 "manufacturer": "Yaskawa",
 "manufacturer_slug": "yaskawa",
 "model": "FP605 enclosed bypass (MEMOBUS/Modbus RTU)",
 "model_slug": "fp605-bypass",
 "short_model": "FP605 Bypass",
 "aliases": [
  "FP605 Enclosed Bypass",
  "FP605 bypass package"
 ],
 "equipment_type": "Variable frequency drive",
 "applies_to": "Yaskawa FP605 enclosed bypass packages using the bypass board RS-485 port (TB3) with H5-08 = 0 (MEMOBUS/Modbus); Technical Reference SIEPYAIF6B01C, section 10.6.",
 "summary": "Yaskawa's FP605 fan and pump drive packaged with a bypass contactor board. The bypass board's RS-485 port speaks MEMOBUS/Modbus RTU (or N2, P1, BACnet). Drive command and monitor registers start at 0001H and 0020H, and the bypass adds its own command word and digital I/O registers at 8400H-8403H. This map covers drive and bypass control, status, fault bits and the b1/H5/Z3-12 setup parameters.",
 "transport": [
  "RTU"
 ],
 "defaults": {
  "unit_id": 31,
  "baud": 9600,
  "parity": "None",
  "data_bits": 8,
  "stop_bits": 1,
  "tcp_port": null
 },
 "addressing": {
  "convention": "hex 0-based",
  "note": "Register numbers are hex and are sent unchanged: the manual's read example asks for starting register 0020H as bytes 00 20. Parameters use the hex number printed under each parameter (H5-01 = 0425H, Z3-12 = 850BH)."
 },
 "default_word_order": null,
 "firmware": null,
 "source": {
  "title": "FP605 Enclosed Bypass Technical Reference",
  "doc_number": "SIEPYAIF6B01C",
  "revision_date": null,
  "url": "https://www.yaskawa.com/delegate/getAttachment?documentId=SIEPYAIF6B01&cmd=documents&documentName=SIEPYAIF6B01.pdf",
  "pages": "b1 p. 151, H5 parameters pp. 285-289, Z3-12 in chapter 5; section 10.6 MEMOBUS/Modbus: Table 10.19 specs, function codes and read example pp. 727-729, Table 10.30 command data pp. 734-738, Table 10.31 monitor data pp. 739-742."
 },
 "notes": [
  "H5-08 defaults to 3 (BACnet) on this package; it must be set to 0 for Modbus.",
  "Frequency registers 0002H, 0023H and 0024H use the units chosen in o1-03, so they are left unscaled.",
  "Left out: 0007H/0008H analog outputs, 0025H output voltage (unit switched by H5-10), 0026H/0027H output current and power, 002DH and later monitors not checked row by row, the U-monitor, fault-trace and fault-description blocks from 0040H, 15FFH (no unit given), the clock registers 3004H-3030H and emergency-override registers 3A93H-3A96H.",
  "The command table prints run bits 0/1 with both meanings (forward run / run and reverse run / reverse) without naming the selecting parameter; on the drive this is H5-12, which is not in the bypass H5 list.",
  "Supported function codes are 03H, 08H, 10H, 5AH and 67H; there is no 06H, so use 10H even for a single register.",
  "With H5-11 = 0 (default), parameter writes take effect only after the Enter command (0900H or 0910H)."
 ],
 "registers": [
  {
   "table": "holding_register",
   "address": 1,
   "documented": "0001H",
   "name": "Run command / drive MFDI command",
   "description": "Bits 4-B drive the drive digital inputs when Z3-12 = 1.",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": {
    "0": "1 = forward run (or run), 0 = stop",
    "1": "1 = reverse run (or reverse), 0 = stop / forward",
    "2": "External fault EF0",
    "3": "Fault reset",
    "4": "Drive digital input bit 4 (Z3-12 = 1)",
    "5": "Drive digital input bit 5 (Z3-12 = 1)",
    "6": "Drive digital input bit 6 (Z3-12 = 1)",
    "7": "Drive digital input bit 7 (Z3-12 = 1)",
    "8": "Drive digital input bit 8 (Z3-12 = 1)",
    "9": "Drive digital input bit 9 (Z3-12 = 1)",
    "10": "Drive digital input bit 10 (Z3-12 = 1)",
    "11": "Drive digital input bit 11 (Z3-12 = 1)"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2,
   "documented": "0002H",
   "name": "Frequency reference",
   "description": "Unsigned; units set by o1-03.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 3,
   "documented": "0003H",
   "name": "Output voltage gain",
   "description": "20-2000 (2.0-200.0 %), 1000 at power-up.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "%",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 6,
   "documented": "0006H",
   "name": "PID setpoint",
   "description": "Signed; enable with 000FH bit 1.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "%",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 9,
   "documented": "0009H",
   "name": "MFDO setting",
   "description": "Drive the drive digital outputs from the network.",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": {
    "0": "Drive MFDO M1-M2",
    "1": "Drive MFDO M3-M4",
    "2": "Drive MFDO MD-ME-MF",
    "6": "Enable bit 7",
    "7": "Drive fault relay MA/MB-MC"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 13,
   "documented": "000DH",
   "name": "PI2 control setpoint",
   "description": "-100.00 to +100.00 %; enable with 000FH bit 4.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "%",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 15,
   "documented": "000FH",
   "name": "Command selection setting",
   "description": "Enables network setpoints and broadcast terminal inputs.",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": {
    "1": "PID target from Modbus",
    "4": "PI2 target from Modbus",
    "5": "PID feedback from Modbus (15FFH)",
    "12": "Broadcast terminal S5 input",
    "13": "Broadcast terminal S6 input",
    "14": "Broadcast terminal S7 input",
    "15": "Broadcast terminal S8 input"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 32,
   "documented": "0020H",
   "name": "Drive status 1",
   "description": "Covers drive and bypass.",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "0": "Drive run or bypass run",
    "1": "During reverse",
    "2": "System ready",
    "3": "Drive or bypass faulted",
    "4": "oPE fault on drive or bypass",
    "5": "MFDO M1-M2 on",
    "6": "MFDO M3-M4 on",
    "7": "MFDO MD-ME-MF on",
    "12": "Safe Torque OFF hardware",
    "13": "Safe Torque OFF",
    "14": "Bypass ComRef enabled",
    "15": "Bypass ComCtrl enabled"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 33,
   "documented": "0021H",
   "name": "Fault description 1",
   "description": "",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "0": "oC overcurrent / GF ground fault",
    "1": "ov overvoltage",
    "2": "oL2 drive overload",
    "3": "oH1 heatsink / oH2 external overheat",
    "7": "EF0-EF7 external fault",
    "8": "CPFxx hardware fault (incl. oFx)",
    "9": "oL1 motor overload, oL3/oL4 overtorque, UL3/UL4 undertorque",
    "10": "oS overspeed / dEv speed deviation",
    "11": "During Uv detection",
    "12": "Uv1/Uv2/Uv3 undervoltage",
    "13": "LF output / PF input phase loss",
    "14": "CE / bUS communication error",
    "15": "oPr keypad connection fault"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 34,
   "documented": "0022H",
   "name": "Fault contents (data link)",
   "description": "Errors from the last write.",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "0": "During data write / motor switching",
    "3": "Upper/lower limit fault",
    "4": "Data integrity fault",
    "5": "During EEPROM write"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 35,
   "documented": "0023H",
   "name": "U1-01 Frequency reference",
   "description": "Units set by o1-03.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 36,
   "documented": "0024H",
   "name": "U1-02 Output frequency",
   "description": "Units set by o1-03.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 41,
   "documented": "0029H",
   "name": "Fault description 2",
   "description": "",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "1": "GF ground fault",
    "2": "PF input phase loss",
    "3": "LF output phase loss",
    "6": "oH4 motor overheat fault (PTC)"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 42,
   "documented": "002AH",
   "name": "Minor fault description 1",
   "description": "Alarms that do not trip the drive.",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "2": "EF run command input error",
    "3": "bb baseblock",
    "4": "oL3 overtorque 1",
    "5": "oH heatsink overheat",
    "6": "ov overvoltage",
    "7": "Uv undervoltage",
    "9": "CE: running at H5-34 go-to frequency",
    "10": "bUS option communication error",
    "11": "UL3/UL4 undertorque",
    "12": "oH3 motor overheat (PTC)",
    "15": "CALL serial transmission error"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 43,
   "documented": "002BH",
   "name": "Drive input terminal status",
   "description": "",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "0": "Drive terminal S1 on",
    "1": "Drive terminal S2 on",
    "2": "Drive terminal S3 on",
    "3": "Drive terminal S4 on",
    "4": "Drive terminal S5 on",
    "5": "Drive terminal S6 on",
    "6": "Drive terminal S7 on",
    "7": "Drive terminal S8 on"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 44,
   "documented": "002CH",
   "name": "Drive status 2",
   "description": "",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "0": "During run",
    "1": "During zero speed",
    "2": "Speed agree",
    "3": "User-defined speed agree",
    "4": "Frequency detection 1",
    "5": "Frequency detection 2",
    "6": "Run ready",
    "7": "During low-voltage detection",
    "8": "During baseblock",
    "9": "Frequency reference mode (1 = not from communication option)",
    "10": "Run command mode (1 = not from communication option)",
    "11": "Over/undertorque 1/2 detected",
    "12": "Frequency reference loss",
    "13": "Auto-restart in progress",
    "14": "Fault",
    "15": "Modbus communication timeout"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 384,
   "documented": "0180H",
   "name": "b1-01 Frequency reference selection 1",
   "description": "Set 2 for a serial frequency reference.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Keypad",
    "1": "Analog input",
    "2": "Serial communications",
    "3": "Option PCB"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 385,
   "documented": "0181H",
   "name": "b1-02 Run command selection 1",
   "description": "Set 2 to take Run from serial.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Keypad",
    "1": "Digital input",
    "2": "Serial communications",
    "3": "Option PCB"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1061,
   "documented": "0425H",
   "name": "H5-01 Drive node address",
   "description": "Default 1FH; range depends on protocol.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1062,
   "documented": "0426H",
   "name": "H5-02 Communication speed selection",
   "description": "Default 3.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "1200 bps",
    "1": "2400 bps",
    "2": "4800 bps",
    "3": "9600 bps",
    "4": "19.2 kbps",
    "5": "38.4 kbps",
    "6": "57.6 kbps",
    "7": "76.8 kbps",
    "8": "115.2 kbps"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1063,
   "documented": "0427H",
   "name": "H5-03 Communication parity selection",
   "description": "Default 0.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "No parity",
    "1": "Even parity",
    "2": "Odd parity"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1064,
   "documented": "0428H",
   "name": "H5-04 Communication error stop method",
   "description": "Default 3.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Ramp to stop",
    "1": "Coast to stop",
    "2": "Fast stop (C1-09)",
    "3": "Alarm only",
    "4": "Run at H5-34 (CE go-to frequency)"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1065,
   "documented": "0429H",
   "name": "H5-05 Comm fault detection selection",
   "description": "Default 1.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Disabled",
    "1": "Enabled"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1066,
   "documented": "042AH",
   "name": "H5-06 Drive transmit wait time",
   "description": "0-65 ms, default 5 ms.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "ms",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1077,
   "documented": "0435H",
   "name": "H5-09 CE detection time",
   "description": "0.0-10.0 s, default 2.0 s.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "s",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1078,
   "documented": "0436H",
   "name": "H5-10 Modbus register 0025H unit selection",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "0.1 V units",
    "1": "1 V units"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1084,
   "documented": "043CH",
   "name": "H5-11 Comm ENTER command mode",
   "description": "Default 0.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "ENTER command required",
    "1": "ENTER command not required"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1581,
   "documented": "062DH",
   "name": "H5-08 Communication protocol selection",
   "description": "Default 3 (BACnet); set 0 for Modbus.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Modbus/MEMOBUS",
    "1": "Metasys N2",
    "2": "APOGEE P1",
    "3": "BACnet"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2304,
   "documented": "0900H",
   "name": "Enter command (save to EEPROM)",
   "description": "Write 0 to store written parameters.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "W",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2320,
   "documented": "0910H",
   "name": "Enter command (RAM only)",
   "description": "Write 0 to apply written parameters without saving.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "W",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2903,
   "documented": "0B57H",
   "name": "H5-20 Communication parameters reload",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Reload at next power cycle",
    "1": "Reload now"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 33792,
   "documented": "8400H",
   "name": "Bypass command word",
   "description": "",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": {
    "3": "Remote transfer",
    "4": "Emergency override bypass",
    "5": "Emergency override (FWD)",
    "6": "Motor OR",
    "7": "Motor AND",
    "11": "Drive select (Z1-39)",
    "12": "Bypass select (Z1-39)",
    "13": "Fault reset",
    "14": "EFB",
    "15": "Emergency override drive (REV)"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 33794,
   "documented": "8402H",
   "name": "Bypass MFDI command",
   "description": "Bypass digital inputs TB2-1..8 when Z3-12 = 1.",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": {
    "0": "Bypass digital input 1 (TB2-1)",
    "1": "Bypass digital input 2 (TB2-2)",
    "2": "Bypass digital input 3 (TB2-3)",
    "3": "Bypass digital input 4 (TB2-4)",
    "4": "Bypass digital input 5 (TB2-5)",
    "5": "Bypass digital input 6 (TB2-6)",
    "6": "Bypass digital input 7 (TB2-7)",
    "7": "Bypass digital input 8 (TB2-8)"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 33795,
   "documented": "8403H",
   "name": "Bypass MFDO command",
   "description": "Bypass outputs whose Z2-xx function is 99 (not used).",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": {
    "6": "Digital output 7 (TB1 1-3)",
    "7": "Digital output 8 (TB1 4-6)",
    "8": "Digital output 9 (TB1 7-9)",
    "9": "Digital output 10 (TB1 10-12)"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 34059,
   "documented": "850BH",
   "name": "Z3-12 Network digital inputs",
   "description": "Enables 0001H bits 4-B and 8402H.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Disabled",
    "1": "Enabled"
   },
   "bits": null,
   "offset": 0
  }
 ],
 "integration": {
  "summary": "Set H5-08 = 0, H5-01..H5-03 and cycle power (or H5-20 = 1); set b1-01 = 2 and b1-02 = 2 for serial reference and run. Write 0001H and 0002H with function 10H, use 8400H for drive/bypass selection and emergency override, and poll 0020H, 0021H and 002CH.",
  "minimum_registers": [
   {
    "table": "holding_register",
    "address": 1,
    "why": "Run/stop, direction, fault reset"
   },
   {
    "table": "holding_register",
    "address": 2,
    "why": "Frequency reference (o1-03 units)"
   },
   {
    "table": "holding_register",
    "address": 33792,
    "why": "Bypass command word (drive/bypass select)"
   },
   {
    "table": "holding_register",
    "address": 32,
    "why": "Drive/bypass status 1"
   },
   {
    "table": "holding_register",
    "address": 33,
    "why": "Fault description 1"
   },
   {
    "table": "holding_register",
    "address": 36,
    "why": "U1-02 output frequency"
   },
   {
    "table": "holding_register",
    "address": 44,
    "why": "Drive status 2 incl. comm timeout"
   }
  ],
  "enable": "H5-08 = 0 selects Modbus (default 3 = BACnet). Set H5-01 address (default 1FH), H5-02 speed (default 3 = 9600 bps), H5-03 parity (default 0 = none), then cycle power or set H5-20 = 1. Set b1-01 = 2 and b1-02 = 2 for serial control; Z3-12 = 1 lets 0001H bits 4-B and 8402H drive the digital inputs.",
  "watchdog": "H5-05 = 1 (default) enables CE detection after H5-09 (0.0-10.0 s, default 2.0 s); H5-04 sets the reaction (0 ramp, 1 coast, 2 fast stop, 3 alarm only - default, 4 run at H5-34 with H5-35 as an optional timeout). Drive status 2 (002CH) bit F shows a timeout.",
  "quirks": [
   "Registers are hex and 0-based: 0020H is sent as 00 20.",
   "No function 06H; use 10H.",
   "8403H bits only act on outputs whose Z2-xx function is 99 (not used)."
  ],
  "setup": [
   "RS-485 on bypass terminal TB3; 8 data bits fixed.",
   "Enable the RS-485 termination resistor (bypass board DIP switch, see the switch table) only on the bypass at the end of the line."
  ],
  "gotchas": [
   "Out of the box the bypass talks BACnet (H5-08 = 3), not Modbus.",
   "With Z3-12 = 0 (default) the network digital-input bits are ignored."
  ]
 },
 "page": "https://easymodbus.com/modbus-register-maps/yaskawa/fp605-bypass",
 "address_note": "address = 0-based Modbus wire (PDU) address; documented = as printed in the source.",
 "note": "Re-typed from the manufacturer's public documentation (see source) and verified against it. Registers vary by firmware and options; verify against the live device before writing."
}