, default 2.0 s) sets the timeout, and H5-04 selects the reaction: 0 ramp to stop, 1 coast, 2 fast stop, 3 alarm only and keep running (default). Drive Status 2 (002CH) bit F shows a communication timeout.

Where is the official Yaskawa A1000 AC drive (MEMOBUS/Modbus RTU) Modbus documentation?

The source is YASKAWA AC Drive-A1000 High Performance Vector Control Drive Technical Manual (SIEP C710616 41H), revision 2022-03, published free by Yaskawa at https://www.yaskawa.com/delegate/getAttachment?documentId=SIEPC71061641&cmd=documents&documentName=SIEPC71061641.pdf.

More Yaskawa Modbus register maps

Source: YASKAWA AC Drive-A1000 High Performance Vector Control Drive Technical Manual · SIEP C710616 41H · rev. 2022-03. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.